Item No.:
44
|
|
Site:
Potable Water-Test Kit
|
|
Violation:
The onboard water test kit used to sample potable water and recreational water facilities continuously measured halogen and pH values greater than 0.2 ppm chlorine and 0.2 pH when compared to the respected analyzers. This was observed at the Deck 2 Lower Far Point analyzer, Deck 7 Upper Far Point analyzer, Aft and Forward Starboard Whirlpool Spa analyzers, and the Aft Pool analyzer.
|
|
Recommendation:
Ensure the supervisor or person in charge of potable water operations on the vessel demonstrates to VSP?during inspections and on request-knowledge of potable water operations, is able to demonstrate this knowledge by compliance with Section 5 of the VSP 2018 Operations Manual or by responding correctly to the inspector?s questions as they relate to the specific operation, and properly trains employees to comply with Section 5 of the VSP 2018 Operations Manual as it relates to their assigned duties. Ensure the supervisor or person in charge of recreational water operations on the vessel demonstrates to VSP?during inspections and on request ? knowledge of recreational water operations, is able to demonstrate this knowledge by compliance with Section 6 of the VSP 2018 Operations Manual or by responding correctly to the inspector?s questions as they relate to the specific operation, and properly trains employees to comply with Section 6 of the VSP 2018 Operations Manual as it relates to their assigned duties.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Engine Room - Forward Diesel Generator Room
|
|
Violation:
The distillate water line from aft evaporator #2 was striped both blue/brown/blue and blue 'potable water' before the reduced pressure principle assembly. Staff explained this line is for technical water only.
|
|
Recommendation:
Stripe or paint potable water lines either in accordance with ISO 14726 (blue/green/blue) or blue only. Stripe or paint distillate and permeate lines directed to the potable water system in accordance with ISO 14726 (blue/gray/blue). Ensure no other lines have the above color designations. Stripe or paint these lines at 5 meters (15 feet) intervals and on each side of partitions, decks, and bulkheads, except where decor would be marred by such markings, including potable water supply lines in technical lockers. Do not stripe or paint potable water lines after reduced pressure assemblies as potable water. Identify all refrigerant brine lines and nonpotable chilled water lines in all food areas, such as on ice machines, ice cream machines, etc., with either ISO 14726 (blue/white/blue) or by another uniquely identifiable method to prevent cross-connections.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Garbage Room
|
|
Violation:
Two atmospheric vacuum breakers and three vented double check valve assemblies were installed on the potable water lines to the biodigesters, however, these were not on the cross-connection control log. This was written on the March 2023 inspection report.
|
|
Recommendation:
Ensure the cross-connection control program includes at a minimum: a complete listing of cross-connections and the backflow prevention method or device for each, so there is a match to the plumbing system component and location. Include air gaps on the listing. Ensure a schedule for inspection frequency is set. Maintain a log documenting the inspection and maintenance in written or electronic form, and ensure it is available for review during inspections.
|
|
|
Item No.:
05
|
|
Site:
Potable Water-Deck 2 - Lower Far Point
|
|
Violation:
The manual test kit measured greater than 0.2 ppm compared to the analyzer. The analyzer indicated 1.39 - 1.41 ppm. The inspector measured 1.77 and 1.72 ppm.
|
|
Recommendation:
Ensure the free residual halogen measured by the halogen analyzer is within 0.2 mg/L (ppm) of the free residual halogen measured by the manual test.
|
|
|
Item No.:
05
|
|
Site:
Potable Water-Deck 7 - Upper Far Point
|
|
Violation:
The manual test kit measured greater than 0.2 ppm compared to the analyzer. The analyzer indicated 1.18 - 1.19 ppm. The inspector measured 1.72 and 1.81 ppm. The crew measured 0.77, 1.42, and 1.43 ppm.
|
|
Recommendation:
Ensure the free residual halogen measured by the halogen analyzer is within 0.2 mg/L (ppm) of the free residual halogen measured by the manual test.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Aft and Forward Starboard Whirlpool Spa Analyzers
|
|
Violation:
Manual pH comparison tests of the aft starboard whirlpool spa analyzer measured a difference greater than 0.2 ppm. The analyzer indicated pH 6.89. Manual pH comparison test to the analyzer by the inspector measured less than 6.5. Manual pH comparison test by the crew measured greater than 8.1.
Manual chlorine comparison tests of the forward starboard whirlpool spa analyzer measured greater than 0.2 ppm. The analyzer indicated 4.31 ppm chlorine. Manual chlorine comparison test to the analyzer by the inspector twice measured greater than 10.0 ppm. Manual chlorine comparison test by the crew measured 5.25, 5.6, 5.23, and 5.21 ppm.
|
|
Recommendation:
Ensure a test kit is available for testing water quality parameters, including free and total halogen levels (chlorine and bromine, where applicable), pH, and total alkalinity. Ensure that test kits are accurate to within 0.2 mg/L (ppm) for halogen and have a testing range of free residual halogen normally maintained in the RWF. Ensure test kits for pH are accurate to within 0.2. Ensure all reagents are not past their expiration dates.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Aft Pool Analyzer
|
|
Violation:
Manual chlorine comparison tests of the analyzer measured greater than 0.2 ppm. The analyzer indicated 2.6 ppm chlorine. Manual chlorine comparison test to the analyzer by the inspector measured 8.74 ppm. Manual chlorine comparison test by the crew measured 3.23 ppm.
Manual pH comparison tests of the analyzer measured greater than 0.2. The analyzer indicated pH 7.36. Manual pH comparison test to the analyzer by the inspector measured pH 7.74. Manual pH comparison test by the crew measured pH 7.8, 7.6, and 7.6.
|
|
Recommendation:
Ensure a test kit is available for testing water quality parameters, including free and total halogen levels (chlorine and bromine, where applicable), pH, and total alkalinity. Ensure that test kits are accurate to within 0.2 mg/L (ppm) for halogen and have a testing range of free residual halogen normally maintained in the RWF. Ensure test kits for pH are accurate to within 0.2. Ensure all reagents are not past their expiration dates.
|
|
|
Item No.:
33
|
|
Site:
Food Service General-Decks and Deckheads
|
|
Violation:
The deck tiles and grout were in disrepair in the following areas: (1) deck 11 - Surf & Turf; (2) deck 9 - bar pantries, Islands Galley and dishwashing area; (3) decks 4 and 5 - main galleys, and (4) deck 2 - crew galley.
Water dripped from the deckhead in the vegetable refrigerator. Additionally, ice accumulated on the deckhead in the following areas: (1) butcher walk-in refrigerator; (2) fish freezer around the fire sprinkler; and (3) frozen vegetables refrigerator. No food was impacted.
|
|
Recommendation:
Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary. Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
|
|
|
Item No.:
39
|
|
Site:
Buffet-Deck 9 - Islands Buffet Starboard Side Beverage Station
|
|
Violation:
Two flies were inside the technical space under the beer dispensers.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
39
|
|
Site:
Buffet-Deck 9 - Islands Buffet Portside Deli Station
|
|
Violation:
A small fly was in the area.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
36
|
|
Site:
Buffet-Deck 9 - Islands Buffet Carving Station
|
|
Violation:
The protective coating was missing on the far-left heat lamp bulb.
|
|
Recommendation:
Ensure light bulbs are shielded, coated, or otherwise shatter-resistant in areas where there is exposed food, clean equipment, utensils, and linens, or unwrapped single-service and single-use articles.
|
|
|
Item No.:
29
|
|
Site:
Buffet-Deck 9 - Islands Buffet Starboard Side Hot Line
|
|
Violation:
When the inspector was in the area, the handwashing station was not functioning. The crew stated the workers will either use the handwashing station on the portside hot line, omelet station, or in the galley behind a closed door. The inspector and crew discussed that using the handwashing station behind the closed door is not acceptable and that the crew should be directed to use the other two handwashing stations. The handwashing station was fixed before the end of the inspection.
|
|
Recommendation:
Ensure a handwashing facility is within 8 meters (26 feet) of all parts of the area and is not located in an adjacent area that requires passage through a closed door where the user makes hand contact with the door. Ensure handwash sinks are at least 750 millimeters (30 inches) above the deck so that employees do not have to reach excessively to wash their hands.
|
|
|
Item No.:
21
|
|
Site:
Other-Deck 9 - Spa Beverage Station
|
|
Violation:
The sealant at the countertop/bulkhead juncture was in disrepair which created seams along the edge. This was corrected immediately.
|
|
Recommendation:
Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
39
|
|
Site:
Galley-Deck 5 - Gallery 47 Room Service
|
|
Violation:
A small fly was near the coffee station.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
27
|
|
Site:
Galley-Deck 5 - Italian Galley
|
|
Violation:
A small amount of grease residue was on the previously cleaned exhaust hood overhang for the hot plate cooking area. This was re-cleaned immediately.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
21
|
|
Site:
Galley-Deck 4 - Sauce Station
|
|
Violation:
The technical space cover behind the grooved grill was in disrepair which created a difficult to clean area.
|
|
Recommendation:
Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
39
|
|
Site:
Bar-Deck 4 - Live Room
|
|
Violation:
A small fly was around the handwashing station in the corner.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
36
|
|
Site:
Provisions-Deck 1 - Breakfast Thawing
|
|
Violation:
The light intensity measured less than 110 lux in the corner opposite the condenser.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
19
|
|
Site:
Bar-Deck 6 - The Coffee Port
|
|
Violation:
The dipper well was not protected from possible contamination from passengers who could stand less than one meter away.
|
|
Recommendation:
Protect food on display from contamination by the use of packaging; counter, service line, or salad bar food guards; display cases; self-closing hinged lids; or other effective means. Install side protection for sneeze guards if the distance between exposed food and where consumers are expected to stand is less than 1 meter (40 inches). During pauses in food preparation or dispensing, ensure food preparation and dispensing utensils are stored: In running water of sufficient velocity to flush particulates to the drain (if used with moist food such as ice cream or mashed potatoes).
|
|
|
Item No.:
39
|
|
Site:
Preparation Room-Deck 1
|
|
Violation:
A small fly was around the potato peeler.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|