Item No.:
22
|
|
Site:
Buffet-Terrace - Dishwashing
|
|
Violation:
A long curtain was incorrectly installed between the wash section and the final rinse section of the dishwashing machine. It blocked the upper final rinse spray pattern for the dishes passing underneath the final rinse. The short curtain was installed at the exit of the final rinse section.
|
|
Recommendation:
Ensure a warewashing machine is operated in accordance with the manufacturer?s instructions.
|
|
|
Item No.:
23
|
|
Site:
Buffet-Terrace - Dishwashing
|
|
Violation:
The wash solution temperature was taken 3 times in the tank and it was reading from 129°-132°F. The machine data plate indicated that acceptable minimum wash temperature for this type of machine is 160°F. The indicator thermometer also read consistently 132°F.
|
|
Recommendation:
Ensure the temperature of the wash solution in spray type warewashers that use hot water to sanitize is not less than: (3) 71°C (160°F) for a single-tank, conveyor, dual-temperature machine.
|
|
|
Item No.:
20
|
|
Site:
Buffet-Terrace - Hamburger Grill
|
|
Violation:
A tip-sensitive thermometer was not provided to the food preparation staff in charge of cooking the hamburgers.
|
|
Recommendation:
Use tip-sensitive temperature-measuring devices, such as a thermocouple or thermistor, for measuring thin food products.
|
|
|
Item No.:
34
|
|
Site:
Provisions-Fish Freezer
|
|
Violation:
Ice was forming on the sprinkler heads and on the deck below them in the fish freezer. Water was pooled in the light fixture adjacent to the freezers evaporator unit. These findings indicated a possible water leak in the deckhead space above this room. No food was impacted by this potential source of contamination.
|
|
Recommendation:
Ensure a plumbing system in a food area is maintained in good repair.
|
|
|
Item No.:
22
|
|
Site:
Galley-Dish Washing
|
|
Violation:
A long curtain was incorrectly installed between the wash section and the final rinse section of the dishwashing machine. It blocked the upper final rinse spray pattern for the dishes passing underneath the final rinse. The short curtain was installed at the exit of the final rinse section.
|
|
Recommendation:
Ensure a warewashing machine is operated in accordance with the manufacturer?s instructions.
|
|
|
Item No.:
22
|
|
Site:
Galley-Dish Washing
|
|
Violation:
Warewash racks were being loaded with the dishes parallel to the spray patterns in the machine, minimizing the ware's exposure to the wash, rinse and sanitizing cycle sprays.
|
|
Recommendation:
Ensure soiled items to be cleaned in a warewashing machine are loaded into racks in a position that (1) exposes the items to the unobstructed spray from all cycles. Ensure a warewashing machine is operated in accordance with the manufacturer?s instructions.
|
|
|
Item No.:
36
|
|
Site:
Bar-Martini Bar Pantry
|
|
Violation:
Lighting levels were less than 110 lux around the ice machine sides and back.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
36
|
|
Site:
Housekeeping-Deck 4 Starboard Pantry
|
|
Violation:
Lighting levels were less than 110 lux around the ice machine sides and back.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Tank Maintenance
|
|
Violation:
Potable Water Tanks FW 2112 underwent maintenance on 7 December 2012. There were notations that the tank was super chlorinated and that it was put back in service. However, there was no written documentation on the free halogen residual level before the tank was put back in service. In addition, it was touched-up with an approved coating system but there was no written documentation of approval from a certification organization independent of the coating manufacturer.
|
|
Recommendation:
Maintain documentation of all inspections, maintenance, cleaning, and disinfection for 12 months and ensure it is available for review during inspections. Ensure records include a method of disinfection, concentration and contact time of the disinfectant, and a halogen value of less than or equal to 5 ppm before the tank is put back into service.
Document the free halogen residual level. Ensure the interior coatings on potable water tanks are approved for potable water contact by a certification organization. Follow all manufacturers? recommendations for application, drying, and curing. For the tank coatings used, maintain the following onboard: (1) written documentation of approval from the certification organization (independent of the coating manufacturer).
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Flow Meters
|
|
Violation:
Flow meters were not installed on the RWFs. This was noted in the previous inspection. Work is to be completed by April 2013.
|
|
Recommendation:
Design recirculation systems and equipment to maintain adequate water chemistry control while operating at the following minimum turnover rates: (1) swimming pool (VSP 2005 Construction Guidelines or earlier): 6 hours; and (5) whirlpool spa: 0.5 hours.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-
|
|
Violation:
The turnover rates and bather loads for all RWFs were calculated using the manufacturer's flow rate of the pumps and not actual flow rates measured by flow meters.
|
|
Recommendation:
Design recirculation systems and equipment, including filter, and pumps to maintain adequate water chemistry control while operating at the following minimum turnover rates: (1) swimming pool (VSP 2005 Construction Guidelines or earlier): 6 hours; and (5) whirlpool spa: 0.5 hours.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Water Chemistry
|
|
Violation:
Flow rates, combined chlorine, and total alkalinity were not monitored. The staff had an appropriate test kit that could measure these parameters. This was noted in the previous inspection.
|
|
Recommendation:
Monitor and adjust the RWF?s flow rates, free and combined halogen levels, pH, total alkalinity, and clarity as recommended by the manufacturer and to maintain optimum public health protection and water chemistry.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Analyzer Chart Recorders
|
|
Violation:
The sample lines for the analyzer chart recorders for the whirlpools and Thalasso spa pool were located after the compensation tanks. Work is to be completed by April 2013.
|
|
Recommendation:
Ensure the sample line for the analyzer probe (monitoring) is either directly from the RWF or on the return line from each RWF and before the compensation tank.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Safety Signs
|
|
Violation:
The safety signs at the RWFs were the same for whirlpools, spa pool, and pool and had confusing information on the bather load for whirlpool/spas. The signs had a bather load of 8 persons for whirlpools and 7 persons for spa Jacuzzis. The staff explained that the ship does not have Jacuzzis in the spa and 8 persons is the actual bather load for the whirlpools.
|
|
Recommendation:
Ensure the signs, at a minimum, include the following words: (4) bather load #.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Whirlpool Bather Loads
|
|
Violation:
The calculated bather load for the whirlpools was 4 persons but the safety signs stated a bather load of 8 persons.
|
|
Recommendation:
Maintain documentation on the maximum bather load for each RWF. Ensure the maximum bather load is based on the following factor: one person per five gallons (19 liters) per minute of recirculation flow. Ensure the signs, at a minimum, include the following words: (4) bather load # (that matches maximum or less from above calculation based on actual flow rate of the whirlpool spa.)
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Sand Filters
|
|
Violation:
The sand was changed in December 2012 but there was no documentation stating that the filter housing was cleaned, rinsed, and disinfected before the new filter media was placed in it.
|
|
Recommendation:
Change granular filter media for whirlpool spas and spa pools based on the inspection and sedimentation test results or every 12 months, whichever is more frequent. For all other RWFs, change granular filter media based on the inspection and sedimentation results or per the manufacturer?s recommendations, whichever is more frequent. Record the results of both the filter inspection and sedimentation test.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Distillate Water Lines
|
|
Violation:
The distillate water lines from the evaporators to the potable water halogenation station were not striped or painted in accordance with ISO 14726 standards (blue/gray/blue).
|
|
Recommendation:
Stripe or paint distillate and permeate lines directed to the potable water system in accordance with ISO 14726 (blue/gray/blue).
|
|
|
Item No.:
03
|
|
Site:
Potable Water-Production
|
|
Violation:
During 12 - 17 November 2012, the ship produced water in the Amazon River every day.
|
|
Recommendation:
Operate a reverse osmosis unit, distillation plant, or other process that supplies water to the vessel?s potable water system only while the vessel is making way, and do not operate in polluted areas, harbors, or at anchor.
|
|