Item No.:
08
|
|
Site:
Potable Water-Bunker Chlorination Station
|
|
Violation:
There were inconsistencies with striping on the 6 inch water line leading to the point of chlorination in the bunker area. The pipe was striped blue/blue/blue after chlorination and before chlorination for approximately 7 meters. Just inside the bulkhead penetration the pipe was striped blue/grey/blue. On the other side of the bulkhead this pipe was not striped at all. Staff explained this this pipe was a chlorinated fresh water line from tanks 9 and 10.
|
|
Recommendation:
Stripe or paint potable water lines either in accordance with ISO 14726 (blue/green/blue) or blue only. Stripe or paint distillate and permeate lines directed to the potable water system in accordance with ISO 14726 (blue/gray/blue). Ensure no other lines have the above color designations. Stripe or paint these lines at 5 meters (15 feet) intervals and on each side of partitions, decks, and bulkheads, except where decor would be marred by such markings, including potable water supply lines in technical lockers. Do not stripe or paint potable water lines after reduced pressure assemblies as potable water. Identify all refrigerant brine lines and nonpotable chilled water lines in all food areas, such as on ice machines, ice cream machines, etc., with either ISO 14726 (blue/white/blue) or by another uniquely identifiable method to prevent cross-connections.
|
|
|
Item No.:
36
|
|
Site:
Pantry-Ice Machine
|
|
Violation:
The lighting behind these machines was insufficient for cleaning on both decks. Staff indicated that there is a comprehensive relighting plan currently in place.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
39
|
|
Site:
Preparation Room-Orange Juice Machine
|
|
Violation:
Four fruit flies were on this previously cleaned machine. The area was not in use.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
39
|
|
Site:
Food Service General-
|
|
Violation:
Eight house flies were found in the following areas: 1) one fly in the starboard lido buffet during breakfast service; 2) one fly on the Trident Grill counter and two flies in the Trident Grill dining room while the area was preparing for opening; 3) one house fly in the main galley hot galley; 4) one fly in the main galley starboard dishwash area; 5) one fly in the Bistro galley pantry; and 6) one fly on a piece of bread out for service at the Bistro. In addition, there was a fruit fly on a bowl containing olives that was out for service at the Bistro.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
26
|
|
Site:
Buffet-Market Place Starboard Beverage Station
|
|
Violation:
The water dispenser was no longer being used as a new water dispensing system had been installed. The old water dispenser had small amounts of brown, black, and silver debris in the nozzle.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
38
|
|
Site:
Buffet-Market Place Beverage Stations
|
|
Violation:
The water dispenser at the starboard beverage station was no longer being used as a new water dispensing system had been installed. The old water dispenser had small amounts of brown, black, and silver debris in the nozzle. Crew reported the water dispenser at the port beverage station was also no longer needed for operation.
|
|
Recommendation:
Ensure only articles necessary for the food service operation are stored in food preparation, food storage, and warewashing areas.
|
|
|
Item No.:
27
|
|
Site:
Galley-Market Place Starboard Pantry
|
|
Violation:
The backflow prevention device and the attached pipe was soiled with greater than a day's accumulation of debris.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
22
|
|
Site:
Galley-Market Place Dishwash
|
|
Violation:
The rack-type conveyor dishwash was out of service since the morning of the inspection due to an issue with the final rinse temperature. Two rinse, five wash, and one pre-rinse nozzle were blocked with debris including food debris and chips of plastic or glass.
|
|
Recommendation:
Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
|
|
|
Item No.:
16
|
|
Site:
Galley-Market Place Walk-In Refrigerator
|
|
Violation:
The temprature of eight individual serving containers of yogurt were measured by the inspector between 43-47°F. The inspector used a sensitive tip thermometer with an error of accuracy of +/- 0.7°F. Crew measured similar temperatures with their sensitive tip thermometer. There were many other yogurts and potentially hazardous food in the refrigerator that measured the proper temperature, and the refrigerator unit measured at the proper temperature. Crew reported the food was brought up to the unit at approximately 0600 but the inspection was conducted at 0948. All food was maintained on temperature control. Yogurts that were measured in the danger zone were discarded.
|
|
Recommendation:
Except during preparation, cooking, or cooling, or when time is used as the public health control, maintain potentially hazardous foods at 57°C (135°F) or above, except that roasts may be held at a temperature of 54°C (130°F); or 5°C (41°F) or less.
|
|
|
Item No.:
28
|
|
Site:
Galley-Trident Grill Show Galley
|
|
Violation:
There was one house fly on the counter while crew were preparing to open the area.
|
|
Recommendation:
Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination; (3) at least 150 millimeters (6 inches) above the deck unless in packages on pallets, skids, or racks, which may be 127 millimeters (5 inches).
|
|
|
Item No.:
16
|
|
Site:
Galley-Trident Grill Show Galley
|
|
Violation:
Menu signs on the side bulkhead andthe small plastic stands and on the buffer counter did not include any asterisks to indicate that items could be served undercooked and did not include the advisory. On the right wall, a menu including all the food items was posted with asterisks after the food items that may be served undercooked; however, there was no asterisk on the sign that indicated what the asterisk meant. There was no public health advisory on the wall menu. There was a small menu on the service area that was designed the same as the wall menu on the right. There was one separate sign that indicated that burgers, steak, and salmon may be cooked to order and included the public health advisory. A similar violation was written on the previous report. Since the previous report, the venue had been renovated and changed.
|
|
Recommendation:
If time only?rather than time in conjunction with temperature?is used as the public health control for a working supply of potentially hazardous food before cooking, or for ready-to-eat potentially hazardous food that is displayed or held for service for immediate consumption, ensure the food (1) Has an initial temperature of 5°C (41°F) or less or 57°C (135°F) or greater before placement on time control. (2) Is not be placed on temperature control again. (3) Is marked, or otherwise identified, to indicate the time 4 hours past the point in time when the food is removed from temperature control (if the time between service set-up and closing is greater than 4 hours). (4) Is labeled with a 4-hour discard time if containers of potentially hazardous foods on time control are placed on preparation counters, even if the outlet is open less than 4 hours. (5) Is discarded within 4 hours of placement on time control. and (6) Is labeled with a 4-hour discard time if time control unit (bain marie, cold basin) meant to be cold holding or hot holding and not operational or used as intended, as the unit is now considered a counter.
|
|
|
Item No.:
28
|
|
Site:
Galley-Silk
|
|
Violation:
The plastic bin that contained single-use tasting spoons was soiled. The spoons were discarded.
|
|
Recommendation:
Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination; (3) at least 150 millimeters (6 inches) above the deck unless in packages on pallets, skids, or racks, which may be 127 millimeters (5 inches).
|
|
|
Item No.:
36
|
|
Site:
Food Service General-
|
|
Violation:
On multiple previous reports, the light intensity in various food service areas was found to be insufficient. Crew presented the inspectors with a plan for correcting the lighting issues. Phase 1 was already completed with some areas corrected during the previous dry dock and some during operations. Crew were in the process of completing phase 2, and expect the lighting issues to be corrected within the next six month.
|
|
Recommendation:
Ensure the light intensity is at least 220 lux (20 foot candles) on food preparation surfaces, and at a distance of 75 centimeters (30 inches) above the deck in food preparation areas, handwashing facilities, warewashing areas, equipment, and utensil storage, pantries, toilet rooms, and consumer self-service areas.
|
|
|
Item No.:
21
|
|
Site:
Galley-Silk Dishwash
|
|
Violation:
A large table had been placed next to the conveyor machine which limited the space to move around the hood-type and conveyor- type machines. Crew reported the table was necessary because they did not have enough sorting space. Crew presented documentation that a smaller table was on order. The top layer of the table that was in use with plates and trays had many areas that were cracked and difficult to clean.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning are constructed of a corrosion-resistant, nonabsorbent, and smooth material.
|
|
|
Item No.:
39
|
|
Site:
Galley-Silk
|
|
Violation:
There was one live ant crawling on the deck near the bottle and cans waste containers.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
33
|
|
Site:
Bar-Silk
|
|
Violation:
The deckhead over the bar area did not continue completely over the preparation area. There was a large gap that exposed the area above. There was a large glass deckhead above that area.
|
|
Recommendation:
Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, bars, and food and equipment storage areas are constructed and maintained for easy cleaning.
|
|
|
Item No.:
33
|
|
Site:
Dining Room-Waterside Aft
|
|
Violation:
A liquor cabinet and seven dishwash racks containing previously-cleaned bottles and glasses were stored in this area. The deck was carpeted and there were gaps between the deckhead panels which exposed the plenum above. The lighting levels were not confirmed.
|
|
Recommendation:
Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, bars, and food and equipment storage areas are constructed and maintained for easy cleaning. Do not use carpet in these areas.
|
|
|
Item No.:
28
|
|
Site:
Dining Room-Waterside Aft
|
|
Violation:
A liquor cabinet and seven dishwash racks containing previously-cleaned bottles and glasses were stored in this area. The deck was carpeted and there were gaps between the deckhead panels which exposed the plenum above. The lighting levels were not confirmed. The items were moved to a locker in the galley.
|
|
Recommendation:
Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination; (3) at least 150 millimeters (6 inches) above the deck unless in packages on pallets, skids, or racks, which may be 127 millimeters (5 inches).
|
|
|
Item No.:
20
|
|
Site:
Food Service General-Ice Machines
|
|
Violation:
Small rips were noted on the white plastic area of the outer ice machine panel that faced in towards the ice bin. The rips exposed the absorbable insulation. This was noted at the right ice machine at the port main galley ice station, the right ice machine at the starboard main galley ice station, and at the market place galley ice machine.
|
|
Recommendation:
Materials used in the construction of multiuse utensils and food contact surfaces of equipment must be: (1) durable, corrosion resistant, and nonabsorbent; (2) sufficient in weight and thickness to withstand repeated warewashing; (3) finished to have a smooth, easily cleanable surface; and (4) resistant to pitting, chipping, crazing, scratching, scoring, distortion and decomposition.
|
|
|
Item No.:
20
|
|
Site:
Galley-Port Cold Galley
|
|
Violation:
The previously-cleaned plastic bin inside the salad spinner was in disrepair. The plastic had chips and tears on the food contact surface. In addition, many of the small holes on the bottom of the bin were soiled with black debris. It was removed from service.
|
|
Recommendation:
Materials used in the construction of multiuse utensils and food contact surfaces of equipment must be: (1) durable, corrosion resistant, and nonabsorbent; (2) sufficient in weight and thickness to withstand repeated warewashing; (3) finished to have a smooth, easily cleanable surface; and (4) resistant to pitting, chipping, crazing, scratching, scoring, distortion and decomposition.
|
|
|
Item No.:
26
|
|
Site:
Galley-Port Cold Galley
|
|
Violation:
The previously-cleaned plastic bin inside the salad spinner was in disrepair. The plastic had chips and tears on the food contact surface. In addition, many of the small holes on the bottom of the bin were soiled with black debris. It was removed from service.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
26
|
|
Site:
Galley-Port Cold Galley
|
|
Violation:
The slicing track of the previously cleaned counter-mounted deli slicer was soiled with food debris. Crew began cleaning the machine.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
08
|
|
Site:
Galley-Cold Galley
|
|
Violation:
The backflow prevention device on the bucket fill at the handwash station next to the walk-in refrigerator was in disrepair. There was a hole in the top of the backflow preventer that appeared to be missing a screw. The inspector discussed sanitizing a new backflow preventer for 4 hours with 50 ppm prior to installation.
|
|
Recommendation:
Maintain backflow prevention devices in good repair.
|
|
|
Item No.:
20
|
|
Site:
Galley-Soup Station
|
|
Violation:
The far left kettle was leaking water which was dripping onto the deck. The gauges for the two left kettles had cracked which created a difficult to clean area. Crew reported they could no longer order replacement parts for the legacy equipment and had submitted a proposal for new machines. The far right kettles were leaking water from the area behind the technical space which pooled onto the deck in an area of recessed grout.
|
|
Recommendation:
Food contact equipment must be maintained in good repair and proper adjustment: (1) Equipment must be maintained in a state of repair and condition that meets the materials, design, construction, and operating specifications of these guidelines; and (2) Cutting or piercing parts of can openers must be kept sharp to minimize the creation of metal fragments that can contaminate food when the container is opened.
|
|
|
Item No.:
21
|
|
Site:
Galley-Soup Station
|
|
Violation:
The gauges for the two left kettles had cracked which created a difficult to clean area. Crew reported they could no longer order replacement parts for the legacy equipment and had submitted a proposal for new machines.
|
|
Recommendation:
Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
35
|
|
Site:
Galley-Soup Station
|
|
Violation:
The far left kettle was leaking water which was dripping onto and pooling on the deck. The gauges for the two left kettles had cracked which created a difficult to clean area. Crew reported they could no longer order replacement parts for the legacy equipment and had submitted a proposal for new machines. The far right kettles were leaking water from the area behind the technical space which pooled onto the deck in an area of recessed grout.
|
|
Recommendation:
Ensure black and gray water is discharged to the vessel's wastewater disposal system and does not pool on the deck.
|
|
|
Item No.:
33
|
|
Site:
Galley-Soup Station
|
|
Violation:
The far right kettles were leaking water from the area behind the technical space which pooled onto the deck in an area of recessed grout.
|
|
Recommendation:
Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
|
|
|
Item No.:
26
|
|
Site:
Galley-Hot Galley Baines-Marie
|
|
Violation:
The area had been previously-cleaned and crew were setting up the area for lunch at the time of the inspection, but a small amount of debris was noted under the over-shelf of two bains-marie in the food-splash area. The area would be above where food would be placed. No food was present. Crew began cleaning the area.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
38
|
|
Site:
Galley-Hot Galley
|
|
Violation:
Outside cold store 32 a wet mop was stored in a bucket in a manner that did not allow it to air dry.
|
|
Recommendation:
After use, ensure mops are placed in a position that allows them to air-dry without soiling walls, equipment, or supplies.
|
|
|
Item No.:
21
|
|
Site:
Galley-Hot Galley Blast Chiller
|
|
Violation:
There was no external or internal ambient temperature measuring device in this unit Crew installed an internal ambient temperature thermometer.
|
|
Recommendation:
Ensure temperature-measuring devices conform to the following guidelines: (1) In a mechanically refrigerated or hot-food storage unit, the sensor of a temperature-measuring device is located to measure the air temperature in the warmest part of a mechanically refrigerated unit and in the coolest part of a hot-food storage unit; (2) Cold or hot holding equipment used for potentially hazardous food is designed to include and equipped with at least one integral or affixed temperature-measuring device that is located to allow easy viewing of the device?s temperature display; (3) Temperature-measuring device is easily readable.
|
|
|
Item No.:
22
|
|
Site:
Galley-Potwash
|
|
Violation:
The overflow drain pipe for the three-compartment sink was leaking and pooling on the deck.
|
|
Recommendation:
Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
|
|
|
Item No.:
35
|
|
Site:
Galley-Potwash
|
|
Violation:
The overflow drain pipe for the three-compartment sink was leaking and pooling on the deck.
|
|
Recommendation:
Ensure black and gray water is discharged to the vessel's wastewater disposal system and does not pool on the deck.
|
|
|
Item No.:
35
|
|
Site:
Galley-Potwash
|
|
Violation:
During the draining part of the cycle of the front-loading potwash, water splashed and pooled on the deck. There was a hole that had been cut in the drain strainer, but it was not located in the area where the water was forcefully draining from.
|
|
Recommendation:
Ensure black and gray water is discharged to the vessel's wastewater disposal system and does not pool on the deck.
|
|
|
Item No.:
22
|
|
Site:
Galley-Potwash
|
|
Violation:
The front-loading potwash machine was in-use with various size pots and pans, pitchers, and other food service equipment but three of four final rinse spray arms were in disrepair. On the left upper final rinse spray arm, two nozzles were missing the caps and three nozzles were broken to the base. On the bottom left final rinse arm, four final rinse nozzle caps were missing in this machine. On the bottom right final rinse arm, one cap was missing and four nozzles were broken to the base. Crew noted all equipment also is sanitized in the three-compartment sink. The inspector was able to measure 160F at the plate surface.
|
|
Recommendation:
Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
|
|
|
Item No.:
08
|
|
Site:
Galley-Pastry
|
|
Violation:
The backflow prevention device on the bucket fill at the handwash station next to the sherbet machine was in disrepair. There was a hole in the top of the backflow preventer that appeared to be missing a screw and the top of the device was not in proper alignment. The inspector discussed sanitizing a new backflow preventer for 4 hours with 50 ppm prior to installation.
|
|
Recommendation:
Maintain backflow prevention devices in good repair.
|
|
|
Item No.:
21
|
|
Site:
Galley-Pastry
|
|
Violation:
The label on the chocolate melting machine was chipped and had started to peel off the machine, which created a difficult-to-clean area. Crew began removing the label.
|
|
Recommendation:
Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
28
|
|
Site:
Galley-Starboard Dishwash
|
|
Violation:
Two crew members were observed drying bowls with linen napkins at the clean end of the rack-type conveyor dishwash. Supervisors did not stop the process until the inspector noted the issue. The bowls were sent for rewash.
|
|
Recommendation:
After cleaning and sanitizing, ensure equipment and utensils are air dried or adequately drained before contact with food.
|
|
|
Item No.:
13
|
|
Site:
Galley-Starboard Dishwash
|
|
Violation:
Two crew members were observed drying bowling with linen napkins at the clean end of the rack-type conveyor dishwash. Supervisors did not stop the process until the inspector noted the issue. The bowls were sent for rewash. A supervisor noted that this was not the normal process for drying items.
|
|
Recommendation:
Because of the risks for foodborne illness inherent to the food operation, ensure the supervisor or person in charge of food operations on the vessel demonstrates to VSP - during inspections and on request - knowledge of foodborne disease prevention, application of the Hazard Analysis Critical Point principles, and the food-safety guidelines in this manual. Ensure that the person in charge demonstrates this knowledge: (1) By compliance with these guidelines; (2) By being a domestically or foreign certified food protection manager who has shown proficiency of required information through passing a test that is part of an accredited program; or (3) By responding correctly to the inspector's questions as they relate to the specific food operation. Ensure that the areas of knowledge include: (1) Describing the relation between prevention of foodborne disease and personal hygiene of a food employee; (2) Explaining the responsibility of the person in charge to prevent transmission of foodborne disease by a food employee who has a disease or medical condition that may cause foodborne disease; (3) Describing the symptoms associated with diseases that are transmissible through food; (4) Explaining the significance of the relation between maintaining the time and temperature of potentially hazardous food and the prevention of foodborne illness; (5) Explaining the hazards involved in the consumption of raw or undercooked meat, poultry, eggs, and fish; (6) Stating the required food temperatures and times for safe cooking of potentially hazardous food, including meat, poultry, eggs, and fish; (7) Stating the required temperatures and times for the safe refrigerated storage, hot holding, cooling, and reheating of potentially hazardous food; (8) Describing the relation between prevention of foodborne illness and management and control of the following: cross-contamination, hand contact with ready-to-eat foods, handwashing, and maintaining food operations in a clean condition and in good repair; (9) Explaining the relation between food safety and providing equipment that is sufficient in number and capacity as well as properly designed, constructed, located, installed, operated, maintained, and cleaned; (10) Explaining correct procedures for cleaning and sanitizing utensils and food-contact surfaces of equipment; (11) Identifying poisonous or toxic materials on the vessel and the procedures necessary to ensure they are safely stored, dispensed, used, and disposed of according to law; (12) Identifying critical-control points in the operation from purchasing through service that when not controlled may contribute to the transmission of foodborne illness and explaining steps taken to ensure the points are controlled in accordance with the guidelines in this manual.
|
|
|
Item No.:
35
|
|
Site:
Galley-Starboard Dishwash
|
|
Violation:
The flight-type conveyor dishwash machine was leaking water which was pooling on the deck. Additionally, water was overflowing from the drain and pooled on the deck.
|
|
Recommendation:
Ensure black and gray water is discharged to the vessel's wastewater disposal system and does not pool on the deck.
|
|
|
Item No.:
22
|
|
Site:
Galley-Starboard Dishwash
|
|
Violation:
The flight-type conveyor dishwash machine was leaking water which was pooling on the deck.
|
|
Recommendation:
Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
|
|
|
Item No.:
21
|
|
Site:
Galley-Bistro Pantry
|
|
Violation:
There was a cork board on the bulkhead near the walk-in refrigeration. The cork was absorbable and difficult to clean.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning are constructed of a corrosion-resistant, nonabsorbent, and smooth material.
|
|
|
Item No.:
20
|
|
Site:
Bar-Bistro
|
|
Violation:
There were three slotted fasteners on the food-contact surface of the espresso machine.
|
|
Recommendation:
Ensure multiuse food-contact surfaces are: (1) Smooth; (2) Free of breaks, open seams greater than 0.8 mm (1/32 inch), cracks, chips, inclusions, pits, and similar imperfections; (3) Free of sharp internal angles, corners, and crevices; (4) Finished to have smooth welds and joints; and (5) Accessible for cleaning and inspection by one of the following methods without being disassembled, by disassembling without the use of tools, or by easy disassembling with the use of handheld tools commonly available to maintenance and cleaning personnel. Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
|
|
|
Item No.:
21
|
|
Site:
Bar-Bistro
|
|
Violation:
The counter-mounted espresso machine was raised approximately 3.25 inches off the counter, and the lowest part of the machine was approximately 2 inches above the counter. This created a difficult-to-clean area. The counter below the machine was soiled with greater than a day's accumulation of coffee grounds. The espresso machine had been installed since the last inspection.
|
|
Recommendation:
Ensure table-mounted equipment that is not easily movable is elevated on legs that provide at least a 100 mm (4-inch) clearance between the table and the equipment.
|
|
|
Item No.:
27
|
|
Site:
Bar-Bistro
|
|
Violation:
The counter-mounted espresso machine was raised approximately 3.25 inches off the counter, and the lowest part of the machine was approximately 2 inches above the counter. This created a difficult-to-clean area. The counter below the machine was soiled with greater than a day's accumulation of coffee grounds. The espresso machine had been installed since the last inspection.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
28
|
|
Site:
Buffet-Bistro Island
|
|
Violation:
There was one fly on a piece of bread out for service.
|
|
Recommendation:
Protect food from contamination that may result from a physical, chemical, biological origin.
|
|
|
Item No.:
28
|
|
Site:
Buffet-Bistro Island
|
|
Violation:
There was a fruit fly on a bowl containing olives that was out for service at the Bistro.
|
|
Recommendation:
Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination; (3) at least 150 millimeters (6 inches) above the deck unless in packages on pallets, skids, or racks, which may be 127 millimeters (5 inches).
|
|