Cruise Ship: Seadream II Cruise Line: Sea Dream Yacht Club Inspection Date: 02/03/2018 Inspection Score: 95
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 06
Site: Potable Water-Equipment Failure - Manual Readings
Violation: At least since 26 January, charts had manual readings every 4 hours. The analyzer was malfunctioning.
Recommendation: Complete repairs on malfunctioning halogen analyzer-chart recorders within 10 days of equipment failure.
Item No.: 08
Site: Pantry-Deck 3
Violation: The backflow prevention device for the ice machine had the intermediate vents blocked by paint. Corrections started immediately.
Recommendation: Maintain backflow prevention devices in good repair.
Item No.: 10
Site: Recreational Water Facilities-Equipment Failure - Manual Readings
Violation: In the last month, the Jacuzzi and pool analyzers malfunctioned, leading to manual readings every 4 hours several days. The analyzers were not working the day of the inspection either. There were nine days of manual readings for the Jacuzzi and nine days of manual readings for the pool
Recommendation: Install chart recorders or electronic data loggers with security features that record pH and halogen measurements for each individual RWF. Ensure the sample line for the analyzer probe (monitoring) is either directly from the RWF or on the return line from each RWF and before the compensation tank. Install appropriate sample taps for analyzer calibration. In the event of equipment failure, measure free residual halogen and pH by a manual test kit at the RWF or return line at least hourly for whirlpool spas, spa pools, children?s pools, and wading pools and every 4 hours for all other RWFs. Record manual readings on a chart or log, retain for at least 12 months, and ensure that they are available for review during inspections. Complete repairs on malfunctioning halogen analyzer-chart recorders within 30 days of equipment failure. Provide an audible alarm in a continuously occupied watch station to indicate low and high free halogen and pH readings in each RWF.
Item No.: 10
Site: Recreational Water Facilities-Whirlpool
Violation: The whirlpool was a new installation and several properties of the system could not be verified. For example, if it had suction or gravity drain or fittings.
Recommendation: For RWFs with gravity drainage and multiple drains (2 or more drains greater than 3 feet apart), provide either a standard design (not compliant with ASME A112.19.8) drain cover and an alarm, or an ASME A112.19.8 compliant antientrapment/antientanglement drain cover. Ensure the alarm is audible and sounds in both a continuously manned space and at the RWF. Ensure this alarm is for all draining: accidental, routine, and emergency. For RWFs with gravity drainage and a single unblockable drain (per ASME A112.19.8), provide either a standard design (not compliant with ASME A112.19.8) drain cover and an alarm, or an ASME A112.19.8 compliant antientrapment/antientanglement drain cover. Ensure the alarm is audible and sounds in both a continuously manned space and at the RWF. Ensure this alarm is for all draining: accidental, routine, and emergency. For RWFs with gravity drainage and a single blockable drain or multiple drains less than 3 feet apart, provide an ASME A112.19.8 compliant antientrapment/antientanglement drain cover and a gravity drainage system. For RWFs with suction fittings and multiple drains (2 or more drains per pump with drains greater than 3 feet apart), provide an ASME A112.19.8 compliant antientrapment/antientanglement drain cover. For RWFs with suction fittings and a single unblockable drain (per ASME A112.19.8-2007), provide an ASME A112.19.8 compliant antientrapment/antientanglement drain cover and a safety vacuum release system or automatic pump shut-off system. For RWFs with suction fittings and a single blockable drain or multiple drains (less than 3 feet apart), provide an ASME A112.19.8 compliant antientrapment/antientanglement drain cover and a safety vacuum release system or automatic pump shut-off system.
Item No.: 10
Site: Recreational Water Facilities-Shepherd?s Hook
Violation: The hook was not visible from the full perimeter of the pool. Several lounge chairs were in front of it.
Recommendation: Provide a rescue or shepherd?s hook and an approved flotation device at a prominent location (visible from the full perimeter of the pool) at each RWF that has a depth of 1 meter (3 feet) or greater. Mount these devices in a manner that allows for easy access during an emergency. Ensure the pole of the rescue or shepherd?s hook is long enough to reach the center of the deepest portion of the pool from the side plus 2 feet. Ensure it is a light, strong, nontelescoping material with rounded, nonsharp ends. Ensure the approved flotation device includes an attached rope that is at least 2/3 of the maximum pool width.
Item No.: 13
Site: Dining Room-Main Salon Lounge
Violation: Numerous food items were stored under the seats and directly on the deck. Supervisory staff knew about using these areas under where passengers seat to store food and food utensils and equipment, knowing that these areas are not appropriate storage areas.
Recommendation: Because of the risks for foodborne illness inherent to the food operation, ensure the supervisor or person in charge of food operations on the vessel demonstrates to VSP - during inspections and on request - knowledge of foodborne disease prevention, application of the Hazard Analysis Critical Point principles, and the food-safety guidelines in this manual. Ensure that the person in charge demonstrates this knowledge: (1) By compliance with these guidelines. Ensure that the areas of knowledge include: (12) Identifying critical-control points in the operation from purchasing through service that when not controlled may contribute to the transmission of foodborne illness and explaining steps taken to ensure the points are controlled in accordance with the guidelines in this manual.
Item No.: 19
Site: Dining Room-Main Salon Lounge
Violation: Numerous food items were stored under the seats and directly on the deck. For example, salt, pepper, sugar, and drink bitters. The deck was soiled and corroded. The surfaces under the seat cushions were corroded. Corrections started immediately.
Recommendation: Protect food from contamination by storing the food: (1) Covered or otherwise protected; (2) In a clean, dry location; (3) Where it is not exposed to splash, dust, or other contamination; and (4) At least 15 centimeters (6 inches) above the deck.
Item No.: 20
Site: Galley-Bakery
Violation: The area where the attachments to the deck mixer were connected was corroded. Corrections started immediately.
Recommendation: Materials used in the construction of multiuse utensils and food contact surfaces of equipment must be: (1) durable, corrosion resistant, and nonabsorbent; (2) sufficient in weight and thickness to withstand repeated warewashing; (3) finished to have a smooth, easily cleanable surface; and (4) resistant to pitting, chipping, crazing, scratching, scoring, distortion and decomposition.
Item No.: 21
Site: Dining Room-Main Salon Lounge
Violation: Numerous food items were stored under the seats and directly on the deck. The surfaces under the seat cushions were corroded. Corrections started immediately.
Recommendation: Ensure nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning are constructed of a corrosion-resistant, nonabsorbent, and smooth material.
Item No.: 21
Site: Pantry-Deck 4
Violation: The top cover of the ice machine was loose creating a gap. Corrections started immediately.
Recommendation: Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 24
Site: Galley-Dishwash
Violation: The final rinse gauge of the in-use rack-type warewasher measured 204°F to over 220°F and gave an error when the temperature continued to increase. Large amounts of steam were leaving the final rinse spray nozzles. Corrections started immediately.
Recommendation: In a mechanical operation, ensure the temperature of the fresh hot water sanitizing rinse as it enters the manifold is not more than 90°C (194°F) or less than: (1) 74°C (165°F) for a stationary rack, single-temperature machine; (2) 82°C (180°F) for all other machines. Ensure the utensil surface temperature is not less than 71°C (160°F) as measured by an irreversible registering temperature indicator.
Item No.: 26
Site: Galley-Clean Storage
Violation: At least five previously cleaned soup bowls and one salad bowl were found soiled in food and nonfood-contact surfaces. Corrections started immediately.
Recommendation: Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
Item No.: 27
Site: Galley-Clean Storage
Violation: At least five previously cleaned soup bowls and one salad bowl were found soiled in food and nonfood-contact surfaces. Corrections started immediately.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 27
Site: Pantry-Deck 4
Violation: The technical space of the ice machine was soiled with debris. Corrections started immediately.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 28
Site: Pantry-Deck 5
Violation: Around 1:30 pm before embarkation, the door to this outdoor pantry was open. The dishwash area with dozens of clean plates on the bulkheads were unprotected. In addition, the outdoor deck immediately outside the pantry had two tables with clean utensils like coffee carafes with water inside, an unprotected tray of cutlery and utensils, and a container with juice remnants still inside was next to the clean utensils.
Recommendation: After cleaning and sanitizing, ensure equipment and utensils are air dried or adequately drained before contact with food. Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination; (3) at least 150 millimeters (6 inches) above the deck. Store clean equipment and utensils in a self-draining position that allows air drying, and covered or inverted.
Item No.: 28
Site: Dining Room-Main Salon Lounge
Violation: Numerous food items were stored under the seats and directly on the deck. For example, straws, glasses, paper cups, napkins, cutting boards, blenders, and containers. Some of these items were in boxes but most were not. The deck was soiled and corroded. The surfaces under the seat cushions were corroded. Corrections started immediately.
Recommendation: Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination; (3) at least 150 millimeters (6 inches) above the deck.
Item No.: 30
Site: Pantry-Deck 4
Violation: The handwashing station had no sign advising frequent handwashing. Corrections started immediately.
Recommendation: Post a sign over handwashing sinks stating "WASH HANDS OFTEN" in a language that the food employees understand.
Item No.: 30
Site: Pantry-Deck 3
Violation: The handwashing station had no sign advising frequent handwashing. Corrections started immediately.
Recommendation: Post a sign over handwashing sinks stating "WASH HANDS OFTEN" in a language that the food employees understand.
Item No.: 33
Site: Dining Room-Main Salon Lounge
Violation: Numerous food items were stored under the seats and directly on the deck. The deck was soiled and corroded. Corrections started immediately.
Recommendation: Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, bars, and food and equipment storage areas are constructed and maintained for easy cleaning. Do not use carpet in these areas.
Item No.: 33
Site: Galley-Saucier Fridge 19
Violation: The deck had no coving.
Recommendation: Cove all bulkhead/deck, equipment/deck, cabinet/deck, and deck sink coaming/deck junctures (including galleys, pantries, buffets, bars, waiter stations, dining room work counters, provisions, food storage rooms, equipment/utensil storage rooms, and toilet rooms intended for use by galley personnel).
Item No.: 33
Site: Provisions-Dry Store and Walk-in Refrigerators 5, 6, and 7
Violation: The decks had no coving.
Recommendation: Cove all bulkhead/deck, equipment/deck, cabinet/deck, and deck sink coaming/deck junctures (including galleys, pantries, buffets, bars, waiter stations, dining room work counters, provisions, food storage rooms, equipment/utensil storage rooms, and toilet rooms intended for use by galley personnel).
Item No.: 39
Site: Pantry-Deck 5
Violation: At the end of breakfast service, the door to this outdoor pantry was open and a fly was inside.
Recommendation: Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
Item No.: 40
Site: Pantry-Deck 5
Violation: At the end of breakfast service, the door to this outdoor pantry was open and a fly was inside. In addition, around 1:30 pm before embarkation, the door was still open and this time no one was in the area.
Recommendation: Protect entry points where pests may enter the food areas.
Item No.: 40
Site: Integrated Pest Management-Active Monitoring
Violation: The records for the active monitoring conducted on 2 February, and 19 and 26 January did not document the time of the inspections.
Recommendation: Ensure the IPM Plan includes provisions for logs for active monitoring of pest sightings in operational areas of the vessel. Ensure the IPM plan includes provisions for training of crew members in charge of log completion. Record the time of the active monitoring inspections in the log.
Item No.: 40
Site: Integrated Pest Management-Main Salon
Violation: No active or passive monitoring was conducted in this area where food storage was found under the seats. This area was not included in the IPM plan.
Recommendation: Include all food areas in the active and passive IPM monitoring activities.