|
|
|
Item No.:
*
|
|
Site:
Recreational Water Facilities-Deck 7 Swimming Pool
|
|
Violation:
Black particles were in the pool water and on the beach access area. Staff explained maintenance work was being conducted in the funnel. The pool was open, but no passengers were in the area.
|
|
Recommendation:
Keep recreational water facilities clean.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Nontestable Device Inspections
|
|
Violation:
Visual inspection results of the nontestable backflow preventers were not documented. Inspections were conducted in February 2017.
|
|
Recommendation:
Inspect backflow prevention devices periodically and replace any failed units. Retain the inspection and test results for backflow prevention devices for at least 12 months and ensure they are available for review during inspections.
|
|
|
Item No.:
09
|
|
Site:
Recreational Water Facilities-Swimming Pools
|
|
Violation:
On 15 February, the chart record for the deck 7 pool indicated less than 1 ppm chlorine from 12:30 - 13:30 while the pool was in operation. On 13 February, the chart record for the deck 11 pool indicated less than 1 ppm chlorine from 16:10 - 18:00. The pool was closed after this time. No notations were recorded to state actions taken during these low chlorine values.
|
|
Recommendation:
Maintain a free residual halogen in recirculated RWFs in the following ranges: (1) swimming pools, between 1.0 and 5.0 mg/L (ppm).
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Whirlpool Spa Water Draining
|
|
Violation:
Draining of the water in the whirlpool spas was not documented.
|
|
Recommendation:
Ensure a written or electronic record of the date and time of water dumping and shock halogenation (concentration in ppm at the start and completion and time) is available for review during inspections.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Whirlpool Spa Shock Chlorination
|
|
Violation:
Some charts indicated shock chlorination was not performed for the entire hour. On 22 February in the deck 7 port and starboard whirlpool spas, shock chlorination started at 19:00 at 10 ppm chlorine and immediately dropped to 7.5 ppm, and increased to 10 ppm from 20:00 - 20:30; On 18 February, shock chlorination was conducted from 19:10 - 19:45; On 25 February, shock chlorination was conducted from 19:40 - 20:30.
|
|
Recommendation:
Increase the free residual halogen to at least 10.0 mg/L (ppm) and circulate for at least 1 hour every 24 hours. Test the free residual halogen both at the start and completion of shock halogenation. Superhalogenate the water in the entire RWF system to 10 ppm to include the whirlpool spa/spa pool tub, compensation tank, filter housing, and all associated piping before starting the 1-hour timing.
|
|
|
Item No.:
19
|
|
Site:
Galley-Waiter Serving Line
|
|
Violation:
The plastic covering on two of the shatter-resistant bulbs was bubbling, cracked, and peeling off above serving plates positioned under them.
|
|
Recommendation:
Protect food from contamination by storing the food: (3) Where it is not exposed to splash, dust, or other contamination.
|
|
|
Item No.:
19
|
|
Site:
Provisions-Ice Cream
|
|
Violation:
Frozen condensate and an accumulation of ice were on two boxes of crepes stored under the condenser. The accumulation appeared to originate from the condenser.
|
|
Recommendation:
Protect food from contamination by storing the food: (2) In a clean, dry location; (3) Where it is not exposed to splash, dust, or other contamination.
|
|
|
Item No.:
19
|
|
Site:
Bar-Lido Pantry
|
|
Violation:
Open and closed bottles of liquor and other foods were stored on a stainless steel shelf constructed in an office space down a hallway off of this bar. The room was not constructed in accordance with food storage standards.
|
|
Recommendation:
Protect food from contamination by storing the food: (3) Where it is not exposed to splash, dust, or other contamination. Do not store foods: (10) In areas not finished in accordance with 7.7.4 and 7.7.5 for food storage areas.
|
|
|
Item No.:
20
|
|
Site:
Galley-
|
|
Violation:
In the clean area of the dishwash, a previously cleaned cutting board had plastic fibers protruding from the food contact surface.
|
|
Recommendation:
Materials used in the construction of multiuse utensils and food contact surfaces of equipment must be: (3) finished to have a smooth, easily cleanable surface.
|
|
|
Item No.:
22
|
|
Site:
Galley-Ballindalloch
|
|
Violation:
While the galley was in service, a bucket of sanitizing solution was dirty and cloudy.
|
|
Recommendation:
Ensure the wash, rinse, and sanitize solutions are maintained clean.
|
|
|
Item No.:
24
|
|
Site:
Buffet-Palms Cafe
|
|
Violation:
During breakfast clean up, the rack-type warewash gauge for the final rinse temperature indicated 182°F while the machine was in use. Two consecutive attempts were made to measure the final rinse. The inspector measured 157°F and 152°F. The ship staff measured 155°F and 146°F. Shortly after leaving the area the inspector was summoned back to the area and presented a thermometer that registered 164°F. Upon taking measurements again with a staff member, the inspector measured 157°F and the crew member measured 153°F. Approximately three trays of dishes were observed as cleaned just pervious to the inspector arrival.
|
|
Recommendation:
In a mechanical operation, ensure the temperature of the fresh hot water sanitizing rinse as it enters the manifold is not more than 90°C (194°F) or less than: (1) 74°C (165°F) for a stationary rack, single-temperature machine; (2) 82°C (180°F) for all other machines. Ensure the utensil surface temperature is not less than 71°C (160°F) as measured by an irreversible registering temperature indicator.
|
|
|
Item No.:
26
|
|
Site:
Galley-Dishwash
|
|
Violation:
A tray of six previously cleaned coffee cups and saucers contained old coffee residue. The residue was easily cleaned off with an alcohol wipe. Most of the build-up was on the bottom with some build-up was on the inside of cup.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
28
|
|
Site:
Dining Room-Ballindalloch
|
|
Violation:
In the large dining room adjacent to the cafe, staff was observed polishing the coffee cups with a white towel. When the inspector examined the towel it was found to be wet.
|
|
Recommendation:
After cleaning and sanitizing, ensure equipment and utensils are air dried or adequately drained before contact with food.
|
|
|
Item No.:
28
|
|
Site:
Galley-Dishwash
|
|
Violation:
The water on top of the rack-type dishwash machine from condensate was being blown across the small walkway approximately one meter and landing on a rack of previously cleaned dishware.
|
|
Recommendation:
Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination.
|
|
|
Item No.:
28
|
|
Site:
Buffet-Palms Cafe
|
|
Violation:
On the clean side of the rack-type machine condensation was collecting at the ventilation duct and dripping back onto clean plates exiting the machine at the rate of one drip per second. Three full racks of plates were seen exiting the machine with water on them.
|
|
Recommendation:
Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination.
|
|
|
Item No.:
28
|
|
Site:
Galley-Dishwash
|
|
Violation:
A tray of six previously cleaned coffee cups and saucers contained old coffee residue. The residue was easily cleaned off with an alcohol wipe. Most of the build-up was on the bottom with some build-up was on the inside of cup.
|
|
Recommendation:
Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination.
|
|
|
Item No.:
33
|
|
Site:
Buffet-Palms Cafe
|
|
Violation:
The area adjacent to the deck in the technical space in the center serving line was heavily soiled with dust greater than one day's accumulation. The area was not in operation during the inspection.
|
|
Recommendation:
Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
|
|
|
Item No.:
33
|
|
Site:
Galley-Ballindalloch
|
|
Violation:
Standing water from unit 41 condenser was observed on the cold pantry deck. A green slime containing insect eggs extended for approximately 5 cm high and for 4 meters along the bulkhead.
|
|
Recommendation:
Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
|
|
|
Item No.:
33
|
|
Site:
Provisions-Ice Cream
|
|
Violation:
The deckhead contained a significant amount (3-6 cm) of frost condensate on the deckhead. There was no provisioning the day of the inspection.
|
|
Recommendation:
Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
|
|
|
Item No.:
35
|
|
Site:
Galley-Dishwash
|
|
Violation:
When water was running in the far left three-compartment sink it splashed and drained onto the deck. A significant amount of water was on the deck.
|
|
Recommendation:
Ensure black and gray water is discharged to the vessel's wastewater disposal system and does not pool on the deck.
|
|
|
Item No.:
37
|
|
Site:
Buffet-Palms Cafe
|
|
Violation:
A significant amount of condensation was at the dirty end of the rack-type machine on the deckhead and dripping onto the dirty area.
|
|
Recommendation:
Ensure exhaust ventilation hood systems in food preparation and warewashing areas--including components such as hoods, fans, guards, and ducting--are designed to prevent grease or condensation from draining or dripping onto food, equipment, utensils, linens, and single-service and single-use articles.
|
|
|
Item No.:
37
|
|
Site:
Buffet-Palms Cafe
|
|
Violation:
On the clean side of the rack-type machine condensation was collecting at the ventilation duct and dripping back onto clean plates exiting the machine at the rate of one drip per second. Three full racks of plates were seen exiting the machine with water on them.
|
|
Recommendation:
Ensure exhaust ventilation hood systems in food preparation and warewashing areas--including components such as hoods, fans, guards, and ducting--are designed to prevent grease or condensation from draining or dripping onto food, equipment, utensils, linens, and single-service and single-use articles.
|
|
|
Item No.:
37
|
|
Site:
Galley-Dishwash
|
|
Violation:
A significant amount of steam was being pulled through the ventilation shaft at the end of the machine. Water from the steam was collecting at the interface between the ventilation shaft and the top of the dishwasher and dripping back into the clean area of the washer.
|
|
Recommendation:
Ensure all food preparation, warewashing, and toilet rooms have sufficient ventilation to keep them free of excessive heat, steam, condensation, vapors, obnoxious odors, smoke, and fumes.
|
|
|
Item No.:
37
|
|
Site:
Galley-
|
|
Violation:
A large amount of condensation was collecting over the dirty end of the conveyor dishwasher and dripping onto the dirty end. No clean plates were impacted.
|
|
Recommendation:
Ensure ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.
|
|
|
Item No.:
40
|
|
Site:
Integrated Pest Management-Mooring Lines
|
|
Violation:
The rat guards on the mooring lines were placed in a manner that did not prevent rodents from entering the ship. Where two mooring lines came together near the pier, a large opening was between the two lines at the guards. Some guards were U-shaped and the bottom portion was open, and were blowing in the wind. Some guards were placed near the hull of the ship.
|
|
Recommendation:
Protect entry points where pests may enter the food areas.
|
|