Item No.:
07
|
|
Site:
Potable Water-Engine Room
|
|
Violation:
The line connected to the technical water tank branched off the main line to the potable water tanks after chemical injection. When permeate water was produced for the technical water tanks, it would not have chemistry control, and there was no protection between this line and the potable water tanks other than valves. (There was backflow protection between the technical water tank and the potable water line, but this did not protect against all the permeate in the line.) This created a potential cross connection. This was planned to be corrected in the upcoming dry dock.
|
|
Recommendation:
Ensure the potable water distribution system is maintained free of cross-connections.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Whirlpool Spa 3
|
|
Violation:
The water temperature measured at 43.1°C/109.6°F by the inspector's tip-sensitive maximum registering temperature thermometer. The inspector's thermocouple measured 108°F. The crew's thermometer measured 43.2°C. A second inspector's tip sensitive thermopen measured 109°F. The facility was open for passenger use and crew proceeded to close the facility until the temperature was in the proper range.
|
|
Recommendation:
Provide a temperature-control mechanism to prevent the temperature from exceeding 40°C (104°F) on whirlpool spas and spa pools. Measure the water temperature within the whirlpool spa or spa pool tub itself.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Children's Pool
|
|
Violation:
Both round antientrapment drain covers only had two screws, but both drain covers had holes for four screws. On one drain cover, the screws were positioned opposite one another, and the inspector could lift the side of the cover slightly. On the other drain cover, the screws were positioned next to each other, and the inspector was able to lift the drain cover higher. The facility was open for passenger use and crew began to close the facility. Corrective actions began immediately.
|
|
Recommendation:
Ensure the testing of manufactured drain covers is by a nationally or internationally recognized testing laboratory. Ensure the following information is stamped on each manufactured antientrapment drain cover: (1) certification standard and year; (2) type of drain use (single or multiple); (3) maximum flow rate (in gallons or liters per minute); (4) type of fitting (suction outlet); (5) life expectancy of cover; (6) mounting orientation (wall, floor, or both); (7) manufacturer?s name or trademark; and (8) model designation. Ensure the design of custom/shipyard constructed (field fabricated) drain covers and suction fittings is fully specified by a registered design professional in accordance with ASME A112.19.8-2007. Ensure the specifications fully address cover/grate loadings, durability, hair, finger and limb entrapment issues, cover/grate secondary layer of protection, related sump design, and features specific to the RWF. Provide a letter from the shipyard for each custom/shipyard constructed (field fabricated) drain cover fitting. At a minimum, ensure the letter specifies the shipyard, name of the vessel, specifications and dimensions of the drain cover, as well as the exact location of the RWF for which it was designed. Ensure the name of and contact information for the registered design professional and signature are on the letter. Ensure antientrapment protection equipment (covers, suction fittings, safety vacuum release system, etc.) complies with ASME A112.19.8-2007?or any successor standards?whether the equipment is manufactured or field fabricated.
|
|
|
Item No.:
13
|
|
Site:
Other-Sushi-Making Class Variance
|
|
Violation:
The vessel did not have the most recent variance approval letter for the interactive sushi-making class onboard. By the end of the inspection, staff were able to provide the inspector with the most recent approval letter.
|
|
Recommendation:
Ensure the supervisor or person in charge of food operations on the vessel monitors that: (1) Food operations are not conducted in a room used as living or sleeping quarters; (2) Persons unnecessary to the food operation are not allowed in the food preparation, food storage, or warewashing areas. (3) Employees and other persons such as delivery and maintenance persons and pesticide applicators entering the food preparation, food storage, or warewashing areas comply with the guidelines in this manual; (4) Food employees are effectively cleaning their hands; (5) Employees are observing foods as they are received to determine that they are from approved sources, delivered at the required temperatures, protected from contamination, unadulterated, and accurately presented; (6) Employees are properly cooking potentially hazardous food, being particularly careful in cooking foods known to cause severe foodborne illness and death, such as eggs and comminuted meats; (7) Employees are using proper methods to rapidly cool potentially hazardous foods that are not held hot or are not for consumption within 4 hours; (8) Consumers who order raw or partially cooked ready-to-eat foods of animal origin are informed that the food is not cooked sufficiently to ensure its safety; (9) Employees are properly sanitizing cleaned multiuse equipment and utensils before they are reused; (10) Consumers are notified that clean tableware is to be used when they return to self-service areas such as salad bars and buffets; (11) Employees are preventing cross-contamination of ready-to-eat food with bare hands by properly using suitable utensils such as deli tissue, spatulas, tongs, single-use gloves, or dispensing equipment; (12) Employees are properly trained in food safety, including food allergy awareness, as it relates to their assigned duties; (13) Food employees are informed of their responsibility to report to the supervisor or person in charge information about their health and activities as they relate to diseases that are transmissible through food.
|
|
|
Item No.:
13
|
|
Site:
Galley-Windjammer
|
|
Violation:
A container of raw fish was on the counter with a time control label of 10:30-14:30. The time control plan for the area stated time control for lunch began at 11:00.
|
|
Recommendation:
Because of the risks for foodborne illness inherent to the food operation, ensure the supervisor or person in charge of food operations on the vessel demonstrates to VSP - during inspections and on request - knowledge of foodborne disease prevention, application of the Hazard Analysis Critical Point principles, and the food-safety guidelines in this manual. Ensure that the person in charge demonstrates this knowledge: (1) By compliance with these guidelines; (2) By being a domestically or foreign certified food protection manager who has shown proficiency of required information through passing a test that is part of an accredited program; or (3) By responding correctly to the inspector's questions as they relate to the specific food operation. Ensure that the areas of knowledge include: (1) Describing the relation between prevention of foodborne disease and personal hygiene of a food employee; (2) Explaining the responsibility of the person in charge to prevent transmission of foodborne disease by a food employee who has a disease or medical condition that may cause foodborne disease; (3) Describing the symptoms associated with diseases that are transmissible through food; (4) Explaining the significance of the relation between maintaining the time and temperature of potentially hazardous food and the prevention of foodborne illness; (5) Explaining the hazards involved in the consumption of raw or undercooked meat, poultry, eggs, and fish; (6) Stating the required food temperatures and times for safe cooking of potentially hazardous food, including meat, poultry, eggs, and fish; (7) Stating the required temperatures and times for the safe refrigerated storage, hot holding, cooling, and reheating of potentially hazardous food; (8) Describing the relation between prevention of foodborne illness and management and control of the following: cross-contamination, hand contact with ready-to-eat foods, handwashing, and maintaining food operations in a clean condition and in good repair; (9) Explaining the relation between food safety and providing equipment that is sufficient in number and capacity as well as properly designed, constructed, located, installed, operated, maintained, and cleaned; (10) Explaining correct procedures for cleaning and sanitizing utensils and food-contact surfaces of equipment; (11) Identifying poisonous or toxic materials on the vessel and the procedures necessary to ensure they are safely stored, dispensed, used, and disposed of according to law; (12) Identifying critical-control points in the operation from purchasing through service that when not controlled may contribute to the transmission of foodborne illness and explaining steps taken to ensure the points are controlled in accordance with the guidelines in this manual.
|
|
|
Item No.:
13
|
|
Site:
Galley-Windjammer
|
|
Violation:
Inside time control refrigerator 10.7, a pan of choco bars (containing cream), a pan of cheese cake, and a pan of peach custard tarts had time control labels with 10:39-14:39. According to the time control plan for the area, time control for lunch began at 11:00. Staff stated items are moved from the buffet preparation area on deck 2 around 10:30 in preparation for lunch service at 11:00.
|
|
Recommendation:
Because of the risks for foodborne illness inherent to the food operation, ensure the supervisor or person in charge of food operations on the vessel demonstrates to VSP - during inspections and on request - knowledge of foodborne disease prevention, application of the Hazard Analysis Critical Point principles, and the food-safety guidelines in this manual. Ensure that the person in charge demonstrates this knowledge: (1) By compliance with these guidelines; (2) By being a domestically or foreign certified food protection manager who has shown proficiency of required information through passing a test that is part of an accredited program; or (3) By responding correctly to the inspector's questions as they relate to the specific food operation. Ensure that the areas of knowledge include: (1) Describing the relation between prevention of foodborne disease and personal hygiene of a food employee; (2) Explaining the responsibility of the person in charge to prevent transmission of foodborne disease by a food employee who has a disease or medical condition that may cause foodborne disease; (3) Describing the symptoms associated with diseases that are transmissible through food; (4) Explaining the significance of the relation between maintaining the time and temperature of potentially hazardous food and the prevention of foodborne illness; (5) Explaining the hazards involved in the consumption of raw or undercooked meat, poultry, eggs, and fish; (6) Stating the required food temperatures and times for safe cooking of potentially hazardous food, including meat, poultry, eggs, and fish; (7) Stating the required temperatures and times for the safe refrigerated storage, hot holding, cooling, and reheating of potentially hazardous food; (8) Describing the relation between prevention of foodborne illness and management and control of the following: cross-contamination, hand contact with ready-to-eat foods, handwashing, and maintaining food operations in a clean condition and in good repair; (9) Explaining the relation between food safety and providing equipment that is sufficient in number and capacity as well as properly designed, constructed, located, installed, operated, maintained, and cleaned; (10) Explaining correct procedures for cleaning and sanitizing utensils and food-contact surfaces of equipment; (11) Identifying poisonous or toxic materials on the vessel and the procedures necessary to ensure they are safely stored, dispensed, used, and disposed of according to law; (12) Identifying critical-control points in the operation from purchasing through service that when not controlled may contribute to the transmission of foodborne illness and explaining steps taken to ensure the points are controlled in accordance with the guidelines in this manual.
|
|
|
Item No.:
13
|
|
Site:
Buffet-Crew Mess Service Line
|
|
Violation:
The inspection team entered the area at 10:25. Inside the undercounter time control unit were five bowls of vegetarian curry. According to the time control plan for the crew mess, time control for the area did not start until 10:30. The inspector took a temperature of the curry, and it was above 135°F. When the inspector asked why food was in the time control unit, staff stated that as soon as food is finished cooking, it is placed in the cabinets in preparation for service.
|
|
Recommendation:
Because of the risks for foodborne illness inherent to the food operation, ensure the supervisor or person in charge of food operations on the vessel demonstrates to VSP - during inspections and on request - knowledge of foodborne disease prevention, application of the Hazard Analysis Critical Point principles, and the food-safety guidelines in this manual. Ensure that the person in charge demonstrates this knowledge: (1) By compliance with these guidelines; (2) By being a domestically or foreign certified food protection manager who has shown proficiency of required information through passing a test that is part of an accredited program; or (3) By responding correctly to the inspector's questions as they relate to the specific food operation. Ensure that the areas of knowledge include: (1) Describing the relation between prevention of foodborne disease and personal hygiene of a food employee; (2) Explaining the responsibility of the person in charge to prevent transmission of foodborne disease by a food employee who has a disease or medical condition that may cause foodborne disease; (3) Describing the symptoms associated with diseases that are transmissible through food; (4) Explaining the significance of the relation between maintaining the time and temperature of potentially hazardous food and the prevention of foodborne illness; (5) Explaining the hazards involved in the consumption of raw or undercooked meat, poultry, eggs, and fish; (6) Stating the required food temperatures and times for safe cooking of potentially hazardous food, including meat, poultry, eggs, and fish; (7) Stating the required temperatures and times for the safe refrigerated storage, hot holding, cooling, and reheating of potentially hazardous food; (8) Describing the relation between prevention of foodborne illness and management and control of the following: cross-contamination, hand contact with ready-to-eat foods, handwashing, and maintaining food operations in a clean condition and in good repair; (9) Explaining the relation between food safety and providing equipment that is sufficient in number and capacity as well as properly designed, constructed, located, installed, operated, maintained, and cleaned; (10) Explaining correct procedures for cleaning and sanitizing utensils and food-contact surfaces of equipment; (11) Identifying poisonous or toxic materials on the vessel and the procedures necessary to ensure they are safely stored, dispensed, used, and disposed of according to law; (12) Identifying critical-control points in the operation from purchasing through service that when not controlled may contribute to the transmission of foodborne illness and explaining steps taken to ensure the points are controlled in accordance with the guidelines in this manual.
|
|
|
Item No.:
16
|
|
Site:
Galley-Windjammer
|
|
Violation:
A container of raw fish was on the counter with a time control label of 10:30-14:30. The time control plan for the area stated time control for lunch began at 11:00.
|
|
Recommendation:
If time only?rather than time in conjunction with temperature?is used as the public health control for a working supply of potentially hazardous food before cooking, or for ready-to-eat potentially hazardous food that is displayed or held for service for immediate consumption, ensure the food (1) Has an initial temperature of 5°C (41°F) or less or 57°C (135°F) or greater before placement on time control. (2) Is not be placed on temperature control again. (3) Is marked, or otherwise identified, to indicate the time 4 hours past the point in time when the food is removed from temperature control (if the time between service set-up and closing is greater than 4 hours). (4) Is labeled with a 4-hour discard time if containers of potentially hazardous foods on time control are placed on preparation counters, even if the outlet is open less than 4 hours. (5) Is discarded within 4 hours of placement on time control. and (6) Is labeled with a 4-hour discard time if time control unit (bain marie, cold basin) meant to be cold holding or hot holding and not operational or used as intended, as the unit is now considered a counter.
|
|
|
Item No.:
16
|
|
Site:
Buffet-Crew Mess Service Line
|
|
Violation:
The inspection team entered the area at 10:25. Inside the undercounter time control unit were five bowls of vegetarian curry. According to the time control plan for the crew mess, time control for the area did not start until 10:30. The inspector took a temperature of the curry, and it was above 135°F. When the inspector asked why food was in the time control unit, staff stated that as soon as food is finished cooking, it is placed in the cabinets in preparation for service.
|
|
Recommendation:
If time only?rather than time in conjunction with temperature?is used as the public health control for a working supply of potentially hazardous food before cooking, or for ready-to-eat potentially hazardous food that is displayed or held for service for immediate consumption, ensure the food (1) Has an initial temperature of 5°C (41°F) or less or 57°C (135°F) or greater before placement on time control. (2) Is not be placed on temperature control again. (3) Is marked, or otherwise identified, to indicate the time 4 hours past the point in time when the food is removed from temperature control (if the time between service set-up and closing is greater than 4 hours). (4) Is labeled with a 4-hour discard time if containers of potentially hazardous foods on time control are placed on preparation counters, even if the outlet is open less than 4 hours. (5) Is discarded within 4 hours of placement on time control. and (6) Is labeled with a 4-hour discard time if time control unit (bain marie, cold basin) meant to be cold holding or hot holding and not operational or used as intended, as the unit is now considered a counter.
|
|
|
Item No.:
16
|
|
Site:
Buffet-Windjammer Fruit Station
|
|
Violation:
A carafe of milk was on the rolling trolley located behind the curtain near the fruit station. The milk was on time control, but did not have a time control label. The milk was labeled.
|
|
Recommendation:
If time only?rather than time in conjunction with temperature?is used as the public health control for a working supply of potentially hazardous food before cooking, or for ready-to-eat potentially hazardous food that is displayed or held for service for immediate consumption, ensure the food (1) Has an initial temperature of 5°C (41°F) or less or 57°C (135°F) or greater before placement on time control. (2) Is not be placed on temperature control again. (3) Is marked, or otherwise identified, to indicate the time 4 hours past the point in time when the food is removed from temperature control (if the time between service set-up and closing is greater than 4 hours). (4) Is labeled with a 4-hour discard time if containers of potentially hazardous foods on time control are placed on preparation counters, even if the outlet is open less than 4 hours. (5) Is discarded within 4 hours of placement on time control. and (6) Is labeled with a 4-hour discard time if time control unit (bain marie, cold basin) meant to be cold holding or hot holding and not operational or used as intended, as the unit is now considered a counter.
|
|
|
Item No.:
16
|
|
Site:
Galley-Windjammer
|
|
Violation:
Inside time control refrigerator 10.7, a pan of choco bars (containing cream), a pan of cheese cake, and a pan of peach custard tarts had time control labels with 10:39-14:39. According to the time control plan for the area, time control for lunch began at 11:00. Staff stated items are moved from the buffet preparation area on deck 2 around 10:30 in preparation for lunch service at 11:00.
|
|
Recommendation:
If time only?rather than time in conjunction with temperature?is used as the public health control for a working supply of potentially hazardous food before cooking, or for ready-to-eat potentially hazardous food that is displayed or held for service for immediate consumption, ensure the food (1) Has an initial temperature of 5°C (41°F) or less or 57°C (135°F) or greater before placement on time control. (2) Is not be placed on temperature control again. (3) Is marked, or otherwise identified, to indicate the time 4 hours past the point in time when the food is removed from temperature control (if the time between service set-up and closing is greater than 4 hours). (4) Is labeled with a 4-hour discard time if containers of potentially hazardous foods on time control are placed on preparation counters, even if the outlet is open less than 4 hours. (5) Is discarded within 4 hours of placement on time control. and (6) Is labeled with a 4-hour discard time if time control unit (bain marie, cold basin) meant to be cold holding or hot holding and not operational or used as intended, as the unit is now considered a counter.
|
|
|
Item No.:
17
|
|
Site:
Galley-Windjammer
|
|
Violation:
Inside time control refrigerator 10.7, a pan of choco bars (containing cream), a pan of cheese cake, and a pan of peach custard tarts had time control labels with 10:39-14:39. According to the time control plan for the area, time control for lunch began at 11:00. Staff stated items are moved from the buffet preparation area on deck 2 around 10:30 in preparation for lunch service at 11:00.
|
|
Recommendation:
Maintain a written time control plan(s) that ensures compliance with these guidelines on the vessel and make it available for review during inspections. Post a time control plan at each outlet where time control is used and ensure time control plan is accessible to all crew working at each outlet where time control is used. Ensure plan(s): (1) Include set-up and discard times for each outlet. Include all services and events where potentially hazardous foods are kept on time control. If used, ensure colored labels correspond to the discard times stated in the plan. (2) List all units (to include preparation counters, cabinets, compartments, and equipment) on time control, but only cabinets and compartments on time control must be physically labeled. and (3) Describe or show the flow of potentially hazardous food from when last in temperature control to placement in time control and discard.
|
|
|
Item No.:
17
|
|
Site:
Galley-Windjammer
|
|
Violation:
Time control unit 10.7 was not physically labeled as on time control. This was corrected.
|
|
Recommendation:
Maintain a written time control plan(s) that ensures compliance with these guidelines on the vessel and make it available for review during inspections. Post a time control plan at each outlet where time control is used and ensure time control plan is accessible to all crew working at each outlet where time control is used. Ensure plan(s): (1) Include set-up and discard times for each outlet. Include all services and events where potentially hazardous foods are kept on time control. If used, ensure colored labels correspond to the discard times stated in the plan. (2) List all units (to include preparation counters, cabinets, compartments, and equipment) on time control, but only cabinets and compartments on time control must be physically labeled. and (3) Describe or show the flow of potentially hazardous food from when last in temperature control to placement in time control and discard.
|
|
|
Item No.:
17
|
|
Site:
Buffet-Crew Mess Service Line
|
|
Violation:
The inspection team entered the area at 10:25. Inside the undercounter time control unit were five bowls of vegetarian curry. According to the time control plan for the crew mess, time control for the area did not start until 10:30. The inspector took a temperature of the curry, and it was above 135°F. When the inspector asked why food was in the time control unit, staff stated that as soon as food is finished cooking, it is placed in the cabinets in preparation for service.
|
|
Recommendation:
Maintain a written time control plan(s) that ensures compliance with these guidelines on the vessel and make it available for review during inspections. Post a time control plan at each outlet where time control is used and ensure time control plan is accessible to all crew working at each outlet where time control is used. Ensure plan(s): (1) Include set-up and discard times for each outlet. Include all services and events where potentially hazardous foods are kept on time control. If used, ensure colored labels correspond to the discard times stated in the plan. (2) List all units (to include preparation counters, cabinets, compartments, and equipment) on time control, but only cabinets and compartments on time control must be physically labeled. and (3) Describe or show the flow of potentially hazardous food from when last in temperature control to placement in time control and discard.
|
|
|
Item No.:
17
|
|
Site:
Galley-Windjammer
|
|
Violation:
A container of raw fish was on the counter with a time control label of 10:30-14:30. The time control plan for the area stated time control for lunch began at 11:00.
|
|
Recommendation:
Maintain a written time control plan(s) that ensures compliance with these guidelines on the vessel and make it available for review during inspections. Post a time control plan at each outlet where time control is used and ensure time control plan is accessible to all crew working at each outlet where time control is used. Ensure plan(s): (1) Include set-up and discard times for each outlet. Include all services and events where potentially hazardous foods are kept on time control. If used, ensure colored labels correspond to the discard times stated in the plan. (2) List all units (to include preparation counters, cabinets, compartments, and equipment) on time control, but only cabinets and compartments on time control must be physically labeled. and (3) Describe or show the flow of potentially hazardous food from when last in temperature control to placement in time control and discard.
|
|
|
Item No.:
20
|
|
Site:
Galley-Deck 5 Midship Coffee Station
|
|
Violation:
The dispensing nozzle on the water dispenser was heavily corroded, making it difficult to clean.
|
|
Recommendation:
Materials used in the construction of multiuse utensils and food contact surfaces of equipment must be: (1) durable, corrosion resistant, and nonabsorbent; (2) sufficient in weight and thickness to withstand repeated warewashing; (3) finished to have a smooth, easily cleanable surface; and (4) resistant to pitting, chipping, crazing, scratching, scoring, distortion and decomposition.
|
|
|
Item No.:
20
|
|
Site:
Buffet-Windjammer Fruit Station
|
|
Violation:
The corners of three melamine bowls were chipped, making them difficult to clean.
|
|
Recommendation:
Design and construct food contact surfaces of equipment and utensils to be durable and to retain their characteristic qualities under normal use conditions.
|
|
|
Item No.:
20
|
|
Site:
Buffet-Windjammer Orange Juice Station
|
|
Violation:
The left plastic piece on the orange juice machine was cracked, making the area difficult to clean. Staff stated they would replace the plastic piece.
|
|
Recommendation:
Ensure multiuse food-contact surfaces are: (1) Smooth; (2) Free of breaks, open seams greater than 0.8 mm (1/32 inch), cracks, chips, inclusions, pits, and similar imperfections; (3) Free of sharp internal angles, corners, and crevices; (4) Finished to have smooth welds and joints; and (5) Accessible for cleaning and inspection by one of the following methods without being disassembled, by disassembling without the use of tools, or by easy disassembling with the use of handheld tools commonly available to maintenance and cleaning personnel. Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
|
|
|
Item No.:
20
|
|
Site:
Housekeeping-Deck 9 Aft
|
|
Violation:
The white coating on the plastic above the ice bin was chipped and cracked.
|
|
Recommendation:
Materials used in the construction of multiuse utensils and food contact surfaces of equipment must be: (1) durable, corrosion resistant, and nonabsorbent; (2) sufficient in weight and thickness to withstand repeated warewashing; (3) finished to have a smooth, easily cleanable surface; and (4) resistant to pitting, chipping, crazing, scratching, scoring, distortion and decomposition.
|
|
|
Item No.:
20
|
|
Site:
Other-Deck 3 Room Service Pantry
|
|
Violation:
A slotted fastener was located on the food-contact area of the pizza cutter. This was replaced.
|
|
Recommendation:
Ensure multiuse food-contact surfaces are: (1) Smooth; (2) Free of breaks, open seams greater than 0.8 mm (1/32 inch), cracks, chips, inclusions, pits, and similar imperfections; (3) Free of sharp internal angles, corners, and crevices; (4) Finished to have smooth welds and joints; and (5) Accessible for cleaning and inspection by one of the following methods without being disassembled, by disassembling without the use of tools, or by easy disassembling with the use of handheld tools commonly available to maintenance and cleaning personnel. Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
|
|
|
Item No.:
21
|
|
Site:
Other-Deck 3 Room Service Pantry
|
|
Violation:
The bottom pieces of three metal fruit baskets were missing, exposing wires that made the area difficult to clean. These baskets were discarded.
|
|
Recommendation:
Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
22
|
|
Site:
Galley-Windjammer Glasswash
|
|
Violation:
A dead fly was found on the curtain at the exit of the glasswash. The machine was running during the inspection, but no dishes were exiting the machine.
|
|
Recommendation:
Ensure warewashing machines, drainboards, and the compartments of sinks, basins, or other receptacles used for washing and rinsing equipment, utensils, or raw foods, or laundering wiping cloths are cleaned: (1) before use; (2) throughout the day at a frequency necessary to prevent recontamination and accumulation of excessive debris, and to ensure that the equipment performs its intended function; (3) at least every 24 hours (if used).
|
|
|
Item No.:
29
|
|
Site:
Galley-Windjammer
|
|
Violation:
A rolling cart with three cleaning buckets was stored in front of the handwash station located across from the clean dish storage rack. The cart was moved.
|
|
Recommendation:
Ensure handwashing facilities are used for no other purpose and are accessible at all times.
|
|
|
Item No.:
33
|
|
Site:
Buffet-Windjammer Orange Juice Station
|
|
Violation:
The ventilation cover above the juice machine was soiled with greater than one day's worth of dust. This was cleaned at the end of service.
|
|
Recommendation:
Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
|
|
|
Item No.:
33
|
|
Site:
Other-Engine Control Room
|
|
Violation:
There was no coving at the deck/bulkhead juncture below the coffee station.
|
|
Recommendation:
Cove all bulkhead/deck, equipment/deck, cabinet/deck, and deck sink coaming/deck junctures (including galleys, pantries, buffets, bars, waiter stations, dining room work counters, provisions, food storage rooms, equipment/utensil storage rooms, and toilet rooms intended for use by galley personnel).
|
|
|
Item No.:
34
|
|
Site:
Galley-Deck 5 Midship Starboard Hot Line
|
|
Violation:
The handwash sink was draining directly on the deck. This was corrected immediately.
|
|
Recommendation:
Ensure a plumbing system in a food area is maintained in good repair.
|
|
|
Item No.:
39
|
|
Site:
Buffet-Windjammer Orange Juice Station
|
|
Violation:
One fruit fly was observed in this area. The pest manager was immediately called.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
39
|
|
Site:
Other-Crew Scullery
|
|
Violation:
One fruit fly was observed in this area. The pest manager was called immediately.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
39
|
|
Site:
Other-Chops Side Stand
|
|
Violation:
One fruit fly was observed in this area. The pest manager was called.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
40
|
|
Site:
Galley-Windjammer Glasswash
|
|
Violation:
A dead fly was found on the curtain at the exit of the glasswash. The machine was running during the inspection, but no dishes were exiting the machine.
|
|
Recommendation:
Remove dead or trapped insects, rodents, and other pests from control devices and the vessel at a frequency that prevents their accumulation or decomposition or the attraction of other pests.
|
|
|