Cruise Ship: Asuka II Cruise Line: NYK Cruises Co., LTD Inspection Date: 05/26/2018 Inspection Score: 91
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 03
Site: Potable Water-Bunkering Record Review
Violation: On May 24, the ship bunkered water at less than 2 ppm chlorine (Cl) from 1200 to 1615. On May 22, the ship bunked water at less than 2 ppm Cl from 1300 to 2100. On May 15 the ship bunkered water at less than 2 ppm Cl from 1145 to 2120. On May 12, the ship bunkered water at less than 2 ppm Cl from 0930 to 1700. On May 10, the ship bunkered water from 1055 to 1300. On May 8, the ship bunkered water at less than 2 ppm Cl from 0900 to 1735. Staff stated the manual sample line was less than 3 meters from the halogen injection point, and that this impacted their readings of Cl.
Recommendation: Continuously halogenate potable water to at least 2.0 mg/L (ppm) free residual halogen at the time of bunkering or production with an automatic halogenation device that is controlled by a flow meter and adjust the pH so it does not exceed 7.8. Ensure the amount of halogen injected during bunkering or production is controlled by a flow meter or a free halogen analyzer.
Item No.: 03
Site: Potable Water-Production Record Review
Violation: The ship produced water at less than 2 ppm Cl from 0415 on May 23 to 0015 on May 24. On May 16, The ship produced water at less than 2 ppm Cl from 0036 on May 16 to 0015 on May 22. The ship produced water at less than 2 ppm Cl from 2112 on May 12 to 0415 on May 15. Staff stated the manual sample line was less than 3 meters from the halogen injection point, and that this impacted their readings of Cl.
Recommendation: Continuously halogenate potable water to at least 2.0 mg/L (ppm) free residual halogen at the time of bunkering or production with an automatic halogenation device that is controlled by a flow meter and adjust the pH so it does not exceed 7.8. Ensure the amount of halogen injected during bunkering or production is controlled by a flow meter or a free halogen analyzer.
Item No.: 08
Site: Potable Water-Bunkering Record Review
Violation: The concentration of chlorine was not adjusted to at least 2 ppm within 30 minutes of the start of bunkering on the following dates: May 24, May 22, May 15, May 12, May 10, and May 8.
Recommendation: Adjust the free halogen residual level to at least 2.0 mg/L (ppm) within 30 minutes of the start of the bunkering and production processes.
Item No.: 08
Site: Potable Water-Production Record Review
Violation: The concentration of chlorine was not adjusted to at least 2 ppm within 30 minutes of the start of production on the following dates: May 23, May 16, and May 12.
Recommendation: Adjust the free halogen residual level to at least 2.0 mg/L (ppm) within 30 minutes of the start of the bunkering and production processes.
Item No.: 38
Site: Other-Bridge Beverage Station
Violation: The cleaning locker was not labeled 'CLEANING MATERIALS ONLY.'
Recommendation: Label the locker "CLEANING MATERIALS ONLY."
Item No.: 08
Site: Potable Water-Forward Starboard Bunker Station
Violation: The separate and designated technical water filling line had the same fittings as the adjacent potable water bunkering connections. This was noted on the previous inspection.
Recommendation: Ensure potable water hoses have unique fittings from all other hose fittings on the vessel. Bunker technical water, if used on the vessel, through separate piping using fittings incompatible for potable water bunkering.
Item No.: 08
Site: Potable Water-Forward Starboard Bunkering Station
Violation: Outside of the forward starboard bunkering station, there was a trolley with seven blue hoses labeled 'POTABLE WATER ONLY.' The ends of four of these hoses were uncoupled and uncapped. The other three hoses had the couplings cut off. Staff first stated the hoses would be used to bunker water later that day. Then staff stated they were emergency hoses. Staff then stated these hoses were used only for bunkering technical water. The trolley with the uncapped or uncoupled hoses was noted on the previous inspection.
Recommendation: Ensure potable water hoses are rolled tight with the ends capped, on reels, or on racks, or with ends coupled together and stowed in potable water hose lockers. Do not use potable water hoses for any other purpose. Handle and store all hoses, fittings, water filters, buckets, equipment, and tools used for connection with the bunkering of potable water in a sanitary manner. Ensure potable water hoses are rolled tight with the ends capped, on reels, or on racks, or with ends coupled together and stowed in potable water hose lockers.
Item No.: 08
Site: Potable Water-Aft and Forward Portside Bunkering Stations
Violation: The aft portside bunkering station contained one hose. The ends of this hose were not coupled or capped.
Recommendation: Ensure potable water hoses are rolled tight with the ends capped, on reels, or on racks, or with ends coupled together and stowed in potable water hose lockers.
Item No.: 08
Site: Potable Water-Bunkering and Production Sampling Point
Violation: The ship uses manual tests instead of analyzer-chart recorders. Staff were taking manual sample readings from a sampling point located approximately 2 meters from the halogen injection point. The analyzer drew its sample from another sample point approximately 3 meters from the halogen injection point. When the inspector asked why staff were drawing samples from the sample point located 2 meters from the injection point, staff stated they had been instructed not to take samples from the analyzer sample line.
Recommendation: Obtain water samples for halogen and pH testing from a sample cock and/or a halogen analyzer probe located on the bunker or production water line at least 3 meters (10 feet) after the halogen injection point and before the storage tank.
Item No.: 44
Site: Potable Water-Forward Starboard Bunkering Station
Violation: Outside of the forward starboard bunkering station, there was a trolley with seven blue hoses labeled 'POTABLE WATER ONLY.' The ends of four of these hoses were uncoupled and uncapped. Three of the hoses had the couplings cut off. Staff first stated the hoses would be used to bunker water later that day. Then staff stated they were emergency hoses. Staff then stated these hoses were used only for the bunkering of technical water. The trolley with the uncapped or uncoupled hoses was noted on the previous inspection.
Recommendation: Ensure the supervisor or person in charge of potable water operations on the vessel demonstrates to VSP?during inspections and on request-knowledge of potable water operations, is able to demonstrate this knowledge by compliance with Section 5 of the VSP 2011 Operations Manual or by responding correctly to the inspector?s questions as they relate to the specific operation, and properly trains employees to comply with Section 5 of the VSP 2011 Operations Manual as it relates to their assigned duties.
Item No.: *
Site: Potable Water-Bunkering and Production Injection Points
Violation: There was no injection point for pH control on the bunkering and production water line. Staff stated there was no way to control the pH, and if bunkered water had a pH above 7.8, bunkering was stopped. The inspector reviewed the bunkering and production records to verify pH was not above 7.8.
Recommendation: Provide a pH injection point in order to control pH levels.
Item No.: 28
Site: Galley-Hot Galley
Violation: A crew member was observed drying two plate covers with a paper towel. Next to the crew member was a stack of approximately 20 plate covers. The inspector was told crew members had been instructed not to dry dishes with a paper towel. The plate covers were sent to be rewashed.
Recommendation: After cleaning and sanitizing, ensure equipment and utensils are air dried or adequately drained before contact with food.
Item No.: 13
Site: Galley-Hot Galley
Violation: A crew member was observed drying two plate covers with a paper towel. Next to the crew member was a stack of approximately 20 plate covers. The inspector was told crew members had been instructed not to dry dishes with a paper towel. The plate covers were sent to be rewashed.
Recommendation: Ensure the supervisor or person in charge of food operations on the vessel monitors that: (1) Food operations are not conducted in a room used as living or sleeping quarters; (2) Persons unnecessary to the food operation are not allowed in the food preparation, food storage, or warewashing areas. (3) Employees and other persons such as delivery and maintenance persons and pesticide applicators entering the food preparation, food storage, or warewashing areas comply with the guidelines in this manual; (4) Food employees are effectively cleaning their hands; (5) Employees are observing foods as they are received to determine that they are from approved sources, delivered at the required temperatures, protected from contamination, unadulterated, and accurately presented; (6) Employees are properly cooking potentially hazardous food, being particularly careful in cooking foods known to cause severe foodborne illness and death, such as eggs and comminuted meats; (7) Employees are using proper methods to rapidly cool potentially hazardous foods that are not held hot or are not for consumption within 4 hours; (8) Consumers who order raw or partially cooked ready-to-eat foods of animal origin are informed that the food is not cooked sufficiently to ensure its safety; (9) Employees are properly sanitizing cleaned multiuse equipment and utensils before they are reused; (10) Consumers are notified that clean tableware is to be used when they return to self-service areas such as salad bars and buffets; (11) Employees are preventing cross-contamination of ready-to-eat food with bare hands by properly using suitable utensils such as deli tissue, spatulas, tongs, single-use gloves, or dispensing equipment; (12) Employees are properly trained in food safety, including food allergy awareness, as it relates to their assigned duties; (13) Food employees are informed of their responsibility to report to the supervisor or person in charge information about their health and activities as they relate to diseases that are transmissible through food.
Item No.: 21
Site: Galley-Pastry
Violation: The deck oven had brown fuzzy material on the glass outside of the oven that was not easily cleanable.
Recommendation: Design and construct nonfood-contact surfaces of equipment and utensils to be durable and to retain their characteristic qualities under normal use conditions.
Item No.: 37
Site: Galley-Potwash
Violation: Condensate had collected on the deckhead above the hood type potwash. No dishes were impacted.
Recommendation: Ensure ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.
Item No.: 22
Site: Galley-Dishwash
Violation: There was less than one meter between the soiled dish table and the clean storage rack. Staff stated they would add a plastic shield on the side of the clean dish rack.
Recommendation: Provide adequate separation between clean and soiled dishes.
Item No.: 37
Site: Galley-Dishwash
Violation: Condensate was dripping from the canopy above the dirty side of the dishwash.
Recommendation: Ensure ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.
Item No.: 24
Site: Galley-Rack Type Dish Machine
Violation: The final rinse manifold temperature did not reach 180°F. The inspector placed a 180°F sticker on the manifold, which did not turn black after several cycles. A crew member held a thermometer up to the nozzle on the final rinse manifold, which reached a maximum temperature of 173°F. The final rinse temperature gauge on the dish machine reached 185°F.
Recommendation: In a mechanical operation, ensure the temperature of the fresh hot water sanitizing rinse as it enters the manifold is not more than 90°C (194°F) or less than: (1) 74°C (165°F) for a stationary rack, single-temperature machine; (2) 82°C (180°F) for all other machines. Ensure the utensil surface temperature is not less than 71°C (160°F) as measured by an irreversible registering temperature indicator.
Item No.: 22
Site: Galley-Rack Type Dish Machine
Violation: The final rinse manifold temperature gauge read a maximum temperature of 185°F. However, the inspector placed a 180°F sticker on the manifold, which did not turn black after several cycles. Additionally, a crew member held a thermometer up to the nozzle on the final rinse manifold. The thermometer reached a maximum temperature of 173°F.
Recommendation: Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
Item No.: 13
Site: Galley-Rack Type Dish Machine
Violation: The inspector asked crew members how they checked the temperature of the final rinse manifold. Crew members stated they used the final rinse gauge to determine the temperature. The inspector then asked how they manually check the temperature of the final rinse manifold. Crew members were unaware that this needed to be done. When the inspector checked the temperature of the final rinse manifold with a color-changing sticker and a thermometer, it did not reach 180°F even though the gauge on the machine reached a temperature of 185°F.
Recommendation: Ensure the supervisor or person in charge of food operations on the vessel monitors that: (1) Food operations are not conducted in a room used as living or sleeping quarters; (2) Persons unnecessary to the food operation are not allowed in the food preparation, food storage, or warewashing areas. (3) Employees and other persons such as delivery and maintenance persons and pesticide applicators entering the food preparation, food storage, or warewashing areas comply with the guidelines in this manual; (4) Food employees are effectively cleaning their hands; (5) Employees are observing foods as they are received to determine that they are from approved sources, delivered at the required temperatures, protected from contamination, unadulterated, and accurately presented; (6) Employees are properly cooking potentially hazardous food, being particularly careful in cooking foods known to cause severe foodborne illness and death, such as eggs and comminuted meats; (7) Employees are using proper methods to rapidly cool potentially hazardous foods that are not held hot or are not for consumption within 4 hours; (8) Consumers who order raw or partially cooked ready-to-eat foods of animal origin are informed that the food is not cooked sufficiently to ensure its safety; (9) Employees are properly sanitizing cleaned multiuse equipment and utensils before they are reused; (10) Consumers are notified that clean tableware is to be used when they return to self-service areas such as salad bars and buffets; (11) Employees are preventing cross-contamination of ready-to-eat food with bare hands by properly using suitable utensils such as deli tissue, spatulas, tongs, single-use gloves, or dispensing equipment; (12) Employees are properly trained in food safety, including food allergy awareness, as it relates to their assigned duties; (13) Food employees are informed of their responsibility to report to the supervisor or person in charge information about their health and activities as they relate to diseases that are transmissible through food.
Item No.: 27
Site: Galley-Hot Galley
Violation: The potable water supply line located behind the tilting pan and deep fryer was heavily soiled with more than one day's worth of accumulation.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 27
Site: Galley-Hot Galley
Violation: The legs of the deep fryer located next to the flat top grill were soiled with more than one day's worth of accumulation.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 37
Site: Galley-Hot Galley
Violation: Condensate had collected on the deckhead above the deck ovens.
Recommendation: Ensure ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.
Item No.: 18
Site: Galley-Upright Middle Refrigerator
Violation: A hotel pan of raw pork was stored under a hotel pan of chicken. This was immediately corrected.
Recommendation: Protect food from cross-contamination or other sources of contamination by the following methods: (1) Physically separating raw animal foods during storage, preparation, holding, and display from raw ready-to-eat food so that products do not physically touch and so that one product does not drip into another. (2) Separating types of raw animal foods from each other such as beef, fish, lamb, pork, and poultry?except when combined as ingredients?during storage, preparation, holding, and display by using separate equipment for each type, or by arranging each type of food in equipment so that cross-contamination of one type with another is prevented, or by preparing each type of food at different times or in separate areas. (3) Cleaning and sanitizing equipment and utensils. (4) Storing the food in packages, covered containers, or wrappings. (5) Cleaning visible soil on hermetically sealed containers of food before opening. (6) Protecting food containers that are received packaged together in a case or overwrap from cuts when the case or overwrap is opened. (7) Separating damaged, spoiled, or recalled food being held on the vessel. (8) Separating unwashed fruits and vegetables from ready-to-eat food.
Item No.: 37
Site: Galley-Hood Type Potwash
Violation: Condensate had collected on the deckhead above the hood type potwash.
Recommendation: Ensure ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.
Item No.: 21
Site: Preparation Room-
Violation: Tape had been used to seal the preparation table to the bulkhead, making the area difficult to clean.
Recommendation: Ensure nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning are constructed of a corrosion-resistant, nonabsorbent, and smooth material.
Item No.: 18
Site: Preparation Room-Meat Thaw Cooler
Violation: Ground beef was stored above whole muscle beef. This was immediately corrected.
Recommendation: Protect food from cross-contamination or other sources of contamination by the following methods: (1) Physically separating raw animal foods during storage, preparation, holding, and display from raw ready-to-eat food so that products do not physically touch and so that one product does not drip into another. (2) Separating types of raw animal foods from each other such as beef, fish, lamb, pork, and poultry?except when combined as ingredients?during storage, preparation, holding, and display by using separate equipment for each type, or by arranging each type of food in equipment so that cross-contamination of one type with another is prevented, or by preparing each type of food at different times or in separate areas. (3) Cleaning and sanitizing equipment and utensils. (4) Storing the food in packages, covered containers, or wrappings. (5) Cleaning visible soil on hermetically sealed containers of food before opening. (6) Protecting food containers that are received packaged together in a case or overwrap from cuts when the case or overwrap is opened. (7) Separating damaged, spoiled, or recalled food being held on the vessel. (8) Separating unwashed fruits and vegetables from ready-to-eat food.
Item No.: 16
Site: Galley-Bistro
Violation: Four boxes of yogurt, which staff stated were on temperature control, where stored in a unit labeled time control. The yogurt was moved to a temperature controlled refrigerator.
Recommendation: Ensure only time controlled foods are kept in time control units.
Item No.: 16
Site: Buffet-Bistro
Violation: A tray of desserts was out for service on the buffet line were on time control. There was no discard sticker affixed to the tray, but there were foods and discard times printed on a bulkhead mounted paper log in the area. This outlet was open for more than 4 hours. A coffee machine with two milk containers was also on time control. There was no discard sticker affixed to the milk containers, but there was a bulkhead mounted paper log in the area which designated set up and discard times. This area was also open for greater than 4 hours. Staff stated these paper logs were printed each morning and mounted to the bulkheads.
Recommendation: If time only?rather than time in conjunction with temperature?is used as the public health control for a working supply of potentially hazardous food before cooking, or for ready-to-eat potentially hazardous food that is displayed or held for service for immediate consumption, ensure the food (1) Has an initial temperature of 5°C (41°F) or less or 57°C (135°F) or greater before placement on time control. (2) Is not be placed on temperature control again. (3) Is marked or otherwise identified to indicate the time 4 hours past the point in time when the food is removed from temperature control (if the time between service set-up and closing is greater than 4 hours. and (4) Is discarded within 4 hours of placement on time control.
Item No.: 43
Site: Other-Showerhead Disinfection Records
Violation: Staff stated crew members were responsible for disinfecting their own showerheads and that they were given a document with instructions on how to do so. The directions instructed crew members to use 120 ppm water, but did not have a time for how long crew should disinfect the showerheads. The logs indicated the showerheads had been disinfected.
Recommendation: Clean and disinfect shower heads every 6 months. Disinfect with an appropriate halogen-based disinfectant at 10 ppm for 60 minutes, or an equivalent CT value.