Cruise Ship: Pearl Mist Cruise Line: V. Ships Leisure U.S.A. Inspection Date: 11/30/2017 Inspection Score: 87
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: *
Site: Potable Water-Throughout Ship
Violation: The potable water was found throughout the ship to be a yellow/brown color, including at the sample cock of potable water tank 4, sanitizing bucket in the preparation room, the 3 compartment sink in main galley, medical toilet room sink, sanitizing buckets in the main galley, and in other areas. The engineering staff stated the discoloration was from the old pipes and he had reported it to the company. He was unsure what kind of pipes were installed, but stated they needed to be replaced.
Recommendation: VSP recommends testing for metals in the potable water system.
Item No.: 38
Site: Provisions-Corridor
Violation: A large, out-of-service stand mixer was stored soiled on the deck in the provisions corridor. There was a large black plastic trash bag covering part of the mixer with an 'out of service' sign. There were paper towels balled up in the mixing bowl. Crew reported the mixer had been out-of-service for approximately 6 months and they were waiting for approval to offload the machine.
Recommendation: Ensure only articles necessary for the food service operation are stored in food preparation, food storage, and warewashing areas.
Item No.: 26
Site: Provisions-Corridor
Violation: A large, out-of-service stand mixer was stored soiled with food debris on the deck in the provisions corridor. There was a large black plastic trash bag covering part of the mixer with an 'out of service' sign. There were paper towels balled up in the mixing bowl. Crew reported the mixer had been out-of-service for approximately 6 months and they were waiting for approval to offload the machine.
Recommendation: Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
Item No.: 27
Site: Provisions-Corridor
Violation: A large, out-of-service stand mixer was stored soiled with food debris on the deck in the provisions corridor. There was a large black plastic trash bag covering part of the mixer with an 'out of service' sign. There were paper towels balled up in the mixing bowl. Crew reported the mixer had been out-of-service for approximately 6 months and they were waiting for approval to offload the machine.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 03
Site: Potable Water-Bunkering
Violation: Crew began bunkering water at 6:50 AM. At 7:10 AM, the chlorine was recorded in the log as 2.31 ppm and pH was 7.64. Recorded readings at 7:30 AM and 8:30 AM were within range. There was no note of a calibration done the morning of the inspection. At 8:50 AM, the inspector began inspecting the area and the following chlorine measurements were obtained: 1) 2.13ppm (analyzer), 1.52ppm (inspector), 1.13ppm (crew) and 2) 2.01ppm (analyzer), 1.41ppm (inspector). At this time the crew increased the chlorination and the analyzer values began increasing. The following values were measured 1) 3.68ppm (analyzer), 4.75ppm (crew) and 2) 5.16ppm (analyzer), 6.02ppm (inspector). The analyzer values increased to over 5.2 ppm before they began to drop again. The crew reported they were going to wait until the values leveled out around 2.5ppm on the analyzer before they would calibrate the analyzer. The pH values were also measured: 1) 8.0 (analyzer), >8.4 (inspector), 8.0 (crew) and 2) 8.0 (analyzer), >8.4 (inspector), and 8.12 (crew). The crew obtained secondary standards from the nurse to verify that both machines were properly calibrated. The engineering staff were not familiar with the secondary standards or how to use them. Engineering staff reported they had not verified their machine's calibration before. Secondary standards were used and verified that both machines were properly calibrated. Additional chlorine samples were taken: 1) 2.82 ppm (analyzer), 3.54 ppm (inspector); 2) 2.92ppm (analyzer), 2.92ppm (crew); and 3) 3.12ppm (analyzer), 3.15ppm (inspector) and 2.92ppm (crew). The pH was adjusted and the following measurements were obtained: 7.6 (analyzer) and 7.8 (inspector). Tanks 1,2,3,4 were filled. The following measurements were obtained at 10:30 AM from Tank 4 by the inspector: 0.72ppm, 0.77ppm, and 0.89ppm chlorine and 8.06, 7.92, and 8.01 pH. The following measurements were obtained from Tank 1 by the inspector: 3.22ppm chlorine and 8.21, 8.18, and 8.31 pH. Both tanks had potable water in them when bunkering began.
Recommendation: Continuously halogenate potable water to at least 2.0 mg/L (ppm) free residual halogen at the time of bunkering or production with an automatic halogenation device that is controlled by a flow meter and adjust the pH so it does not exceed 7.8. Ensure the amount of halogen injected during bunkering or production is controlled by a flow meter or a free halogen analyzer.
Item No.: 08
Site: Potable Water-Bunkering
Violation: The cap to the portside bunkering connection was disconnected from the chain and was laying directly on the deck, partly submerged in soiled, non-potable water, during the active bunkering process. Water was collecting below the connection point due to the construction of the ship and a leak. The length of the chain would allow the cap to sit in the water when connected if the water level from the leak continued to rise. Crew shortened the chain and connected the cap.
Recommendation: Ensure the potable water filling line has a screw cap fastened by a noncorroding cable or chain to an adjacent bulkhead or surface in such a manner that the cap cannot touch the deck when hanging free.
Item No.: 28
Site: Other-Potable Water Tank 1 Room
Violation: A box of single use plastic cups were stored directly on the sloped bulkhead of the ship below the fire water line and a hot water line. The bulkhead was soiled. This box of cups was moved. Another box of single use paper hot cups were stored in the same area on the sloped bulkhead in a higher up area. The room was a soiled technical area and not intended for storage of single use food service items.
Recommendation: Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination; (3) at least 150 millimeters (6 inches) above the deck.
Item No.: 08
Site: Potable Water-Deck 4 Aft Public Restroom
Violation: There was no visible 'blue' or 'blue/green/blue' striping for the potable water lines running to the sink.
Recommendation: Stripe or paint potable water lines either in accordance with ISO 14726 (blue/green/blue) or blue only. Ensure no other lines have the above color designations. Stripe or paint these lines at 5 meters (15 feet) intervals and on each side of partitions, decks, and bulkheads, except where decor would be marred by such markings, including potable water supply lines in technical lockers.
Item No.: *
Site: Medical-Bacterial Specimen Collection Containers
Violation: The bacterial specimen collection containers had an expiration date of 11/30/2017, the date of the inspection. The current medical staff stated the previous staff had submitted a requisition, but he did not have a copy of the requisition.
Recommendation: Ensure the medical staff maintains a supply of at least 10 clinical specimen collection containers for both viral and bacterial agents (10 for each) that are not past the expiration date.
Item No.: 02
Site: Medical-Acute Gastroenteritis (AGE) Surveillance Log
Violation: The ship was in port in Ft. Lauderdale, FL from 11/06/2017 until 11/10/2017 after repositioning with only crew on board, but no AGE log was maintained. Medical staff stated 60 to 70 crew members were onboard. A similar violation was written during the last inspection when the ship was in dry dock.
Recommendation: Maintain a daily, standardized AGE surveillance log for each cruise by the master of the vessel, the medical staff, or other designated staff. Maintain a daily, standardized AGE surveillance log when crew and/or passengers are aboard the vessel, including when the vessel is docked for extended periods.
Item No.: 01
Site: Medical-Acute Gastroenteritis (AGE) Reporting
Violation: The 24-hour AGE report submitted to VSP on 11/19/2017 stated the embarkation date and disembarkation date were 11/20/2017. The actual embarkation date was 11/10/2017.
Recommendation: Ensure the AGE report contains the following: (1) name of the vessel; (2) port of embarkation; (3) date of embarkation; (4) port of disembarkation; (5) date of disembarkation; (6) total numbers of reportable cases of AGE among passengers, including those who have disembarked because of illness-even if the number is 0 (zero reporting); (7) total numbers of reportable cases of AGE among crew members, including those who have disembarked because of illness-even if the number is 0 (zero reporting); and (8) total number of passengers and crew members on the cruise.
Item No.: 19
Site: Housekeeping-Midship Linen Locker
Violation: Five boxes of coffee, tea, and coffee condiment packets, and several sleeves of disposable coffee cups were stored on the rack above toiletry items, hand sanitizer, and cleaning equipment. The area was very organized and it was clear that great care had been put into keeping it that way, but food and single-use food equipment are not allowed to be stored with the other items.
Recommendation: Protect food from contamination by storing the food: (1) Covered or otherwise protected; (2) In a clean, dry location; and (3) Where it is not exposed to splash, dust, or other contamination. Protect food from contamination that may result from a physical, chemical, biological origin.
Item No.: 28
Site: Housekeeping-Midship Linen Locker
Violation: Five boxes of coffee, tea, and coffee condiment packets, and several sleeves of disposable coffee cups were stored on the rack above toiletry items, hand sanitizer, and cleaning equipment. The area was very organized and it was clear that great care had been put into keeping it that way, but food and single-use food equipment are not allowed to be stored with the other items.
Recommendation: Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; and (2) in a location where they are not exposed to splash, dust, or other contamination.
Item No.: 31
Site: Housekeeping-Midship Linen Locker
Violation: Five boxes of coffee, tea, and coffee condiment packets, and several sleeves of disposable coffee cups were stored on the rack above toiletry items, hand sanitizer, and cleaning equipment. The area was very organized and it was clear that great care had been put into keeping it that way, but food and single-use food equipment are not allowed to be stored with the other items.
Recommendation: Store poisonous or toxic materials used in the cleaning and maintenance of food areas in a cleaning materials locker so they cannot contaminate food, equipment, utensils, linens, and single-service and single-use articles.
Item No.: 33
Site: Housekeeping-Midship Linen Locker
Violation: There was no coving at the deck/bulkhead juncture. Food and single-use coffee cups were stored in this area.
Recommendation: Cove all bulkhead/deck, equipment/deck, cabinet/deck, and deck sink coaming/deck junctures (including galleys, pantries, buffets, bars, waiter stations, dining room work counters, provisions, food storage rooms, equipment/utensil storage rooms, and toilet rooms intended for use by galley personnel).
Item No.: 06
Site: Potable Water-Far Point Chart Records
Violation: On the chart dated 10/6/2017, the free halogen residual was above 5 ppm from 1330 to 1530. There was no notation on the chart or in the potable water system log explaining the high halogen level. On 10/14/2017, the free halogen residual was above 5 ppm from 2130 to 0300. There was no notation on the chart or in the potable water system log explaining the high halogen level. At 2400, the manual test value recorded in the log was 3.07 ppm and the chart value recorded in the log was 4.07 ppm. The same violation was written on the previous inspection.
Recommendation: Ensure records from the halogen analyzer-chart recorder verifies the free residual halogen of between 0.2 mg/L (ppm) and 5.0 mg/L (ppm) in the water distribution system for at least 16 hours in each 24 hour period since the last inspection of the vessel. Maintain the halogen analyzer-chart recorder properly and operate it in accordance with the manufacturer's instructions. Conduct a manual comparison test daily to verify calibration. Calibrate whenever the manual test value is greater than 0.2 ppm higher or lower than the analyzer reading.
Item No.: 08
Site: Potable Water-Tank Coating Records
Violation: On 11/7/2017, potable water tanks 1 and 2 received touch-up to the paint coating. The temperature of tank and the time the coating was allowed to dry was not recorded. According to the officer in charge, the drying time according to the manufacturer's specification minimum overcoat graph was 18 hours.
Recommendation: Follow all manufacturers' recommendations for application, drying, and curing. For the tank coatings used, maintain the following onboard: (1) written documentation of approval from the certification organization (independent of the coating manufacturer); (2) manufacturers' recommendations for application, drying, and curing; and (3) written documentation that the manufacturers' recommendations have been followed for application, drying, and curing.
Item No.: 41
Site: Other-Bridge Toilet Room
Violation: The toilet room for the bridge officers did not have a sanitary method to dry hands. Cloth towels and tissues were the only available options. This was corrected.
Recommendation: Provide the passenger and crew public toilets with a handwashing station that includes: (3) A method to dry hands; Ensure the method to dry hands is sanitary.
Item No.: 16
Site: Galley-Walk-in Freezer
Violation: A tray of apple pies in the freezer did not have an associated discard date. A review of the cooling logs indicated that the last time apple pies were cooked was on 11/22/2017. It was not clear if these were the same pies, and there was no record of how long the pies were in cold storage before being placed in the freezer.
Recommendation: Ensure refrigerated, ready-to-eat, potentially hazardous food: (1) Prepared on a vessel and held refrigerated for more than 24 hours is clearly marked at the time of preparation to indicate the date or day by which the food must be consumed (7 calendar days or fewer from the day the food is prepared). The day of preparation is counted as day 1. Ensure refrigerated, ready-to-eat, potentially hazardous food is discarded if not consumed within 7 calendar days from the date of preparation or opening.
Item No.: 33
Site: Galley-
Violation: The deck was damaged at the juncture between the stainless steel scupper and the poured deck material to the left of the single combination oven.
Recommendation: Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, bars, and food and equipment storage areas are constructed and maintained for easy cleaning. Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
Item No.: 33
Site: Galley-
Violation: A small bronze plate on the deck labeled 'WAGER' in front of the steam kettle had a hole in the center to insert a tool, and the hole was filled with water.
Recommendation: Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, bars, and food and equipment storage areas are constructed and maintained for easy cleaning. Ensure surfaces subject to routine splashes, spillage, or other soiling during normal use have easily cleanable features. Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 16
Site: Galley-
Violation: A pan of chicken salad in an undercounter refrigerator was labeled with a production date of 11/29/2017 and a discard date of 12/5/2017. A review of the cooling logs indicated that while the chicken salad was prepared on 11/29/2017, the chicken for the salad was cooked on 11/27/2017. A pan of sweet potato salad in another undercounter refrigerator was labeled with a production date of 11/29/2017 and a discard date of 12/5/2017. A review of the cooling logs indicated that while the sweet potato salad was prepared on 11/29/2017, the potatoes for the salad were cooked on 11/27/2017.
Recommendation: Ensure refrigerated, ready-to-eat, potentially hazardous food: (1) Prepared on a vessel and held refrigerated for more than 24 hours is clearly marked at the time of preparation to indicate the date or day by which the food must be consumed (7 calendar days or fewer from the day the food is prepared). The day of preparation is counted as day 1. Ensure refrigerated, potentially hazardous, ready-to-eat food ingredients or a portion of a refrigerated, potentially hazardous, ready-to-eat food that is subsequently combined with additional ingredients or portions of food retains the date marking of the earliest or first-prepared ingredient.
Item No.: 26
Site: Galley-
Violation: The previously-cleaned deli slicer was soiled under the ledge in the exit path of the sliced food.
Recommendation: Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
Item No.: 33
Site: Galley-
Violation: A small bronze plate on the deck behind the ice machine had a hole in the center to insert a tool, and the hole was filled with water. The deck around the plate was damaged.
Recommendation: Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, bars, and food and equipment storage areas are constructed and maintained for easy cleaning. Ensure surfaces subject to routine splashes, spillage, or other soiling during normal use have easily cleanable features. Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 20
Site: Galley-
Violation: The foam insulation on the stainless steel top cover for the ice machine was absorbent and in poor repair.
Recommendation: Materials used in the construction of multiuse utensils and food contact surfaces of equipment must be: (1) durable, corrosion resistant, and nonabsorbent; (2) sufficient in weight and thickness to withstand repeated warewashing; (3) finished to have a smooth, easily cleanable surface; and (4) resistant to pitting, chipping, crazing, scratching, scoring, distortion and decomposition.
Item No.: 33
Site: Galley-Hot Galley
Violation: The deck in the hot galley in front of the range and grills was pitted.
Recommendation: Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, bars, and food and equipment storage areas are constructed and maintained for easy cleaning. Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
Item No.: 39
Site: Dining Room-Main Dining Room
Violation: Three house flies were observed in the main dining room.
Recommendation: Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
Item No.: 39
Site: Galley-Warewash
Violation: Three flies were observed in the main galley near the warewash area.
Recommendation: Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
Item No.: 40
Site: Dining Room-Main Dining Room Aft Port Side
Violation: The most aft and port side dining area had a pest trap that was ineffectively placed on the carpet near a dining table, was soiled, and was dated 6/6/2017. The inspector talked to staff about effectively placing these traps in areas more near the waiter stations and not near the dining tables.
Recommendation: Ensure the IPM Plan includes passive surveillance procedures such as glue traps or other passive monitoring devices and the location of each. Maintain a passive device monitoring log. Inspect all food areas at a frequency that can quickly detect the evidence of pests, harborage conditions, cleanliness, and protection of outer openings. In nonfood areas, give reasonable care to conduct inspections for the presence of insects, rodents, and other pests.
Item No.: 28
Site: Dining Room-Main Dining Room
Violation: Five ice coolers were stored inverted at the waiter stations. However, they were placed at the stations the night before and are only used for dinner service. While they were at the waiter stations, breakfast was served and a mixture of clean and soiled dishes were present. The inspector talked to staff about not storing them until their actual service time.
Recommendation: Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination.
Item No.: 27
Site: Dining Room-Main Dining Room
Violation: Staff stated that the forward starboard side waiter station had been cleaned since breakfast. On the counter, six coffee pots were inverted and were said to be clean; however, three of the six were stored soiled with coffee. Staff stated that the cleaned coffee jugs are usually stored until dry, then brought to the waiter station for use. Due to the water in the coffee and water jugs and the coffee remaining in the soiled coffee jugs, the waiter station counter was soiled as well. Staff removed all items and sent them back to be washed.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 26
Site: Dining Room-Main
Violation: Staff stated that the forward starboard side waiter station had been cleaned since breakfast. On the counter, six coffee pots were inverted and were said to be clean; however, three of the six were stored soiled with coffee that poured out. Staff stated that the cleaned coffee jugs are usually stored until dry, then brought to the waiter station for use.
Recommendation: Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
Item No.: 28
Site: Dining Room-Dry Storage Area
Violation: A plastic bin had a lemon granular powder packet that had broken open and the granular substance was resting on other items in the bin and on ready-to-serve empty popcorn bags. Staff removed the bin and threw away the popcorn bags.
Recommendation: Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination.
Item No.: 26
Site: Galley-Ice Machine
Violation: The ice machine next to the warewash machine was heavily soiled with black and brown debris on the evaporator, on the ice chute, and on the plastic areas in the recirculation bath area. The machine was closed and cleaned during the inspection. Staff stated that the machine was last cleaned in May 2017.
Recommendation: Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
Item No.: 08
Site: Galley-Ice Machine
Violation: The backflow prevention device on the ice machine was heavily soiled and covered with rust.
Recommendation: Maintain backflow prevention devices in good repair.
Item No.: 22
Site: Galley-Warewash Machine
Violation: The warewash machine wash temperature gauge was out of calibration consistently by 10°F.
Recommendation: Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
Item No.: 26
Site: Galley-Ice Machine
Violation: The ice machine was heavily soiled with brown and black debris near the evaporator, the adjoining wall, and on the plastic areas near the recirculation bath. The machine was closed and cleaned.
Recommendation: Ensure food contact surfaces of equipment and utensils are clean to sight and touch.