Item No.:
03
|
|
Site:
Potable Water-Production
|
|
Violation:
While sailing in the Amazon River, the ship produced water on April 9, 10, 11, 12, 13, 14 and 15.
|
|
Recommendation:
Operate a reverse osmosis unit, distillation plant, or other process that supplies water to the vessel?s potable water system only while the vessel is making way, and do not operate in polluted areas, harbors, or at anchor.
|
|
|
Item No.:
08
|
|
Site:
Housekeeping-Deck 7 Forward Housekeeping Pantry
|
|
Violation:
The backflow preventer on the ice machine did not have a vent.
|
|
Recommendation:
Ensure backflow prevention devices are vented.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Evaporator #1
|
|
Violation:
A hose was attached to the vent of the reduced pressure assembly on the overboard discharge line. The hose ended in the bilge of the ship. Staff stated the hose would be removed.
|
|
Recommendation:
Ensure air gaps are at least twice the diameter of the delivery fixture opening and a minimum of 25 millimeters (1 inch).
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Cross Connections Log
|
|
Violation:
The cross connections control log had the incorrect device listed for the potable water connect on the sauna steam line.
|
|
Recommendation:
Ensure the cross-connection control program includes at a minimum: a complete listing of cross-connections and the backflow prevention method or device for each, so there is a match to the plumbing system component and location. Include air gaps on the listing. Ensure a schedule for inspection frequency is set. Maintain a log documenting the inspection and maintenance in written or electronic form, and ensure it is available for review during inspections.
|
|
|
Item No.:
16
|
|
Site:
Galley-Deck 9 Terrace Cafe
|
|
Violation:
Five pans of food were on time control on the stove top with 4-hour discard labels, but the stove top was not indicated on the time control plan. The foods were beef gravy, fish sauce, mushroom sauce, turkey sauce, and soup. Staff moved the food pans into a time control cabinet.
|
|
Recommendation:
Ensure the time control plan matches the operations.
|
|
|
Item No.:
16
|
|
Site:
Pantry-Deck 9 Waves Grill
|
|
Violation:
A bowl on the counter with a white powder did not have a label identifying the food product. Staff stated it was flour.
|
|
Recommendation:
Ensure working containers used for storing poisonous or toxic materials such as cleaners and sanitizers taken from bulk supplies are clearly and individually identified with the common name of the material.
|
|
|
Item No.:
16
|
|
Site:
Galley-Deck 4 Cold Galley
|
|
Violation:
A hotel pan of white powder in the dry store locker had no label identifying the contents. Staff stated it was flour.
|
|
Recommendation:
Ensure working containers used for storing poisonous or toxic materials such as cleaners and sanitizers taken from bulk supplies are clearly and individually identified with the common name of the material.
|
|
|
Item No.:
16
|
|
Site:
Galley-Deck 4 Cold Galley
|
|
Violation:
A pan of potato chicken salad in the walk-in refrigerator had a production date of 5/3/18 and a 7-day discard date of 5/9/18. However, the cooling logs indicated the chicken was cooked and cooled on 5/1/18 and the potatoes were cooked and cooled on 5/2/18. The 7-day discard date was changed to 5/7/18.
|
|
Recommendation:
Ensure refrigerated, potentially hazardous, ready-to-eat food ingredients or a portion of a refrigerated, potentially hazardous, ready-to-eat food that is subsequently combined with additional ingredients or portions of food retains the date marking of the earliest or first-prepared ingredient.
|
|
|
Item No.:
19
|
|
Site:
Provisions-Deck 2 Stairwell
|
|
Violation:
A pallet of canned soda was stored at the bottom of the stairs across from the food lifts. The sides of the palleted beverages were wrapped in plastic, but the top was exposed. Staff stated the soda was part of the stocks and had not been provisioned the day of the inspection. A waste bin was stored in front of and touching the soda and a large amount of metal scrap was stored behind. Staff stated the waste bin was in the area for repair. Finally, a sticky piece of cardboard and the remnants of a balloon were found on top of the cans and the bottom of a cardboard tray with cans was soiled with a dried, white material. The pallet was moved to a more appropriate storage area immediately.
|
|
Recommendation:
Protect food from contamination by storing the food: (2) In a clean, dry location; (3) Where it is not exposed to splash, dust, or other contamination.
|
|
|
Item No.:
19
|
|
Site:
Provisions-Deck 2 Wine Store
|
|
Violation:
A deck pallet was stored on its side at the entrance to the room with the feet in direct contact with boxes of beverages. The pallet was removed.
|
|
Recommendation:
Protect food from contamination by storing the food: (3) Where it is not exposed to splash, dust, or other contamination.
|
|
|
Item No.:
19
|
|
Site:
Housekeeping-Deck 7 Forward Pantry
|
|
Violation:
A half empty bottle of water was sitting on the counter with unopened bottles of water. Staff stated the unopened bottles of water were for guests, and that the open bottle belonged to a crew member.
|
|
Recommendation:
Protect food from contamination by storing the food: (1) Covered or otherwise protected; (2) In a clean, dry location; (3) Where it is not exposed to splash, dust, or other contamination; and (4) At least 15 centimeters (6 inches) above the deck.
|
|
|
Item No.:
20
|
|
Site:
Preparation Room-
|
|
Violation:
The bottom of the previously-cleaned plastic lettuce dryer insert was rough, making it difficult to clean. Staff stated a new insert would be used.
|
|
Recommendation:
Materials used in the construction of multiuse utensils and food contact surfaces of equipment must be: (3) finished to have a smooth, easily cleanable surface.
|
|
|
Item No.:
22
|
|
Site:
Galley-Deck 9 Terrace Cafe
|
|
Violation:
The hood-type glasswash machine was out of order since the morning of the inspection. A work order had been submitted.
|
|
Recommendation:
Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
|
|
|
Item No.:
26
|
|
Site:
Preparation Room-
|
|
Violation:
The plastic insert for the lettuce dryer was soiled with a dark brown residue in every single one of the small holes. Staff stated the insert had been previously cleaned.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
27
|
|
Site:
Galley-Deck 4 Cold Galley
|
|
Violation:
The backside of the slider mechanism on the deli slicer was soiled with dried, white residue.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
28
|
|
Site:
Galley-Deck 4 Dishwash Area
|
|
Violation:
A brown liquid was slowly dripping down the bulkhead from the deckhead/bulkhead juncture and pooling onto the clean storage counter below. Stacks of inverted clean plates were stored on the counter but none were directly impacted.
|
|
Recommendation:
Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination; (3) at least 150 millimeters (6 inches) above the deck.
|
|
|
Item No.:
28
|
|
Site:
Provisions-Deck 2 Dry Store
|
|
Violation:
A jacket was stored on top of a box of coffee filters and a previously-used broom was stored behind this box and other boxes of single-use/single-service items. Another previously used broom was stored between boxes of single-use/single-service items across from the coffee filters. The jacket and brooms were removed.
|
|
Recommendation:
Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (2) in a location where they are not exposed to splash, dust, or other contamination.
|
|
|
Item No.:
28
|
|
Site:
Galley-Deck 10 Red Ginger/Tuscan Steak
|
|
Violation:
Liquid was leaking from the bulkhead-mounted hood-cleaning cabinet to the 3-bucket trolley below. The liquid was dripping onto the inverted red bucket and pooling on the bottom of the trolley and the deck below.
|
|
Recommendation:
Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination; (3) at least 150 millimeters (6 inches) above the deck.
|
|
|
Item No.:
29
|
|
Site:
Galley-Deck 9 Terrace Cafe
|
|
Violation:
Two cubes of ice were in the handwashing station next to the ice machine.
|
|
Recommendation:
Ensure handwashing facilities are used for no other purpose and are accessible at all times.
|
|
|
Item No.:
30
|
|
Site:
Preparation Room-
|
|
Violation:
The pink soap in the dispenser at the handwash station was a watery, thin liquid and had very little surfactant quality. The inspector asked to see a bottle of the pink soap refill and that soap had a much thicker consistency. It appeared the soap in the dispenser had been watered down. The area was open, a crew member was actively working in the area, and paper towels were in the waste receptacle at the handwash station. The watery soap was discarded and the dispenser was refilled with the thicker refill soap.
|
|
Recommendation:
Do not water down the soap.
|
|
|
Item No.:
32
|
|
Site:
Galley-Deck 9 Terrace Cafe
|
|
Violation:
Several paper towels soiled with excessive food waste were in the handwash station waste receptacle. Staff stated these were from holding the edges of food pans.
|
|
Recommendation:
Ensure receptacles and waste-handling containers for refuse and recyclables and for use with materials containing food residue are insect and rodent resistant and have tight-fitting lids. Ensure receptacles and waste-handling containers for refuse and recyclables and for use with materials containing food residue are durable, nonabsorbent, easily cleanable, and leakproof.
|
|
|
Item No.:
33
|
|
Site:
Galley-Deck 4 Dishwash Area
|
|
Violation:
A brown liquid was slowly dripping down the bulkhead from the deckhead/bulkhead juncture and pooling onto the clean storage counter below. Stacks of inverted clean plates were stored on the counter but none were directly impacted.
|
|
Recommendation:
Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
|
|
|
Item No.:
33
|
|
Site:
Provisions-Deck 2 Liquor Store
|
|
Violation:
The deck below pallets to the left of the condenser unit was soiled with debris.
|
|
Recommendation:
Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
|
|
|
Item No.:
33
|
|
Site:
Provisions-Deck 2 Dry Store
|
|
Violation:
The deck under the pallets on the raised platform was soiled with a thick layer of dust and residue from a liquid spill.
|
|
Recommendation:
Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
|
|
|
Item No.:
33
|
|
Site:
Galley-Deck 10 Red Ginger/Tuscan Steak
|
|
Violation:
Liquid was leaking from the bulkhead-mounted hood-cleaning cabinet to the 3-bucket trolley below. The liquid was dripping onto the inverted red bucket and pooling on the bottom of the trolley and the deck below.
|
|
Recommendation:
Ensure liquid does not drip from the cabinet and pool on the deck.
|
|
|
Item No.:
33
|
|
Site:
Pantry-Deck 9 Waves Grill
|
|
Violation:
A long, brown hair was stuck on the bulkhead above the handwash station, partially caught behind the paper towel dispenser. The hair was removed.
|
|
Recommendation:
Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
|
|
|
Item No.:
38
|
|
Site:
Provisions-Deck 2 Dry Store
|
|
Violation:
A jacket was stored on top of a box of coffee filters and a previously-used broom was stored behind this box and other boxes of single-use/single-service items. Another previously used broom was stored between boxes of single-use/single-service items across from the coffee filters. The jacket and brooms were removed.
|
|
Recommendation:
Ensure only articles necessary for the food service operation are stored in food preparation, food storage, and warewashing areas. Ensure maintenance tools such as mops, brooms, and similar items are stored in a designated locker so they do not contaminate food, food-contact surfaces of utensils, and equipment, linens, and single-service and single-use articles.
|
|
|
Item No.:
39
|
|
Site:
Galley-Deck 4 Cold Galley
|
|
Violation:
A house fly was by the two-compartment utility sink.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
40
|
|
Site:
Pantry-Deck 9 Waves Grill
|
|
Violation:
The door to the pantry was pinned open when the inspection arrived and remained open until the inspector pointed it out. The outlet was on an open deck.
|
|
Recommendation:
Protect entry points where pests may enter the food areas.
|
|