Item No.:
09
|
|
Site:
Recreational Water Facilities-
|
|
Violation:
On 3 March, the starboard whirlpool spa was open all day and the halogen analyzer-chart recorder charts indicated the chlorine levels were less than 3 ppm and the pH was 8.0 or above. On 8 March, the starboard whirlpool spa was open from 01:02 - 08:09 and the values recorded on the halogen analyzer-chart recorder chart were 2.0 ppm, however the manual readings stated 4 ppm. Also, on 9 March, the chlorine residual levels were approximately 2.0 ppm and less than 3.0 ppm from 02:30 - 13:30 p.m. for the starboard whirlpool spa. This spa was never closed and there was no clarifications of discrepancies for these levels.
|
|
Recommendation:
Maintain a free residual halogen in recirculated RWFs in the following ranges: (6) whirlpool spas and spa pools, between 3.0 and 10.0 mg/L (ppm) free chlorine or between 4.0 and 10.0 mg/L (ppm) bromine. Maintain the pH level in all RWFs between 7.0 and 7.8. Immediately close facilities if these halogen and pH ranges are not maintained.
|
|
|
Item No.:
36
|
|
Site:
Provisions-Liquor 2d060
|
|
Violation:
The light intensity was less than 110 lux in the area near the evaporator. Boxes of liquor were stored in this area. The company's Public Health Director stated the ship had been approved for an extension until 30 April for lighting upgrades.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning.
|
|
|
Item No.:
33
|
|
Site:
Galley-Vegetable Preparation
|
|
Violation:
Below technical compartment 4.22, a deck tile was broken and missing a large corner piece.
|
|
Recommendation:
Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
|
|
|
Item No.:
26
|
|
Site:
Galley-Hot Section
|
|
Violation:
A few soiled plates were stored above the far left bain marie. The area was not in operation at the time of the inspection. The plates were taken to the dishwash area.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
22
|
|
Site:
Galley-Dishwash
|
|
Violation:
Large food particles were in the wash basket of the in-use dishwash machine.
|
|
Recommendation:
Ensure warewashing machines, drainboards, and the compartments of sinks, basins, or other receptacles used for washing and rinsing equipment, utensils, or raw foods, or laundering wiping cloths are cleaned: (1) before use; (2) throughout the day at a frequency necessary to prevent recontamination of equipment and utensils and to ensure that the equipment performs its intended function; (3) at least every 24 hours (if used).
|
|
|
Item No.:
21
|
|
Site:
Other-Coffee Station for Discoveries Restaurant
|
|
Violation:
Two cords from the water purification unit to the carbon dioxide machine were draped across the counter top, making cleaning difficult.
|
|
Recommendation:
Remove the cords from the counter top.
|
|
|
Item No.:
27
|
|
Site:
Other-Coffee Station for Discoveries Restaurant
|
|
Violation:
At the two flat grills, the grease pan housings and the underside of the grease pans were soiled. The area was not in operation at the time of the inspection.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
22
|
|
Site:
Galley-Dishwash
|
|
Violation:
The in-use conveyor dishwash machine was not operating properly and as a result there was excess condensation in the final compartment below the blower. Condensation was dripping onto the clean dishes.
|
|
Recommendation:
Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines.
|
|
|
Item No.:
22
|
|
Site:
Galley-Dishwash
|
|
Violation:
When not used with the proper rack, plastic cups were coming out of the dishwash machine fallen over and right-side up. This prohibited proper washing and sanitizing of the cups. The cups were then repositioned on an appropriate rack and sent through the dishwash machine again for proper washing and sanitizing.
|
|
Recommendation:
Ensure items are placed in the proper rack in the dishwash machine so they can be properly washed and sanitized.
|
|
|
Item No.:
19
|
|
Site:
Buffet-Beverage Stations
|
|
Violation:
Stacks of saucers out for passenger self service were not inverted or covered. This was corrected.
|
|
Recommendation:
Ensure that dishware, glassware, and utensils out for service are inverted or covered.
|
|
|
Item No.:
19
|
|
Site:
Buffet-Beverage Stations
|
|
Violation:
The food contact portion of the small spoons out for self service were not protected.
|
|
Recommendation:
During service, ensure the food contact portion of each self-service food dispensing utensil is covered or located beneath shielding.
|
|
|
Item No.:
33
|
|
Site:
Buffet-
|
|
Violation:
There was no bulkhead/deck or cabinet/deck coving on the worker side of the service line.
|
|
Recommendation:
Cove all bulkhead/deck, equipment/deck, cabinet/deck, and deck sink coaming/deck junctures (including galleys, pantries, buffets, bars, waiter stations, dining room work counters, provisions, food storage rooms, equipment/utensil storage rooms, and toilet rooms intended for use by galley personnel).
|
|
|
Item No.:
33
|
|
Site:
Buffet-
|
|
Violation:
There was missing deck tile grout at the cabinet/deck juncture of the service line. A small amount of water had pooled in some of these areas from cleaning operations.
|
|
Recommendation:
Repair the deck tile grout.
|
|
|
Item No.:
11
|
|
Site:
Medical-Crew Member Reporting
|
|
Violation:
A food worker had an onset of AGE symptoms on 9 March at 09:00, but did not report to the medical center until 10 March at 08:56. According to their time card, this crew member worked on 9 March from 06:58 - 11:37 and on 10 March from 05:30 - 06:58.
|
|
Recommendation:
When food employees meet the case definition for AGE, ensure the following actions are taken: (1) isolate in cabin or designated restricted area until symptom-free for a minimum of 48 hours; (2) follow-up with and receive approval by designated medical personnel before returning crew to work; (3) document date and time of last symptom and clearance to return to work. Exclude food employees suspected of, diagnosed with, or exposed to any communicable disease caused by Salmonella typhi, Shigella spp., E. coli O157:H7, hepatitis A virus, norovirus, or other communicable diseases that can be transmitted by food, from working in any food or food related areas or operations, including working with exposed food, warewashing, equipment, utensils, table linens, single-service articles and single-use articles. Do not allow the excluded individual to return to the above duties until they are symptom free for a minimum of 48 hours.
|
|
|
Item No.:
02
|
|
Site:
Medical-Crew Member Close Contacts
|
|
Violation:
There were no close contacts documented for a food worker that had an onset of AGE symptoms on 9 March. According to the staff, this crew member had a close contact, but technical problems prevented them from entering the information into the STARDOCS medical surveillance system. A crew member with an onset of AGE on 15 February had a passenger listed as their immediate contact, but upon discussion with the medical staff, their immediate contact was actually a crew member. The interview for this close contact was documented in the food worker's medical paperwork.
|
|
Recommendation:
When any crew member (food or nonfood employee) meets the case definition for AGE, take the following actions: (3) complete a verbal interview daily with medical or supervisory staff until 48 hours after the ill crew members' symptoms began. Ensure that the first verbal interview is conducted within 8 hours from the time the ill crew member initially reported to the medical staff. If the asymptomatic immediate contact or cabin mate is at work, ensure that he or she must is contacted by medical or supervisory staff as soon as possible. Document the date and time of verbal interviews. Ensure the records for an AGE close contact are accurate and complete, without conflicting information or discrepancies.
|
|
|
Item No.:
02
|
|
Site:
Medical-Reportable Diarrhea Definition
|
|
Violation:
A food worker had one diarrhea episode within 24 hours, stomach cramps, and muscle aches, but was listed on the AGE log as nonreportable. The medical staff were unaware of the new diarrhea definition in the 2011 VSP Operations Manual. According to the documentation, this individual was isolated for 48 hours as a precaution. Another food worker had an onset of AGE symptoms on 13 February. Their last symptoms were on 15 February at 09:00. Their symptoms included one diarrhea episode within 24 hours and stomach cramps, but they were listed on the AGE log as nonreportable. The underlying illness on the AGE log was recorded as 'nil of note'. According to the doctor, this crew member was thought to have faked their illness, but this was not documented. The crew member was only isolated for 24 hours and according to their time card, they worked several hours on 16 and 17 February. A nonfood worker had an onset of AGE symptoms on 15 February at 02:00, including two diarrhea episodes within 24 hours and stomach cramps. The underlying illness on the AGE surveillance log stated 'nil of note'. According to staff, this crew member's symptoms were thought to be caused by antibiotics, but this was not documented. This crew member had left the ship and their work record was not available.
|
|
Recommendation:
Ensure a reportable case of AGE is a case reported to the master of the vessel, the medical staff, or other designated staff by a passenger or a crew member and meets the case definition based on the following symptoms: (1) Diarrhea (three or more episodes of loose stools in a 24 hour period or what is above normal for the individual. See section 4.1.2.1.3, illness symptoms); or (2) vomiting and one additional symptom including one or more episodes of loose stools in a 24-hour period, or abdominal cramps, or headache, or muscle aches, or fever (temperature of greater than or equal to 38°C [100.4°F]).
|
|
|
Item No.:
02
|
|
Site:
Medical-AGE Surveillance Log
|
|
Violation:
On 10 March, a passenger with four diarrhea episodes within 24 hours was recorded as nonreportable on the AGE log. Diabetes Type II was recorded as the underlying illness on the AGE log, but upon further discussion with medical staff, diverticulitis was the true cause of the diarrhea and why this case was not reportable.
|
|
Recommendation:
Ensure the records for an AGE case are accurate and complete, without conflicting information or discrepancies.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Striping
|
|
Violation:
The distillate line from the evaporators was not striped blue/gray/blue to the production chlorine injection point.
|
|
Recommendation:
Stripe or paint distillate and permeate lines directed to the potable water system in accordance with ISO 14726 (blue/gray/blue). Ensure no other lines have the above color designations. Stripe or paint these lines at 5 meters (15 feet) intervals and on each side of partitions, decks, and bulkheads, except where decor would be marred by such markings, including potable water supply lines in technical lockers.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Cross-Connection Control Log
|
|
Violation:
The specific plumbing components that contained backflow prevention devices were not mentioned in several areas of the cross-connection control log, including the deck 8 starboard hot and cold water lines, the deck 7 spa room water hose, the air gap for the technical water backflow on deck 1, and the air gap for the mineralizer. It was difficult getting information from staff on these devices due to the limited information.
|
|
Recommendation:
Ensure the cross-connection control program includes at a minimum: a complete listing of cross-connections and the backflow prevention method or device for each, so there is a match to the plumbing system component and location. Include air gaps on the listing. Ensure a schedule for inspection frequency is set. Maintain a log documenting the inspection and maintenance in written or electronic form, and ensure it is available for review during inspections.
|
|
|
Item No.:
06
|
|
Site:
Potable Water-Far Point Calibration
|
|
Violation:
The far point halogen analyzer-chart recorder charts were not initialed and the calibration verification was not documented on the charts from 15 February - 3 March or on 6 March.
|
|
Recommendation:
Change, initial, and date halogen analyzer-chart recorder charts daily. Ensure the charts contain notations of any unusual events in the potable water system. Record the daily manual comparison test or calibration either on the recorder chart or in a log.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Shock Halogenation
|
|
Violation:
There was no shock halogenation documented on 10 March for the port whirlpool spa. Also, for this whirlpool, the same values of 4 ppm and 5 ppm for the start of shocking and 10 ppm at the end of shocking were recorded and repeated every single day with no variation. It could not be verified that shocking occurred on these days. There was no shock halogenation documented on the starboard whirlpool spa on 18 February - 5 March or on 10 March. Also, from 6 March - 9 March and on 11 March, the shock halogenation was documented as having a starting value of 4.0 ppm and an ending value of 10.0 ppm every day with no variation. It could not be verified that shock halogenation occurred at all during these times.
|
|
Recommendation:
Increase the free residual halogen to at least 10.0 mg/L (ppm) and circulate for at least 1 hour every 24 hours. Test the free residual halogen both at the start and completion of shock halogenation. Superhalogenate the water in the entire RWF system to 10 ppm to include the whirlpool spa/spa pool tub, compensation tank, filter housing, and all associated piping before starting the 1-hour timing.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-
|
|
Violation:
The starboard whirlpool spa was open from 14:00 on 1 March to 05:00 on 2 March and there was no calibration recorded on the halogen analyzer-chart recorder chart. Also, on all of the charts, the previous technician had used a 0-5 ppm scale manually written on top of the 0-10 ppm scale included on the halogen chart. There was no documentation and it was very difficult to determine the actual readings for residual halogen and pH.
|
|
Recommendation:
Maintain and operate the halogen and pH analyzer-chart recorder in accordance with the manufacturer's instructions. Conduct a manual comparison test before opening the RWF to verify calibration for free halogen residual and pH. Ensure the analyzer reading is within 0.2 ppm for free halogen and 0.2 for pH. For RWFs open longer than 24 hours, conduct a manual comparison test every 24 hours.
|
|
|
Item No.:
09
|
|
Site:
Recreational Water Facilities-Residual Halogen Levels
|
|
Violation:
During the inspection on the pool and whirlpool spa equipment rooms, it was discovered the dosing pumps for three RWFs were not working. The analyzer for the swimming pool was at less than 1.0 ppm, the starboard whirlpool spa was less than 1.0 ppm, and the port whirlpool spa was less than 2.0 ppm. The inspector verified the analyzer reading of the starboard whirlpool spa measured 0.24 ppm and that the low residual chlorine levels went off, but the staff in the ECR did not notify anyone or take any action upon hearing the alarms. All of these facilities were open. The inspector tested these facilities and measured the following readings: 0.29 ppm for the swimming pool, 0.55 ppm for the starboard whirlpool spa, and several minutes later the port whirlpool spa was measured at 1.54 ppm. Staff immediately closed all three facilities.
|
|
Recommendation:
Maintain a free residual halogen in recirculated RWFs in the following ranges: (1) swimming pools, between 1.0 and 5.0 mg/L (ppm); (6) whirlpool spas and spa pools, between 3.0 and 10.0 mg/L (ppm) free chlorine or between 4.0 and 10.0 mg/L (ppm) bromine.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Thalasso Sample Line
|
|
Violation:
The sample line for the Thalasso spa pool was after the compensation tank.
|
|
Recommendation:
Ensure the sample line for the analyzer probe (monitoring) is either directly from the RWF or on the return line from each RWF and before the compensation tank.
|
|
|
Item No.:
44
|
|
Site:
Recreational Water Facilities-System Knowledge
|
|
Violation:
The person in charge of documenting and maintaining the RWFs was not knowledgeable enough about these systems to ensure they were operated correctly. For example, the shock halogenation for the port and starboard whirlpool spas was either not recorded or was shocked at the incorrect level for at least the past several weeks. There were several days when the manual logs stated that shock halogenation was taking place and the whirlpools were open at the same time with much lower halogen residual readings than what would be required for shocking. Also, the manual logs were filled out incorrectly. This individual did not properly record when the RWFs were open or closed and still recorded readings for the RWFs when the pools were closed, but wrote they were open on the manual logs. Staff were using multiple scales to record the chlorine residual level on the halogen analyzer charts and there was no documentation to determine which scale was correct. There were several days when the manual logs did not match the residual halogen or the pH levels on the halogen analyzer charts for the exact same period of time and there was no documentation why this occurred. The RWFs were not closed when the residual halogen levels were low as documented on several charts.
|
|
Recommendation:
Ensure the supervisor or person in charge of recreational water operations on the vessel demonstrates to VSP-during inspections and on request - knowledge of recreational water operations, is able to demonstrate this knowledge by compliance with Section 6 of the VSP 2011 Operations Manual or by responding correctly to the inspector's questions as they relate to the specific operation, and properly trains employees to comply with Section 6 of the VSP 2011 Operations Manual as it relates to their assigned duties.
|
|
|
Item No.:
11
|
|
Site:
Medical-Reportable Diarrhea Definition
|
|
Violation:
A food worker had one diarrhea episode within 24 hours, stomach cramps, and muscle aches, but was listed on the acute gastroenteritis (AGE) log as nonreportable. The medical staff were unaware of the new diarrhea definition in the 2011 VSP Operations Manual. According to the documentation, this individual was isolated for 48 hours as a precaution. Another food worker had an onset of AGE symptoms on 13 February. Their last symptoms were on 15 February at 09:00. Their symptoms included one diarrhea episode within 24 hours and stomach cramps, but they were listed on the AGE log as nonreportable. The underlying illness on the AGE log was recorded as 'nil of note'. According to the doctor, this crew member was thought to have faked their illness, but this was not documented. The crew member was only isolated for 24 hours and according to their time card, they worked several hours on 16 and 17 February.
|
|
Recommendation:
When food employees meet the case definition for AGE, ensure the following actions are taken: (1) isolate in cabin or designated restricted area until symptom-free for a minimum of 48 hours.
|
|
|
Item No.:
44
|
|
Site:
Medical-Reportable Diarrhea Definition
|
|
Violation:
A food worker had one diarrhea episode within 24 hours, stomach cramps, and muscle aches, but was listed on the AGE log as nonreportable. The medical staff were unaware of the new diarrhea definition in the 2011 VSP Operations Manual. Another food worker had AGE symptoms which included one diarrhea episode within 24 hours and stomach cramps, but they were listed on the AGE log as nonreportable. The underlying illness on the AGE log was recorded as 'nil of note'. According to the doctor, this crew member was thought to have faked their illness, but this was not documented. A nonfood worker had AGE symptoms which included two diarrhea episodes within 24 hours and stomach cramps. The underlying illness on the AGE surveillance log stated 'nil of note'. According to staff, this crew member's symptoms were thought to be caused by antibiotics, but this was not documented.
|
|
Recommendation:
Ensure the supervisor or person in charge of medical operations related to AGE on the vessel demonstrates to VSP-during inspections and on request-knowledge of medical operations related to AGE, is able to demonstrate this knowledge by compliance with Section 4 of the VSP 2011 Operations Manual or by responding correctly to the inspector's questions as they relate to the specific operation, and properly trains employees to comply with Section 4 of the VSP 2011 Operations Manual as it relates to their assigned duties.
|
|
|
Item No.:
20
|
|
Site:
Preparation Room-Vegetable
|
|
Violation:
There were slotted fasteners in the food contact area of the potato peeler.
|
|
Recommendation:
Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
|
|
|
Item No.:
20
|
|
Site:
Galley-Pastry
|
|
Violation:
There were slotted fasteners in the deck oven.
|
|
Recommendation:
Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
|
|
|
Item No.:
33
|
|
Site:
Galley-Hot Section
|
|
Violation:
There was missing and recessed deck tile grout around the deck sink in front of the two tilting kettles. During the inspection, the grout was repaired.
|
|
Recommendation:
Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
|
|
|
Item No.:
37
|
|
Site:
Galley-Dishwash
|
|
Violation:
There was excess condensation on the inside final compartment of the in-use conveyor dishwash machine where the blower was located. This condensation was dripping onto clean dishes as they exited the machine.
|
|
Recommendation:
Ensure exhaust ventilation hood systems in food preparation and warewashing areas--including components such as hoods, fans, guards, and ducting--are designed to prevent grease or condensation from draining or dripping onto food, equipment, utensils, linens, and single-service and single-use articles.
|
|
|
Item No.:
28
|
|
Site:
Galley-Dishwash
|
|
Violation:
Condensation from the blower compartment of the machine was dripping onto clean dishes as they exited the machine.
|
|
Recommendation:
Do not allow for condensation to drip onto cleaned items.
|
|
|
Item No.:
36
|
|
Site:
Buffet-Beverage Stations
|
|
Violation:
The light intensity was less than 220 lux in front of the beverage equipment and less than 110 lux behind and around the beverage equipment. The company's Public Health Director stated the ship had been approved for an extension until 30 April for lighting upgrades.
|
|
Recommendation:
Ensure the light intensity is at least 220 lux (20 foot candles) on food preparation surfaces, and at a distance of 75 centimeters (30 inches) above the deck in food preparation areas, handwashing facilities, warewashing areas, equipment, and utensil storage, pantries, toilet rooms, and consumer self-service areas. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
08
|
|
Site:
Pantry-Across from Stateroom 8048
|
|
Violation:
Closest to the handwash station, the continuous pressure backflow prevention device for the ice machine was corroded.
|
|
Recommendation:
Maintain backflow prevention devices in good repair.
|
|