Item No.:
08
|
|
Site:
Other-Carbonator Room
|
|
Violation:
Two carbonator backflow preventers were installed with the relief vent facing upwards, which prevented proper release of the water. Water was observed in the backflow preventer.
|
|
Recommendation:
Install backflow prevention devices oriented so that the relief vent is facing down or to the side. Do not install backflow prevention devices so that the relief vent is facing up.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Engine Room
|
|
Violation:
The distillate line from evaporator #1 was not striped blue/grey/blue after the evaporator and leading to the mineralizer. Also, water lines from and going into the mineralizer were striped to indicate potable water.
|
|
Recommendation:
Stripe or paint potable water lines either in accordance with ISO 14726 (blue/green/blue) or blue only. Stripe or paint distillate and permeate lines directed to the potable water system in accordance with ISO 14726 (blue/gray/blue). Ensure no other lines have the above color designations. Stripe or paint these lines at 5 meters (15 feet) intervals and on each side of partitions, decks, and bulkheads, except where decor would be marred by such markings, including potable water supply lines in technical lockers. Do not stripe or paint potable water lines after reduced pressure assemblies as potable water. Uniquely identify all refrigerant brine lines in all galleys, pantries, and cold rooms to prevent cross-connections.
|
|
|
Item No.:
16
|
|
Site:
Galley-Rossini
|
|
Violation:
Three refrigerators designated for temperature control were out of temperature and contained potentially hazardous food that was above 5°C. The inspector calibrated two thermometers and the crew calibrated one thermometer in an ice bath prior to reading temperatures. Refrigerator #4 contained beef gravy. The inspector's thermometer read 45-47°F and the crew's thermometer read 8°C. The refrigerator's thermometer read 14°C. In refrigerator #8, a large cut of Parma ham was 44°F by the inspector's thermometer and 6.7°F by the crew's thermometer. Fresh cheese rolled in paprika was 47°F according to the inspector's thermometer and 8.6°C according to the crew's thermometer. Two rolls of approximately 10 cheese rolls were tested. White mousse prepared in small bowls was 46°F and a tray of pesto was at 48°F according to the inspector's thermometer. The refrigerator was 7°C. Refrigerator #6 contained an open carton of yogurt that was 43-44°F according to the inspector's thermometer and 6.5°C according to the crew's thermometer. The refrigerator was 7°C. All potentially hazardous food was disposed of.
|
|
Recommendation:
Except during preparation, cooking, or cooling, or when time is used as the public health control, maintain potentially hazardous foods at 57°C (135°F) or above, except that roasts may be held at a temperature of 54°C (130°F); or 5°C (41°F) or less.
|
|
|
Item No.:
19
|
|
Site:
Buffet-Calypso Starboard Pizza Station
|
|
Violation:
The pizza station was being used as a station for passengers with allergies during breakfast service. Four open boxes of gluten-free food were found in the display area above the buffet within passenger reach, including 3 boxes of crackers and one box of corn flakes. The boxes had been opened and the inner plastic packaging was also open. There were no service utensils. Crew reported that these boxes were not intended for guest consumption, but rather were for guests to be able to read the packaging and be informed about specific ingredients and allergens.
|
|
Recommendation:
Protect food on display from contamination by the use of packaging; counter, service line, or salad bar food guards; display cases; self-closing hinged lids; or other effective means. Provide food-dispensing utensils for each container displayed at a consumer self-service unit such as a buffet or salad bar. Protect food from contamination that may result from a physical, chemical, biological origin.
|
|
|
Item No.:
19
|
|
Site:
Provisions-Vegetable
|
|
Violation:
A box containing cut palms for decoration were stored in the vegetable provisions room.
|
|
Recommendation:
Protect food from contamination that may result from a physical, chemical, biological origin.
|
|
|
Item No.:
19
|
|
Site:
Galley-Calypso
|
|
Violation:
The protective coating on the light fixtures in the canopy hood above the grills and deep fat fryer was peeling. Two fixtures had been replaced with covers that did not have the sticky, peeling coating. This was noted on the previous report. Crew provided documentation that a work order was placed on 22 December 2016 for the order of additional light covers. The light fixtures were also noted in the Market Restaurant.
|
|
Recommendation:
Protect food from contamination that may result from a physical, chemical, biological origin. Protect food from contamination by storing the food: (1) Covered or otherwise protected; (2) In a clean, dry location; (3) Where it is not exposed to splash, dust, or other contamination; and (4) At least 15 centimeters (6 inches) above the deck.
|
|
|
Item No.:
20
|
|
Site:
Galley-Market Restaurant Pantry
|
|
Violation:
Two crushed ice machines had slotted screws on the food contact surface.
|
|
Recommendation:
Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
|
|
|
Item No.:
20
|
|
Site:
Galley-Rossini
|
|
Violation:
Multiple refrigerators designated for temperature control were out of temperature and contained potentially hazardous food. Refrigerator #4 was 14°C and contained beef gravy, an open milk carton, butter, and eggs. Refrigerator #8 was 7°C. The left side of refrigerator #8 contained approximately 15 open cheese products, a tray of cold cuts, a tray of sliced Parma ham, large (not sliced) cuts of Parma ham, and other miscellaneous meats. The right side of refrigerator #8 contained approximately two dozen small bowls of white mousse and a pan of pesto. Refrigerator #6 contained an open carton of yogurt, carton of open whipping cream, and bowl of horseradish with cream. Many foods were above 5°C. All potentially hazardous food was disposed of.
|
|
Recommendation:
Ensure equipment for cooling and heating food, and holding cold and hot food, is sufficient in number and capacity to maintain potentially hazardous food temperatures. Maintain utensils and temperature measuring devices in good repair and proper adjustment: (1) Utensils must be maintained in a state of repair or condition that meets the materials, design, and construction specifications of these guidelines, or the utensils must be discarded; (2) food temperature measuring devices must be calibrated in accordance with the manufacturer's specifications to ensure accuracy.
|
|
|
Item No.:
21
|
|
Site:
Buffet-Calypso Aft Beverage Station
|
|
Violation:
A cord from the counter-mounted milk dispenser was draped on the counter, making cleaning difficult.
|
|
Recommendation:
Elevate the cords above the counter.
|
|
|
Item No.:
21
|
|
Site:
Bar-Aida Bar
|
|
Violation:
Multiple cords from the counter-mounted espresso machine and milk cooler were draped on the counter, making cleaning difficult.
|
|
Recommendation:
Elevate cords above the counter.
|
|
|
Item No.:
22
|
|
Site:
Galley-Warewash
|
|
Violation:
The upper final rinse spray for the rack type dishwasher did not create a fan pattern and was therefore ineffective. This was immediately corrected.
|
|
Recommendation:
Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
|
|
|
Item No.:
26
|
|
Site:
Galley-Market Restaurant Pantry
|
|
Violation:
Ten of over 50 previously cleaned wine carafes were found soiled on the food contact surface. Carafes were stored on the clean storage rack near the ice machine.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
26
|
|
Site:
Pantry-Aida Bar
|
|
Violation:
Five previously cleaned beer glasses were soiled on the food-contact surface and stored on the clean dish rack.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
27
|
|
Site:
Pantry-Aida Bar
|
|
Violation:
There was one previously cleaned mug soiled on the nonfood-contact surface that was stored on the clean dish rack.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
27
|
|
Site:
Buffet-Calypso Aft Beverage Station
|
|
Violation:
A cord from the counter-mounted milk dispenser was draped on the counter, making cleaning difficult. The counter was soiled with greater than a day's accumulation of soil, including a dead fly.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
27
|
|
Site:
Bar-Aida Bar
|
|
Violation:
Multiple cords from the counter-mounted espresso machine and milk cooler were draped on the counter, making cleaning difficult. The counter was soiled with greater than a day's accumulation of debris.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
28
|
|
Site:
Galley-Calypso Pantry
|
|
Violation:
Two previously cleaned plastic bins were stored stacked together while wet in the clean storage area, preventing them from air drying.
|
|
Recommendation:
Store clean equipment and utensils in a self-draining position that allows air drying, and covered or inverted.
|
|
|
Item No.:
30
|
|
Site:
Galley-Warewash
|
|
Violation:
The sensor for the automatic paper towel dispenser for the handwash station next to the dishwash did not function. Crew immediately began work on the dispenser and a stack of paper towels were also brought to the handwash station.
|
|
Recommendation:
Ensure each handwashing facility has a supply of single-service paper towels available.
|
|
|
Item No.:
33
|
|
Site:
Galley-Market Restaurant Warewash
|
|
Violation:
Water was dripping from the deckhead above the soiled end of both rack type dishwashers. Crew reported that the dripping above the left-side machine was caused by the dishwasher on the deck above. Condensation accumulated above the soiled end of the right-side machine. No clean dishes were observed being impacted.
|
|
Recommendation:
Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
|
|
|
Item No.:
35
|
|
Site:
Preparation Room-Cold Galley Preparation Room
|
|
Violation:
The drain line on the front of the blast chiller was leaking onto the deck, causing standing water that was not directed to the drain. This was immediately corrected.
|
|
Recommendation:
Ensure black and gray water is discharged to the vessel's wastewater disposal system and does not pool on the deck.
|
|
|
Item No.:
35
|
|
Site:
Galley-Calypso
|
|
Violation:
There was standing water on the deck under the handwash sink in the warewash area near the clean dish racks. Crew reported the water was coming from a blocked pipe.
|
|
Recommendation:
Ensure black and gray water is discharged to the vessel's wastewater disposal system and does not pool on the deck.
|
|
|
Item No.:
37
|
|
Site:
Galley-Market Restaurant Warewash
|
|
Violation:
Condensation accumulated above the soiled end of the right-side dishwash machine. Dripping was noted. No clean dishes were observed being impacted.
|
|
Recommendation:
Ensure ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads. Ensure all food preparation, warewashing, and toilet rooms have sufficient ventilation to keep them free of excessive heat, steam, condensation, vapors, obnoxious odors, smoke, and fumes. Ensure exhaust ventilation hood systems in food preparation and warewashing areas--including components such as hoods, fans, guards, and ducting--are designed to prevent grease or condensation from draining or dripping onto food, equipment, utensils, linens, and single-service and single-use articles.
|
|
|
Item No.:
38
|
|
Site:
Provisions-Vegetable
|
|
Violation:
Three carts, including 2 luggage carts from airports, that were used for nonfood items such as office supplies, were stored in the vegetable provisions room.
|
|
Recommendation:
Ensure only articles necessary for the food service operation are stored in food preparation, food storage, and warewashing areas.
|
|
|
Item No.:
38
|
|
Site:
Buffet-Calypso Aft Beverage Station
|
|
Violation:
A bucket of bleach solution was stored in an undercounter technical space. The space was not designated for cleaning materials only. No food was stored in this area.
|
|
Recommendation:
Label the locker "CLEANING MATERIALS ONLY."
|
|
|
Item No.:
38
|
|
Site:
Provisions-Vegetable
|
|
Violation:
A box containing cut palms for decoration were stored in the vegetable provisions room.
|
|
Recommendation:
Ensure only articles necessary for the food service operation are stored in food preparation, food storage, and warewashing areas.
|
|
|
Item No.:
40
|
|
Site:
Integrated Pest Management-Mooring Lines
|
|
Violation:
Some of the rat guards did not protect rodents from entering the ship. The black rubber guards were two half-circle pieces placed together, but some were misaligned and open on the bottom of the lines. Also, many guards were resting against the hull of the ship.
|
|
Recommendation:
Protect entry points where pests may enter the food areas.
|
|
|
Item No.:
40
|
|
Site:
Buffet-Calypso Aft Beverage Station
|
|
Violation:
A dead fly was on the counter behind the milk dispenser.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel. Remove dead or trapped insects, rodents, and other pests from control devices and the vessel at a frequency that prevents their accumulation or decomposition or the attraction of other pests.
|
|
|
Item No.:
41
|
|
Site:
Housekeeping-Outbreak Prevention and Response Plan (OPRP)
|
|
Violation:
During red level, Meliseptol Foam was used on designated sensitive surfaces, such as touch screens. No information was available to indicate this product was effective against norovirus. Also, there were no procedures to protect passengers from exposure to disinfectants when using the foggers (nebulizers) in areas such as cabins or theater.
|
|
Recommendation:
Ensure each vessel has a written OPRP that details standard procedures and policies to specifically address AGE onboard. Include the following in the written OPRP: (3) Disinfectant products or systems used, including the surfaces or items the disinfectants will be applied to, concentrations, and required contact times. Ensure the disinfectant products or systems are effective against human norovirus or an acceptable surrogate (e.g., caliciviruses); (6) Procedures to protect the passengers and crew from exposure to disinfectants, if not already included in the vessel?s safety management system. Ensure this protection includes: (a) Material safety data sheets (MSDSs); (b) Personal protective equipment for crew; (c) Health and safety procedures to minimize respiratory and dermal exposures to both passengers and crew.
|
|
|
Item No.:
41
|
|
Site:
Housekeeping-Outbreak Prevention and Response Plan (OPRP)
|
|
Violation:
Letters to inform passengers and crew during and following outbreak voyages stated 'due to elevated cases of viral gastrointestinal infection....' This wording assumed that all outbreaks were caused by viral pathogens. It was advised to remove the word 'viral' since the cause of the outbreaks are not confirmed until laboratory confirmation.
|
|
Recommendation:
Remove the word 'viral' from the referenced statement.
|
|