Item No.:
08
|
|
Site:
Potable Water-Deck 4 Hose Locker Forward Portside
|
|
Violation:
Four new hoses that were stored in the hose locker were not labeled 'Potable Water Only.'
|
|
Recommendation:
Label potable water hoses with the words ?POTABLE WATER ONLY? in letters at least 13 millimeters (0.5 inch) high at each connecting end.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Reverse Osmosis Unit
|
|
Violation:
The air gap for the reduced pressure principle backflow prevention assembly to drain catch was insufficient and not twice the diameter of the pipe. The diameter of the supply pipe was two inches, and the air gap was two inches.
|
|
Recommendation:
Ensure air gaps are at least twice the diameter of the delivery fixture opening and a minimum of 25 millimeters (1 inch).
|
|
|
Item No.:
08
|
|
Site:
Galley-Deck 14
|
|
Violation:
The backflow prevention device next to cold room 14636 was continuously leaking water. This was replaced before the end of the inspection.
|
|
Recommendation:
Maintain backflow prevention devices in good repair.
|
|
|
Item No.:
08
|
|
Site:
Galley-Deck 5
|
|
Violation:
The backflow prevention device was continuously leaking water.
|
|
Recommendation:
Maintain backflow prevention devices in good repair.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-
|
|
Violation:
The bather load numbers were not visible on safety signs at multiple pool locations: Terrace Pool starboard side sign, Oasis Pool sign between the two entrances, and Calypso Pool portside sign.
|
|
Recommendation:
Provide safety signs for all RWFs, except for baby-only water facilities. Ensure the signs, at a minimum, include the following words: (1) do not use these facilities if you are experiencing diarrhea, vomiting, or fever; (2) no children in diapers or who are not toilet trained; (3) shower before entering the facility; and (4) bather load #.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Deck 16 Lotus Spa Pool
|
|
Violation:
The water fill level was between a half inch to two inches below the skim gutter level across the entire pool. The pool was in operation and multiple passengers entered the pool during the inspection.
|
|
Recommendation:
For RWFs with skim gutters, ensure that the fill level of the RWF is to the level of the skim gutters.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Maintenance Records
|
|
Violation:
The whirlpool spa and spa pool maintenance records documented filter and hair and lint strainer inspections more than a week apart. Inspections occurred on 5, 14, 20, and 30 April 2023.
|
|
Recommendation:
Inspect cartridge or canister-type filters weekly for whirlpool spas and spa pools. Clean, rinse, and disinfect the hair and lint strainer and hair and lint strainer housing on all RWFs weekly.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Deck 14 Terrace Pool
|
|
Violation:
The water fill level across two-thirds of the pool did not reach the skim gutter level. There was a visible sheen and stagnant debris floating on the water.
|
|
Recommendation:
For RWFs with skim gutters, ensure that the fill level of the RWF is to the level of the skim gutters.
|
|
|
Item No.:
11
|
|
Site:
Medical-Acute Gastroenteritis (AGE) Surveillance Log
|
|
Violation:
A food-handler was working while symptomatic. The food-handler became symptomatic with AGE symptoms on 17 June 2023 at 2230 but did not report to medical until 18 June 2023 at 0135. Disciplinary action and a food assessment with appropriate corrective actions were documented.
|
|
Recommendation:
When food employees meet the case definition for AGE, ensure the following actions are taken: (1) isolate in cabin or designated restricted area until symptom-free for a minimum of 48 hours. Exclude food employees suspected of, diagnosed with, or exposed to any communicable disease caused by Salmonella typhi, Shigella spp., E. coli O157:H7, hepatitis A virus, norovirus, or other communicable diseases that can be transmitted by food, from working in any food or food related areas or operations, including working with exposed food, warewashing, equipment, utensils, table linens, single-service articles and single-use articles. Do not allow the excluded individual to return to the above duties until they are symptom free for a minimum of 48 hours.
|
|
|
Item No.:
20
|
|
Site:
Galley-Deck 5 Bakery
|
|
Violation:
The stacked oven in the bakery had slotted fasteners on the top oven left side, a missing one on the top oven right side; the second from the bottom had two slotted fasteners on the right side; and the bottom oven was missing a fastener on the right side.
|
|
Recommendation:
Ensure multiuse food-contact surfaces are: (1) Smooth; (2) Free of breaks, open seams greater than 0.8 mm (1/32 inch), cracks, chips, inclusions, pits, and similar imperfections; (3) Free of sharp internal angles, corners, and crevices; (4) Finished to have smooth welds and joints; and (5) Accessible for cleaning and inspection by one of the following methods without being disassembled, by disassembling without the use of tools, or by easy disassembling with the use of handheld tools commonly available to maintenance and cleaning personnel. Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
|
|
|
Item No.:
21
|
|
Site:
Provisions-Deck 4 Food and Beverage Manager's Office
|
|
Violation:
Three pallets of bottled water received four days ago were still stored on wooden pallets.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning are constructed of a corrosion-resistant, nonabsorbent, and smooth material.
|
|
|
Item No.:
21
|
|
Site:
Bar-Deck 15 Calypso
|
|
Violation:
The front bar's profile strip at the countertop/bulkhead juncture was not properly adhered to the countertop or bulkhead, which created a seam and difficult to clean surface. Additionally, the sealant was rough or missing on the passenger side of the bar creating a difficult to clean surface.
|
|
Recommendation:
Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance. Ensure nonfood contact equipment is maintained in good repair and proper adjustment including: (1) Equipment maintained in a state of repair and condition that meets the materials, design, construction, and operation specifications of these guidelines.
|
|
|
Item No.:
22
|
|
Site:
Galley-Deck 15 World Fresh Marketplace
|
|
Violation:
The mid ship dishwash's final sanitizing rinse did not have an adequate spray pattern. The upper spray nozzles had a single stream of water.
|
|
Recommendation:
Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
|
|
|
Item No.:
26
|
|
Site:
Buffet-Deck 15 World Fresh Marketplace Beverage Station Portside
|
|
Violation:
The juice dispenser had more than a day?s worth of food debris in the food splash zone above the dispenser nozzles.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
26
|
|
Site:
Bar-Deck 7 Wheelhouse
|
|
Violation:
The previously cleaned coffee machine had food debris on the group head.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
26
|
|
Site:
Galley-Deck 11 Bell Box
|
|
Violation:
The juice dispenser had more than a day?s worth of food debris in the food splash zone above the dispenser nozzles.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
26
|
|
Site:
Galley-Deck 15 Slice Pizza
|
|
Violation:
The ice machine in the dishwash area had black debris on the bin's thermostat.
|
|
Recommendation:
Ensure food only contacts surfaces of equipment and utensils that are cleaned and sanitized. Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
27
|
|
Site:
Galley-Deck 15 Salty Dog Fry Station
|
|
Violation:
The previously cleaned exhaust hood overhang had grease in it.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
27
|
|
Site:
Bar-Deck 15 Calypso
|
|
Violation:
The starboard side waiter station had more than a day?s worth of debris along the countertop/bulkhead juncture. This was cleaned immediately.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
29
|
|
Site:
Galley-Deck 15 Planks BBQ
|
|
Violation:
The handwashing sink's water temperature registered 125°F. The temperature could not be adjusted by the user.
|
|
Recommendation:
Ensure handwashing sinks are equipped to provide water at a temperature of at least 38°C (100°F) through a mixing valve or combination faucet. For handwash sinks with electronic sensors, and other types of handwash sinks where the user cannot make temperature adjustments, ensure the temperature provided to the user after the mixing valve does not exceed 49°C (120°F).
|
|
|
Item No.:
33
|
|
Site:
Bar-Deck 15 Calypso
|
|
Violation:
The technical space next to refrigerator 3 had a clogged drain which caused water to back up and pool on the deck of the technical compartment.
|
|
Recommendation:
Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
|
|
|
Item No.:
33
|
|
Site:
Buffet-Deck 15 World Fresh Marketplace
|
|
Violation:
There were multiple light fixtures that where not affixed to the deckhead making it difficult to clean and exposing an open gap into the plenum.
|
|
Recommendation:
Ensure light fixtures, vent covers, and similar equipment attached to the bulkheads or deckheads are easily cleanable. Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
|
|
|
Item No.:
33
|
|
Site:
Provisions-Deck 4 Vegetable Freezer
|
|
Violation:
The deckhead and bulkhead had an excessive amount of frozen condensate throughout the freezer. No food or storage containers were impacted.
|
|
Recommendation:
Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
|
|
|
Item No.:
33
|
|
Site:
Buffet-Deck 5 Staff Mess
|
|
Violation:
There were multiple light fixtures that were not affixed to the deckhead making it difficult to clean and exposing an open gap into the plenum.
|
|
Recommendation:
Ensure light fixtures, vent covers, and similar equipment attached to the bulkheads or deckheads are easily cleanable. Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
|
|
|
Item No.:
36
|
|
Site:
Galley-Deck 15 Planks BBQ
|
|
Violation:
The light intensity did not reach 110 lux in the area around the combination oven next to the omelet station.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
39
|
|
Site:
Galley-Deck 15 Salty Dog
|
|
Violation:
There was a small, live fly in the area.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
39
|
|
Site:
Galley-Deck 7 Crown Grill
|
|
Violation:
There was a fly in the area.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
39
|
|
Site:
Bar-Deck 7 Explorers
|
|
Violation:
There was a fly in the area.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
39
|
|
Site:
Bar-Deck 5 International Cafe
|
|
Violation:
A tiny, live fly was in the area.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
39
|
|
Site:
Galley-Deck 5 Wine Pantry
|
|
Violation:
A fly was in the area.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
39
|
|
Site:
Galley-Deck 5 Pastry
|
|
Violation:
There were six tiny flies inside the cleaning locker.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
43
|
|
Site:
Ventilation-Deck 10
|
|
Violation:
Ventilation unit AC-08.3.03 had over two inches of water in the condensation collection pan which was not draining and had visible debris on the filters and within the filter compartment.
|
|
Recommendation:
Ensure condensation collection pans are self-draining. Keep air handling units clean.
|
|