Cruise Ship: Silver Whisper Cruise Line: Silversea Inspection Date: 12/19/2017 Inspection Score: 92
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 06
Site: Potable Water-Far Point Chart
Violation: The residual halogen readings were not manually tested at least every 4 hours during equipment failure. On 5 December from 2 am to 8 am the chart annotated a constant maximum 4.7 ppm. The operator stated that he took measurements during this time. However, only one reading of 4.57 ppm was annotated at the beginning of this 6 hour time frame.
Recommendation: In the event of equipment failure, measure the free residual halogen by a manual test kit at the halogen analyzer at least every 4 hours.
Item No.: 08
Site: Galley-Potwash Area
Violation: The backflow device on the spray hose was corroded with rust.
Recommendation: Maintain backflow prevention devices in good repair.
Item No.: 10
Site: Recreational Water Facilities-Charts
Violation: The pH levels for all recreational water facilities were recorded on the 0 to10 ppm scale on the chart instead of the 0 to14 pH scale.
Recommendation: Maintain and operate the halogen and pH analyzer-chart recorder in accordance with the manufacturer?s instructions. Conduct a manual comparison test before opening the RWF to verify calibration for free halogen residual and pH. Ensure the analyzer reading is within 0.2 ppm for free halogen and 0.2 for pH. For RWFs open longer than 24 hours, conduct a manual comparison test every 24 hours.
Item No.: 15
Site: Provisions-Dry Stores
Violation: One large can of peaches and one large can of potatoes were found to be dented during the inspection. The ship was actively provisioning this day.
Recommendation: Ensure food packages are in good condition and protect the integrity of the contents so that the food is not exposed to adulteration or potential contaminants. Ensure canned goods with dents on end or side seams are not used.
Item No.: 19
Site: Provisions-Corridor
Violation: During provisioning 8 cases of wine and beer were stored directly on the deck.
Recommendation: Protect food from contamination by storing the food: (1) Covered or otherwise protected; (2) In a clean, dry location; (3) Where it is not exposed to splash, dust, or other contamination; and (4) At least 15 centimeters (6 inches) above the deck.
Item No.: 19
Site: Provisions-Cooler
Violation: Inside the vegetable cooler condensate from the drain line was observed dripping directly onto an open box of avocadoes. Water was observed inside of and had pooled inside the box of avocadoes. The fruit in the box directly under the unit were wet as well as the fruit two boxes down under the stack. Frozen condensate was also observed on the top of a box of tilapia and squid directly under the condenser in this freezer.
Recommendation: Protect food from contamination by storing the food: (1) Covered or otherwise protected; (2) In a clean, dry location; (3) Where it is not exposed to splash, dust, or other contamination; and (4) At least 15 centimeters (6 inches) above the deck.
Item No.: 19
Site: Provisions-Corridor
Violation: During provisioning a mesh bag of onions was leaning on and in contact with the wet bulkhead.
Recommendation: Protect food from contamination by storing the food: (1) Covered or otherwise protected; (2) In a clean, dry location; (3) Where it is not exposed to splash, dust, or other contamination; and (4) At least 15 centimeters (6 inches) above the deck.
Item No.: 19
Site: Housekeeping-Office
Violation: Pillow chocolates were stored in plastic bins on the carpeted deck in this office.
Recommendation: Do not store foods: (1) In locker rooms; (2) In toilet rooms; (3) In dressing rooms; (4) In garbage rooms; or (5) In areas not finished in accordance with 7.7.4 and 7.7.5 for food storage areas.
Item No.: 22
Site: Galley-Three Compartment Sink
Violation: The wash temperature of the wash sink registered at 105°F. The soap manufacturer's recommended temperature range was listed at 120°F - 140°F. In addition, the water in the sink had an oily film and food particles floating in the water. The water was drained, cleaned, and the proper water temperature was reached during the inspection.
Recommendation: Ensure the wash, rinse, and sanitize solutions are maintained clean.
Item No.: 22
Site: Galley-Warewash Area
Violation: One auxiliary rinse spray nozzle was partially blocked with food debris. In addition, a significant amount of food debris was present in the prewash and wash compartments of the machine. This violation was noted on the last inspection.
Recommendation: Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
Item No.: 23
Site: Galley-Three Compartment Sink
Violation: The wash temperature of the wash sink registered at 105°F. The soap manufacture's recommended temperature range was listed at 120°F - 140°F. In addition, the water in the sink had an oily film and food particles floating in the water. The water was drained, cleaned, and the proper water temperature was reached during the inspection.
Recommendation: Maintain the temperature of the wash solution in manual warewashing equipment at not less than the temperature specified on the cleaning agent manufacturer?s label instructions.
Item No.: 26
Site: Buffet-La Terrazza Buffet Line
Violation: One bowl and two plates were stored soiled on the buffet line. The buffet was in service at the time of the inspection. The items were removed immediately.
Recommendation: Ensure food only contacts surfaces of equipment and utensils that are cleaned and sanitized.
Item No.: 27
Site: Galley-Hot Galley
Violation: The under shelf of the hot lamp area along the service line was soiled with brown and black food debris. It was more than a day's worth of accumulation. No food was present at the time of the inspection.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 27
Site: Buffet-La Terrazza Buffet Line
Violation: The ice machine located just behind the buffet line, had brown and black debris on the outside seam of the evaporator cover. This type of machine does not have a recirculating bath, so no food surface was impacted.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 28
Site: Buffet-La Terrazza Buffet Line
Violation: On the buffet line, in front of the coffee station, four stacks of coffee saucers were stored inverted and in between the sneeze guard shields exposing them to passengers walking by.
Recommendation: Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination; (3) at least 150 millimeters (6 inches) above the deck.
Item No.: 33
Site: Bar-Pool
Violation: The technical areas for the under counter refrigerator was noticeably soiled and wet. One contained food debris, and a metal hose that was disconnected from piping that was tied in a knot around adjacent piping.
Recommendation: Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 33
Site: Galley-Potwash Area
Violation: There was an excessive amount of grout receding around the entire area. Especially, where the deck met the bulkhead.
Recommendation: Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
Item No.: 33
Site: Galley-Pastry
Violation: Many areas of the deck in and around the pastry preparation area had recessed grout.
Recommendation: Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
Item No.: 33
Site: Galley-La Terrazza
Violation: Several areas near the dishwash station had recessed grout in where the deck met the bulkhead.
Recommendation: Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 33
Site: Galley-Warewash Area
Violation: The bulkhead in back of the designated dry area for utensils was heavily soiled with water, some food debris and rust. In addition, the deck had recessed grout and food debris throughout this storage area. Lastly, the deckhead had excess condensation, but was not dripping at the time of the inspection.
Recommendation: Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 37
Site: Provisions-Corridor
Violation: During provisioning the bulkhead and deckhead contained a significant amount of condensation.
Recommendation: Ensure exhaust ventilation hood systems in food preparation and warewashing areas--including components such as hoods, fans, guards, and ducting--are designed to prevent grease or condensation from draining or dripping onto food, equipment, utensils, linens, and single-service and single-use articles.
Item No.: 37
Site: Provisions-Vegetable Cooler
Violation: Condensate from the drain line was observed dripping directly onto an open box of avocadoes. The ship was provisioning and the door was properly closed when the inspector first entered the area.
Recommendation: Ensure exhaust ventilation hood systems in food preparation and warewashing areas--including components such as hoods, fans, guards, and ducting--are designed to prevent grease or condensation from draining or dripping onto food, equipment, utensils, linens, and single-service and single-use articles.
Item No.: 39
Site: Bar-Pool
Violation: One house fly was observed on the stand for the blender. This was an outside bar that was open while in the port.
Recommendation: Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
Item No.: 39
Site: Galley-Pastry
Violation: One housefly was observed.
Recommendation: Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
Item No.: 39
Site: Buffet-La Terrazza Buffet Line
Violation: Three fruit flies and one house fly was observed while inspecting the buffet area.
Recommendation: Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
Item No.: 39
Site: Galley-Hot Galley
Violation: Two flies were observed.
Recommendation: Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
*Inspections scores of 85 or lower are NOT satisfactory