Skip directly to site content Skip directly to page options

Inspection Detail Report

  Advanced Search |  Ship Scored 100 |  Green Sheet  |  CDC Home |  VSP Home
 
Cruise Ship: Kydon Cruise Line: Ferries Del Caribe Inspection Date: 05/07/2018 Inspection Score: 91
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 02
Site: Medical-Acute Gastroenteritis (AGE) Surveillance Log
Violation: A passenger case was reported to VSP for the cruise ending on March 30, 2018, but this case was not recorded on the monthly AGE surveillance log. The log was updated during the inspection.
Recommendation: List in the AGE surveillance log (1) the name of the vessel, cruise dates, and cruise number; (2) all reportable cases of AGE; and (3) all passengers and crew members who are dispensed antidiarrheal medication from the master of the vessel, medical staff, or other designated staff.
Item No.: 08
Site: Potable Water-
Violation: No backflow prevention device was installed on the international shore connection. This was written on the December 2017 and March 2018 inspections. In addition, approximately 25 of the toilets only had dual check valves with no intermediate atmospheric vent and all of the cabin shower hoses only had dual check valves with no intermediate atmospheric vent on the hot and cold water supply lines. These were written on the July 2017, December 2017, and March 2018 inspections. No RP or air gap was installed on the mineralizer backwash drain line. Staff provided documentation that the devices had been ordered and would be installed when received.
Recommendation: Provide a comprehensive cross-connection control program. Protect the following connections to the potable water system against backflow with air gaps or mechanical backflow prevention devices: (1) RWFs; (2) decorative water features/fountains; (3) cabin shower hoses, toilets, whirlpool tubs, and similar facilities; (4) photographic laboratory developing machines and utility sinks; (5) beauty and barber shop spray-rinse hoses; (6) spa steam generators where essential oils can be added; (7) hose-bib connections; (8) garbage grinders and food waste systems; (9) automatic galley hood washing systems; (10) food service equipment; (11) mechanical warewashing machines; (12) detergent dispensers; (13) hospital and laundry equipment; (14) air conditioning expansion tanks; (15) boiler feed water tanks; (16) fire system; (17) public toilets, urinals, and shower hoses; (18) potable water, bilge, and pumps that require priming; (19) freshwater or saltwater ballast systems; (20) international fire and fire sprinkler water connections (install a reduced pressure assembly); (21) the potable water supply to automatic window washing systems that can be used with chemicals or chemical mix tanks; (22) water softeners for nonpotable fresh water; (23) water softener and mineralizer drain lines, including backwash drain lines (install an air gap or a reduced pressure assembly); (24) high saline discharge line from evaporators (install an air gap or a reduced pressure assembly); (25) chemical tanks; (26) other connections between the potable water system and a nonpotable water system, such as the gray water system, laundry system, or technical water system (install an air gap or a reduced pressure assembly); (27) black water or combined gray water/black water systems (install an air gap); (28) any other connection to the potable water system where contamination or backflow can occur.
Item No.: 07
Site: Potable Water-
Violation: No reduced pressure zone assembly backflow prevention device (RP) or air gap was installed on the connection between potable and technical water. This was written on the December 2017 and March 2018 inspections. Staff provided documentation that an RP had been ordered.
Recommendation: Protect the potable water system against backflow or other contamination by backflow prevention devices or air gaps. Ensure the permeate lines and distillate lines directed toward the potable water system are also protected.
Item No.: 08
Site: Potable Water-Cross-Connection Control Plan
Violation: The list of backflow prevention devices did not include the specific location of each device, the type of device, or the type of connection. Also, the quantity column for 'Deck 5' and 'Galley' were blank. This was written on the December 2017 and March 2018 inspections. Staff stated they would update the list when the new devices were received and installed.
Recommendation: Ensure the cross-connection control program includes at a minimum: a complete listing of cross-connections and the backflow prevention method or device for each, so there is a match to the plumbing system component and location. Include air gaps on the listing. Ensure a schedule for inspection frequency is set. Maintain a log documenting the inspection and maintenance in written or electronic form, and ensure it is available for review during inspections.
Item No.: 43
Site: Ventilation-AC Unit 8
Violation: The condenser coils and supports inside the unit were soiled with a black substances. Staff stated this unit was scheduled to be cleaned the next day, but the team in the area began cleaning the unit immediately.
Recommendation: Keep air handling units clean.
Item No.: 03
Site: Potable Water-Bunkering
Violation: For three dates since the last inspection, the free halogen residual was recorded as below 2 ppm and no corrective action was taken. On April 4, the 1000 reading was 0.5 ppm, the 1300 reading was 1.6 ppm, the 1400 reading was 1.3 ppm, and the 1500 reading was 1.4 ppm. On April 30, water was bunkered from 1000 until 1700, and the chlorine readings ranged from 0.25 to 1.2 ppm. Finally, on May 4, the 1000 reading was 1.4 ppm, the 1100 reading was 1.4 ppm, the 1400 reading was 1.5 ppm, and the 1500 reading was 1.0 ppm, the 1600 reading was 1.0 ppm, and the 1700 reading was 1.0 ppm. Staff stated they were not aware that the free halogen residual was required to be above 2 ppm.
Recommendation: Continuously halogenate potable water to at least 2.0 mg/L (ppm) free residual halogen at the time of bunkering or production with an automatic halogenation device that is controlled by a flow meter and adjust the pH so it does not exceed 7.8. Ensure the amount of halogen injected during bunkering or production is controlled by a flow meter or a free halogen analyzer.
Item No.: 44
Site: Potable Water-Bunkering
Violation: Staff stated they were not aware that the free halogen residual was required to be above 2 ppm. For three dates since the last inspection, the free halogen residual was recorded as below 2 ppm and no corrective action was taken.
Recommendation: Ensure the supervisor or person in charge of potable water operations on the vessel demonstrates to VSP-during inspections and on request-knowledge of potable water operations, is able to demonstrate this knowledge by compliance with Section 5 of the VSP 2011 Operations Manual or by responding correctly to the inspector's questions as they relate to the specific operation, and properly trains employees to comply with Section 5 of the VSP 2011 Operations Manual as it relates to their assigned duties.
Item No.: 40
Site: Integrated Pest Management-Garbage Holding Area Inspections
Violation: There was no record of weekly active or passive inspections of the garbage holding area on board. This was written on the March 2018 inspection. Staff stated they checked the area frequently and had not observed any pests.
Recommendation: Inspect all food areas at a frequency that can quickly detect the evidence of pests, harborage conditions, cleanliness, and protection of outer openings. In nonfood areas, give reasonable care to conduct inspections for the presence of insects, rodents, and other pests. Inspect the garbage handling areas of the vessel at least weekly for the presence of insects, rodents, and other pests. Maintain the results of these inspections in a log.
Item No.: 41
Site: Housekeeping-Outbreak Prevention and Response Plan
Violation: The red level section of the plan for 'front of house' parts of food areas indicated that 200 ppm chlorine or another effective disinfectant would be used in these areas. However, the chlorine concentration must be at least 1000 ppm.
Recommendation: Ensure each vessel has a written OPRP that details standard procedures and policies to specifically address AGE onboard. Include the following in the written OPRP: (3) Disinfectant products or systems used, including the surfaces or items the disinfectants will be applied to, concentrations, and required contact times. Ensure the disinfectant products or systems are effective against human norovirus or an acceptable surrogate (e.g., caliciviruses).
Item No.: 33
Site: Provisions-Dry Store
Violation: The deck was made of a vinyl material, which was not considerable durable. In addition, it had many bumps, seams, ridges, and scratches. It was discussed that a painted steel deck would be acceptable and the vessel should let VSP know if they planned to replace the deck during the next dry dock. It was also discussed that if the deck below the vinyl material was still, it could be painted and would be acceptable as long as it was smooth and easily cleanable.
Recommendation: Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, bars, and food and equipment storage areas are constructed and maintained for easy cleaning. Do not use carpet in these areas.
Item No.: 33
Site: Provisions-Dry Store
Violation: No coving was installed at the deck/bulkhead juncture. The coving was on board the vessel and staff stated it would be installed the following day.
Recommendation: Cove all bulkhead/deck, equipment/deck, cabinet/deck, and deck sink coaming/deck junctures (including galleys, pantries, buffets, bars, waiter stations, dining room work counters, provisions, food storage rooms, equipment/utensil storage rooms, and toilet rooms intended for use by galley personnel).
Item No.: 16
Site: Galley-Beverage Station Refrigeration Unit
Violation: The inspector measured the temperature of individual single service butter packets stored in a hotel pan. Approximately 100 butter packets were in the pan. The temperatures of the butters ranged from 47-50°F. The other items in the refrigeration unit were under 41°F. Staff stated the butter may have been used for breakfast. The butter was discarded.
Recommendation: Except during preparation, cooking, or cooling, or when time is used as the public health control, maintain potentially hazardous foods at 57°C (135°F) or above, except that roasts may be held at a temperature of 54°C (130°F); or 5°C (41°F) or less.
Item No.: 30
Site: Galley-Handwash Station Near Walk-in Refrigerator
Violation: The hand soap dispenser was not dispensing soap. The soap container said 'hair and body soap.' The soap was immediately replaced. The area was not in use while the inspector was in the area.
Recommendation: Keep handwashing facilities clean and in good repair.
Item No.: 28
Site: Provisions-
Violation: Two stacks of plastic containers were stored under a stairwell in the provisions hallway. Staff stated these containers are sometimes used to bring food from provisions to the galley. The bulkhead in this area was not easily cleanable, The deck was corroded and not easily cleanable. There deckhead was not closed and had exposed wires.
Recommendation: Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination; (3) at least 150 millimeters (6 inches) above the deck.
Item No.: 28
Site: Buffet-Juice Machine
Violation: Crew members were putting the recently cleaned juice machine back together. The clear plastic portion of the juice machine had water pooled in it. Staff dumped the excess water into a nearby drain and sent the juice machine parts back to be rewashed.
Recommendation: Store clean equipment and utensils in a self-draining position that allows air drying, and covered or inverted.
Item No.: 37
Site: Galley-
Violation: A significant amount of condensation had collected above the combination ovens. The condensate was actively dripping, though no food was impacted. Staff stated the ventilation had been turned off. The ventilation was turned on and the area was wiped down. The inspector came back to the area later and verified the ventilation was working properly.
Recommendation: Ensure exhaust ventilation hood systems in food preparation and warewashing areas--including components such as hoods, fans, guards, and ducting--are designed to prevent grease or condensation from draining or dripping onto food, equipment, utensils, linens, and single-service and single-use articles.
Item No.: 29
Site: Galley-Bakery
Violation: The handwash sink, which was adjustable by the user, reached a maximum temperature of 91°F.
Recommendation: Ensure handwashing sinks are equipped to provide water at a temperature of at least 38°C (100°F) through a mixing valve or combination faucet. For handwash sinks with electronic sensors, and other types of handwash sinks where the user cannot make temperature adjustments, ensure the temperature provided to the user after the mixing valve does not exceed 49°C (120°F).
Item No.: 27
Site: Galley-
Violation: There was a hair on the light shield above the combination ovens.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 33
Site: Galley-Refrigeration Unit #5
Violation: Refrigeration unit #5 was leaking water from the evaporative condenser inside the unit. Staff had placed two trays directly under this leak to collect the dripping water. Water had also pooled on the bottom of the unit. Other than an unopened container of fish base, no food items were stored in this unit. Water was not dripping on the unopened container of fish base. The leak was noted on the previous inspection.
Recommendation: Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 22
Site: Galley-
Violation: The sanitizing bucket near refrigeration unit #8 was cloudy. The sanitizer was immediately replaced.
Recommendation: Ensure the wash, rinse, and sanitize solutions are maintained clean.
Item No.: 16
Site: Galley-Refrigeration Unit #8
Violation: A hotel pan of raw sliced bacon had a temperature of 45-46°F. A block of butter had a temperature of 44°F. A block of cream cheese had a temperature of 44°F. These items were discarded. All other items in the refrigerator were 41°F or below. Staff stated the bacon had been used at breakfast.
Recommendation: Except during preparation, cooking, or cooling, or when time is used as the public health control, maintain potentially hazardous foods at 57°C (135°F) or above, except that roasts may be held at a temperature of 54°C (130°F); or 5°C (41°F) or less.
Item No.: 18
Site: Galley-Refrigeration Unit #8
Violation: A block of cream cheese had pink spots where it had been sliced earlier that morning. The cream cheese was discarded.
Recommendation: Discard a food that is unsafe or adulterated.
Item No.: 17
Site: Galley-Cooling Logs
Violation: The cooling log showed a cooling record for 'pasta salad.' Staff stated the pasta is boiled and then cooled. The cooled pasta is then mixed with mayonnaise and other ingredients. Staff stated the line labeled 'pasta salad' on the cooling log is for the boiled pasta. There was not a second line for the cooling of the pasta with the mayonnaise and other ingredients. Pasta salad was prepared on April 12, April 13, April 16, April 19, April 26, April 27, and May 3.
Recommendation: Ensure logs documenting cooked potentially hazardous food cooling temperatures and times from the starting points designated in 7.3.5.2.1 thru the control points at 2 and 6 hours are maintained onboard the vessel for a period of 30 days from the date the food was placed in the cooling process. Ensure logs documenting cooling of potentially hazardous foods prepared from ingredients at ambient temperatures, with the start time to the time when 5°C (41 °F) is reached are also maintained for a period of 30 days, beginning with the day of preparation.
Item No.: 23
Site: Galley-Hood Type Pot Wash
Violation: The wash temperature of the hood type pot wash reached a maximum temperature of 145°F on the inspector's thermocouple. The wash temperature gauge also read 145°F.
Recommendation: Ensure the temperature of the wash solution in spray type warewashers that use hot water to sanitize is not less than: (1) 74°C (165°F) for a stationary-rack, single-temperature machine; (2) 66°C (150°F) for a stationary-rack, dual-temperature machine; (3) 71°C (160°F) for a single-tank, conveyor, dual-temperature machine; (4) 66°C (150°F) for a multi-tank, conveyor, multi-temperature machine.
Item No.: 22
Site: Galley-Hood Type Pot Wash
Violation: Three pans were loaded into the hood type pot wash in a manner that allowed water to collect in the bottom. Crew members had to dump the water out of the pans before removal from the potwash. Additionally four pans were stack in a manner that did not allow the spray to reach all surfaces of the pans. All pans were sent to be rewashed.
Recommendation: Ensure soiled items to be cleaned in a warewashing machine are loaded into racks, trays, or baskets or onto conveyors in a position that (1) exposes the items to the unobstructed spray from all cycles; (2) allows the items to drain.
Item No.: 22
Site: Galley-Dish Wash Machine
Violation: The conveyor dish wash was out of service since the last inspection on March 19. Staff stated the valve pump needed to be replaced in order for the machine to maintain proper temperatures. Staff stated the part had been ordered.
Recommendation: Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines.
Item No.: 22
Site: Galley-Dish Wash Machine
Violation: Water was leaking from the bottom of the dish wash machine. Staff stated the leak was coming from the valve pump area, which needed to be replaced.
Recommendation: Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines.
Item No.: 33
Site: Galley-Dish Wash Machine
Violation: Water had pooled on the deck underneath the dish wash machine.
Recommendation: Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 39
Site: Galley-Butcher
Violation: One house fly was observed in this area.
Recommendation: Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
Item No.: 39
Site: Galley-Butcher
Violation: One fruit fly was observed in this area.
Recommendation: Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
Item No.: 27
Site: Galley-Dry Store
Violation: The top shelf of the two dry store racks were soiled. They were immediately cleaned.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 39
Site: Buffet-
Violation: There were at least 10 drain flies in the right drain under the service line. The area was heavily soiled.
Recommendation: Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
Item No.: 33
Site: Buffet-
Violation: There were at least 10 drain flies in the right drain under the service line. The area was heavily soiled.
Recommendation: Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
*Inspections scores of 85 or lower are NOT satisfactory
Vessel Sanitation Program