Item No.:
02
|
|
Site:
Medical-Acute Gastroenteritis (AGE) Record Review
|
|
Violation:
No underlying illness information was recorded in the AGE log for one of the patients seen by medical staff on the November 10- November 20 voyage. No underlying illness information was noted in the patient's medical record either.
|
|
Recommendation:
Ensure the AGE surveillance log entry for each passenger or crew member contain the following information in separate columns: (1) Date of the first medical visit or report to staff of illness; (2) time of the first medical visit or report to staff of illness; (3) case identification number; (4) person?s name; (5) person?s age; (6) person?s sex; (7) designation as passenger or crew member; (8) crew member position or job on the vessel, if applicable; (9) cabin number; (10) meal seating information; (11) date of illness onset; (12) time of illness onset; (13) illness symptoms, including the presence or absence of the following selected signs and symptoms, with a separate column for each of the following: (a) number of episodes of diarrhea in a 24-hour period; (b) number of episodes of vomiting in a 24-hour period; (c) bloody stools; (d) recorded temperature; (e) abdominal cramps; (f) headaches; (g) muscle aches; (14) entry (yes/no) for whether this was a reportable case; (15) entry (yes/no) for antidiarrheal medications sold or dispensed by designated medical staff; (16) presence of underlying medical conditions that may affect interpretation of AGE. Ensure the AGE surveillance log contains the above information in the exact order and is entered in the template in Annex 13.2.2. Ensure that the log data is exported in the exact order as in the example template in Annex 13.2.2 with analyzable formats such as Excel or Access. Ensure that any additional data fields are entered only outside of the form margins when exported to VSP.
|
|
|
Item No.:
02
|
|
Site:
Medical-AGE Close Contact Record Review
|
|
Violation:
On the October 31- November 10 voyage, two initial close contact interviews were not conducted within 8 hours.
|
|
Recommendation:
When any crew member (food or nonfood employee) meets the case definition for AGE, take the following actions: (1) restrict exposure to symptomatic crew member(s); (2) undergo a verbal interview with medical or supervisory staff, who will confirm their condition, provide facts and a written fact sheet about hygiene and handwashing, and instruct them to report immediately to medical if they develop illness symptoms; (3) complete a verbal interview daily with medical or supervisory staff until 48 hours after the ill crew members? symptoms began. Ensure that the first verbal interview is conducted within 8 hours from the time the ill crew member initially reported to the medical staff. If the asymptomatic immediate contact or cabin mate is at work, ensure that he or she must is contacted by medical or supervisory staff as soon as possible. Document the date and time of verbal interviews.
|
|
|
Item No.:
10
|
|
Site:
Housekeeping-Private Cabin Whirlpool Spa Disinfection Records
|
|
Violation:
The cleaning and disinfection log could not be located for November 17. The ship was on a 10 day voyage, with turnaround days occurring on Nov 10 and Nov 20. There were no other records indicating the cabin whirlpools spas had been disinfected at least weekly during this voyage.
|
|
Recommendation:
Clean and disinfect private whirlpool spas located in individual passenger cabins, including associated recirculation systems, between occupancies or weekly, whichever is more frequent. Ensure disinfection is accomplished with an appropriate halogen-based disinfectant at 10 ppm for 60 minutes, or an equivalent CT value.
|
|
|
Item No.:
27
|
|
Site:
Housekeeping-Deck 11 Midship Pantry
|
|
Violation:
The two ice machine drain trays, especially the top drain tray, were soiled with brown/black debris.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
27
|
|
Site:
Housekeeping-Deck 10 Midship Pantry
|
|
Violation:
The two drain trays in the ice machine were soiled with brown/black debris.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
27
|
|
Site:
Housekeeping-Deck 8 Midship Pantry
|
|
Violation:
The two drain trays in the ice machine were soiled with brown/black debris.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
22
|
|
Site:
Room Service-Dishwash
|
|
Violation:
The upper final rinse arm of the in-use rack-type warewashing machine had the far right nozzle blocked, creating an ineffective spray pattern. This was corrected.
|
|
Recommendation:
Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
|
|
|
Item No.:
33
|
|
Site:
Galley-Sabatini
|
|
Violation:
Three screws were heavily corroded on the bulkhead above the handwashing station. Corrections started immediately.
|
|
Recommendation:
Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are corrosion resistant. Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
|
|
|
Item No.:
33
|
|
Site:
Galley-Crown Grill Show Galley
|
|
Violation:
The deck had no coving.
|
|
Recommendation:
Cove all bulkhead/deck, equipment/deck, cabinet/deck, and deck sink coaming/deck junctures (including galleys, pantries, buffets, bars, waiter stations, dining room work counters, provisions, food storage rooms, equipment/utensil storage rooms, and toilet rooms intended for use by galley personnel).
|
|
|
Item No.:
39
|
|
Site:
Galley-Deck 6 Garde Manger
|
|
Violation:
A fruit fly was on top of the film covering a pan of croutons.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
28
|
|
Site:
Galley-Deck 5 Hot Section
|
|
Violation:
Approximately 10 single-use tasting spoons were stored in a cup that was soiled inside with food debris.
|
|
Recommendation:
Keep single-service and single-use articles in the original protective package or store by using other means that afford protection from contamination until used.
|
|
|
Item No.:
22
|
|
Site:
Galley-Deck 5 Potwash
|
|
Violation:
The potwash machine was out of service since 15 November. Staff stated they were waiting for a spare part that had an estimated arrival to the ship of 20 December.
|
|
Recommendation:
Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
|
|
|
Item No.:
39
|
|
Site:
Galley-Deck 5 Potwash
|
|
Violation:
A fruit fly was in the area while the area was operational.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
22
|
|
Site:
Preparation Room-
|
|
Violation:
The undercounter warewash machine was out of service since the day prior to the inspection. Staff stated that the spare part to repair it arrived the day of the inspection.
|
|
Recommendation:
Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
|
|
|
Item No.:
39
|
|
Site:
Preparation Room-
|
|
Violation:
A fruit fly was in the area during food preparation.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
22
|
|
Site:
Bar-Coffee & Cones
|
|
Violation:
The undercounter warewash machine was out of service.
|
|
Recommendation:
Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
|
|
|
Item No.:
22
|
|
Site:
Galley-Burger and Pizzeria Dishwash
|
|
Violation:
The side-loading rack-type warewash machine was out of service.
|
|
Recommendation:
Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
|
|
|
Item No.:
33
|
|
Site:
Galley-Pizzeria
|
|
Violation:
The deck had no coving.
|
|
Recommendation:
Cove all bulkhead/deck, equipment/deck, cabinet/deck, and deck sink coaming/deck junctures (including galleys, pantries, buffets, bars, waiter stations, dining room work counters, provisions, food storage rooms, equipment/utensil storage rooms, and toilet rooms intended for use by galley personnel).
|
|
|
Item No.:
22
|
|
Site:
Pantry-Crooners
|
|
Violation:
The in-use undercounter warewash's display was showing an E7 error message. The machine was evaluated repeatedly and the wash temperature was 124-134°F and the final rinse was 126-145°F at the utensil surface. The display was reading exactly what was found during the wash cycles but up to 178°F for the final rinse cycles, indicating a possible malfunction of the final rinse gauge. Corrections started immediately.
|
|
Recommendation:
Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
|
|
|
Item No.:
23
|
|
Site:
Pantry-Crooners
|
|
Violation:
The in-use undercounter warewash's display was showing an E7 error message. The machine was evaluated repeatedly and the wash temperature was 124-134°F. The display was reading exactly what was found during the wash cycles. Corrections started immediately.
|
|
Recommendation:
Ensure the temperature of the wash solution in spray type warewashers that use hot water to sanitize is not less than: (1) 74°C (165°F) for a stationary-rack, single-temperature machine; (2) 66°C (150°F) for a stationary-rack, dual-temperature machine; (3) 71°C (160°F) for a single-tank, conveyor, dual-temperature machine; (4) 66°C (150°F) for a multi-tank, conveyor, multi-temperature machine.
|
|
|
Item No.:
24
|
|
Site:
Pantry-Crooners
|
|
Violation:
The in-use undercounter warewash's display was showing an E7 error message. The machine was evaluated repeatedly and the final rinse was 126-145°F at the utensil surface. The display was reading up to 178°F for the final rinse cycles, indicating a possible malfunction of the final rinse gauge. Corrections started immediately.
|
|
Recommendation:
In a mechanical operation, ensure the temperature of the fresh hot water sanitizing rinse as it enters the manifold is not more than 90°C (194°F) or less than: (1) 74°C (165°F) for a stationary rack, single-temperature machine; (2) 82°C (180°F) for all other machines. Ensure the utensil surface temperature is not less than 71°C (160°F) as measured by an irreversible registering temperature indicator.
|
|
|
Item No.:
13
|
|
Site:
Pantry-Crooners
|
|
Violation:
The in-use undercounter warewash's display was showing an E7 error message. The crew and supervisory personnel were operating the machine, even with the error message. The machine was evaluated repeatedly and the wash temperature was 124-134°F and the final rinse was 126-145°F at the utensil surface. The display was reading exactly what was found during the wash cycles but up to 178°F for the final rinse cycles, indicating a possible malfunction of the final rinse gauge. Corrections started immediately.
|
|
Recommendation:
Because of the risks for foodborne illness inherent to the food operation, ensure the supervisor or person in charge of food operations on the vessel demonstrates to VSP - during inspections and on request - knowledge of foodborne disease prevention, application of the Hazard Analysis Critical Point principles, and the food-safety guidelines in this manual. Ensure that the person in charge demonstrates this knowledge: (1) By compliance with these guidelines; (2) By being a domestically or foreign certified food protection manager who has shown proficiency of required information through passing a test that is part of an accredited program; or (3) By responding correctly to the inspector's questions as they relate to the specific food operation. Ensure that the areas of knowledge include: (1) Describing the relation between prevention of foodborne disease and personal hygiene of a food employee; (2) Explaining the responsibility of the person in charge to prevent transmission of foodborne disease by a food employee who has a disease or medical condition that may cause foodborne disease; (3) Describing the symptoms associated with diseases that are transmissible through food; (4) Explaining the significance of the relation between maintaining the time and temperature of potentially hazardous food and the prevention of foodborne illness; (5) Explaining the hazards involved in the consumption of raw or undercooked meat, poultry, eggs, and fish; (6) Stating the required food temperatures and times for safe cooking of potentially hazardous food, including meat, poultry, eggs, and fish; (7) Stating the required temperatures and times for the safe refrigerated storage, hot holding, cooling, and reheating of potentially hazardous food; (8) Describing the relation between prevention of foodborne illness and management and control of the following: cross-contamination, hand contact with ready-to-eat foods, handwashing, and maintaining food operations in a clean condition and in good repair; (9) Explaining the relation between food safety and providing equipment that is sufficient in number and capacity as well as properly designed, constructed, located, installed, operated, maintained, and cleaned; (10) Explaining correct procedures for cleaning and sanitizing utensils and food-contact surfaces of equipment; (11) Identifying poisonous or toxic materials on the vessel and the procedures necessary to ensure they are safely stored, dispensed, used, and disposed of according to law; (12) Identifying critical-control pints in the operation from purchasing through service that when not controlled may contribute to the transmission of foodborne illness and explaining steps taken to ensure the points are controlled in accordance with the guidelines in this manual.
|
|
|
Item No.:
21
|
|
Site:
Bar-International Café
|
|
Violation:
The back bar counter was covered with contact paper that simulated wood. The contact paper was peeling by the doors and storage areas. This created very difficult to clean surfaces,
|
|
Recommendation:
Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
36
|
|
Site:
Bar-International Café
|
|
Violation:
The light intensity could not be raised to 220 lux for cleaning operations. Staff stated that a light switch controlled the ambient light in the lobby area, including the bar. Even at the highest setting, the light intensity was about 50 lux.
|
|
Recommendation:
Ensure the light intensity is at least 220 lux (20 foot candles) on food preparation surfaces, and at a distance of 75 centimeters (30 inches) above the deck in food preparation areas, handwashing facilities, warewashing areas, equipment, and utensil storage, pantries, toilet rooms, and consumer self-service areas.
|
|
|
Item No.:
34
|
|
Site:
Bar-International Café
|
|
Violation:
The utility sink was continuously leaking. Corrections started immediately.
|
|
Recommendation:
Ensure a plumbing system in a food area is maintained in good repair.
|
|