Item No.:
08
|
|
Site:
Potable Water-Cross-connection Control Log
|
|
Violation:
Two vacuum air breakers installed on the shower hose line at both showers were not listed on the cross-connection control log.
|
|
Recommendation:
Ensure the cross-connection control program includes at a minimum: a complete listing of cross-connections and the backflow prevention method or device for each, so there is a match to the plumbing system component and location. Ensure a schedule for inspection frequency is set. Maintain a log documenting the inspection and maintenance in written or electronic form, and ensure it is available for review during inspections.
|
|
|
Item No.:
05
|
|
Site:
Potable Water-Far Point
|
|
Violation:
The free residual chlorine level measured at the far point by the electronic halogen analyzer was not accurate to at least 0.2 ppm when compared with manual tests. During manual testing, the analyzer showed readings between 0.9 ppm and 1.0 ppm. Four manual tests were taken with two different inspector test kits which measured readings between 0.46 ppm and 0.57 ppm. Several tests by the crew's test kit which was also being used to calibrate the analyzer, measured readings identical to the electronic analyzer, 0.9 - 1.0 ppm. A second, but similar crew test kit was brought in and measured 0.6 ppm. The secondary standards for the test kit being used by the crew to calibrate the far point analyzer was only for High-Range values and not for Mid-Range, therefore, it could not be determined that the instrument being used to calibrate the far point analyzer was accurate. It was also noted that the crew member preforming the calibration was using a glass 10ml sample bottle rather than a plastic sample bottle. When a plastic 10ml sample bottle was used, instrument agreement between all kits was achieved. The instruction manual for this machine did not indicate which type of bottle to use nor could the staff identify which type of bottle was originally issued with the test kit.
|
|
Recommendation:
Ensure the free residual halogen measured by the halogen analyzer is within 0.2 mg/L (ppm) of the free residual halogen measured by the manual test.
|
|
|
Item No.:
06
|
|
Site:
Potable Water-Secondary Standards
|
|
Violation:
No Mid-Range secondary standards were on board to verify the accuracy of the crew's electronic test kit.
|
|
Recommendation:
Where available, maintain appropriate secondary standards onboard for electronic test kits to verify test kit operation.
|
|
|
Item No.:
44
|
|
Site:
Potable Water-Electronic Test Kits
|
|
Violation:
Staff conducting potable water test were not completely knowledgeable in the specifications and the instructions on how to use their electronic test kits.
|
|
Recommendation:
Ensure the supervisor or person in charge of potable water operations on the vessel demonstrates to VSP?during inspections and on request-knowledge of potable water operations, is able to demonstrate this knowledge by compliance with Section 5 of the VSP 2011 Operations Manual or by responding correctly to the inspector?s questions as they relate to the specific operation, and properly trains employees to comply with Section 5 of the VSP 2011 Operations Manual as it relates to their assigned duties.
|
|
|
Item No.:
*
|
|
Site:
Recreational Water Facilities-Chart Recorders
|
|
Violation:
The range of the electronic chart recorders being used for all the RWFs was from 0-100 ppm.
|
|
Recommendation:
Use chart recorders that have a practical mg/l (ppm) range.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Hair and Lint Strainer and Filter Housing
|
|
Violation:
No documentation was available for the CT value being used to disinfect the hair and lint strainers/housings as well as the cartridge filter housings for the three whirlpools. No documentation was available for the swimming pool's hair and lint strainer/housing and cartridge filter housing being disinfected.
|
|
Recommendation:
Clean, rinse, and disinfect the filter housing before the new filter media is placed in it. Ensure disinfection is accomplished with an appropriate halogen-based disinfectant. At a minimum, use a 50-ppm solution for 1 minute, or equivalent CT value. Maintain records on all inspection and cleaning procedures. Clean, rinse, and disinfect the hair and lint strainer and hair and lint strainer housing on all RWFs weekly. Ensure disinfection is accomplished with an appropriate halogen-based disinfectant. At a minimum, use a 50-ppm solution for 1 minute, or equivalent CT value. Maintain records on all inspection and cleaning procedures.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Total Alkalinity
|
|
Violation:
No test kit was available to test for total alkalinity.
|
|
Recommendation:
Ensure a test kit is available for testing water quality parameters, including free and total halogen levels (chlorine and bromine, where applicable), pH, and total alkalinity. Ensure that test kits are accurate to within 0.2 mg/L (ppm) for halogen and have a testing range of free residual halogen normally maintained in the RWF. Ensure test kits for pH are accurate to within 0.2. Ensure all reagents are not past their expiration dates.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Flow Meters
|
|
Violation:
Flow meters were not installed on any of the RWFs. The turnover rates and bather loads were being calculated by the manufacturer's theoretical pump curve.
|
|
Recommendation:
Maintain documentation on the maximum bather load for each RWF. Ensure the maximum bather load is based on the following factor: one person per five gallons (19 liters) per minute of recirculation flow. Use flow rates from flow meters to calculate bather loads. Do not use the manufacturer?s pump rate to calculate bather loads. Monitor and adjust the RWF?s flow rates as recommended by the manufacturer and to maintain optimum public health protection and water chemistry.
|
|
|
Item No.:
19
|
|
Site:
Provisions-Meat Freezer
|
|
Violation:
Water leaks were observed from multiple points in the deckhead seams and at the plastic deckhead panel attachment points in the left portion of the freezer. Ice was noted below the these leaks on many parts of the deck and pallets in the empty areas of the freezer. Along the left bulkhead, larger water leaks were noted coming from vent holes and seams which covered the food cartons on the top two shelves with thick layers of ice. All affected food was discarded.
|
|
Recommendation:
Protect food from contamination by storing the food: (2) In a clean, dry location; and (3) Where it is not exposed to splash or other contamination.
|
|
|
Item No.:
15
|
|
Site:
Provisions-Dry Stores
|
|
Violation:
Rusty end seams were noted on several cans of pineapple and on one can of ketchup. Dented end seams were found on a can of plum tomatoes and a can of mushrooms. A wet and moldy carton containing cans of food was also observed. All affected food found was discarded.
|
|
Recommendation:
Ensure food is safe and unadulterated.
|
|
|
Item No.:
33
|
|
Site:
Provisions-Dry Stores
|
|
Violation:
Heavy soil was noted around and under a pallet placed in a corner on the right side of the dry stores room between two fixed shelves.
|
|
Recommendation:
Ensure decks in food storage areas are cleaned as often as necessary.
|
|
|
Item No.:
21
|
|
Site:
Preparation Room-
|
|
Violation:
The electrical connection conduit to the large floor-mounted mixer was disconnected from the mixer creating an opening to the interior of the bulkhead.
|
|
Recommendation:
Ensure nonfood contact equipment is maintained in good repair and proper adjustment including: (1) Equipment maintained in a state of repair and condition that meets the materials, design, construction, and operation specifications of these guidelines.
|
|
|
Item No.:
33
|
|
Site:
Preparation Room-Food Lift
|
|
Violation:
The deck and sides of the 'not often used' dumbwaiter type food lift was soiled with food debris. This was immediately cleaned while the inspection team was still in the prep area.
|
|
Recommendation:
Ensure decks in food areas are cleaned as often as necessary.
|
|
|
Item No.:
37
|
|
Site:
Galley-Dishwashing
|
|
Violation:
Excessive steam was coming from the middle door to the conveyor dishwasher and condensing on the deckhead. Condensate was dripping from the deckhead and from the side of the ventilation extraction canopy above this machine. No clean dishware was being impacted at the time of the inspection.
|
|
Recommendation:
Ensure ventilation hood systems and devices operate effectively to prevent condensate from collecting on the deckheads and remove contaminants generated by equipment located under them.
|
|
|
Item No.:
26
|
|
Site:
Galley-Ice Machine
|
|
Violation:
Mold was noted on the plastic chute from the cuber to the ice storage bin. The ice machine was taken out of service, emptied and cleaning commenced while the inspection team was in the area. Other food area ice machines were checked during the inspection and the plastic chutes were completely clean.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
16
|
|
Site:
Galley-Hot Galley
|
|
Violation:
A large pan of cooked, sliced and whole roast beef had an internal temperature of 48°- 52°F in an undercounter reach-in cooler. Four large pans of raw beef and pork in the same compartment had internal temperatures of 50° - 52°F. These pans of food were immediately discarded by the ship's staff,
|
|
Recommendation:
Maintain potentially hazardous foods at 5°C (41°F) or less.
|
|
|
Item No.:
18
|
|
Site:
Galley-Hot Galley
|
|
Violation:
A large pan of raw pork was stored on a shelf above the pan of cooked roast beef as noted in the reach-in cooler previously identified.
|
|
Recommendation:
Protect food from cross-contamination or other sources of contamination by the following methods: (2) Separating types of raw animal foods from each other such as beef and pork during storage by arranging each type of food in equipment so that cross-contamination of one type with another is prevented.
|
|
|
Item No.:
20
|
|
Site:
Galley-Hot Galley
|
|
Violation:
The metal food guide attached to the lid of the vertical food processor was severely scored with blade nicks making it difficult to clean. The plastic blade mounting assembly was also severely scratched and difficult to clean. The white plastic was also very stained making it difficult to determine if it was clean.
|
|
Recommendation:
Food contact equipment must be maintained in good repair and proper adjustment: (1) Equipment must be maintained in a state of repair and condition that meets the materials, design, construction, and operating specifications of these guidelines.
|
|
|
Item No.:
08
|
|
Site:
Galley-Signatures Restaurant
|
|
Violation:
The backflow preventer on the water supply for the coffee machine had a constant leak from the air relief vent indicating a possible failure. Water was puddled on the counter under the backflow preventer. Ship staff replaced this backflow preventer while the inspection team was still in the area.
|
|
Recommendation:
Maintain backflow prevention devices in good repair.
|
|
|
Item No.:
19
|
|
Site:
Bar-Mariner Lounge
|
|
Violation:
The ice scoop handle was touching the ice in the ice bin. The ice bin lid was open in the open bar counter.
|
|
Recommendation:
During pauses in food dispensing, ensure utensils are stored: (1) In the food with their handles above the top of the food; and (5) In a clean, protected location (if the utensils, such as ice scoops, are used only with a food that is not potentially hazardous. Protect food from contamination by storing the food: (1) Covered or otherwise protected.
|
|
|
Item No.:
31
|
|
Site:
Bar-Mariner Lounge
|
|
Violation:
The sanitizer strength in the wiping cloth storage bucket far exceeded 200 PPM of free residual chlorine. This solution was immediately changed to one that measured an appropriate 100 PPM.
|
|
Recommendation:
Ensure chemical sanitizers and other chemical antimicrobials applied to food-contact surfaces meet the requirements specified in 21 CFR 178.1010 Sanitizing Solutions.
|
|