Skip directly to site content Skip directly to page options

Inspection Detail Report

  Advanced Search |  Ship Scored 100 |  Green Sheet  |  CDC Home |  VSP Home
 
Cruise Ship: Carnival Elation Cruise Line: Carnival Cruise Lines, Inc. Inspection Date: 05/07/2026 Inspection Score: 98
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 17
Site: Galley-Deck 10 Seafood
Violation: The soup kettle unit listed on the time control plan was not physically labeled.
Recommendation: Ensure a time control plan is posted and available to all crew working at each outlet where time control is used. (1) List all units (to include refrigeration and hot holding units, preparation counters, cabinets, compartments, and equipment) on time control. Cabinets and compartments on time control must be physically labeled.
Item No.: 19
Site: Galley-Deck 8 Center
Violation: A bin of sugar was labeled incorrectly with 'rice flour.' This was corrected.
Recommendation: Ensure containers holding food or food ingredients removed from their original packages for use on the vessel, such as cooking oils, flour, herbs, potato flakes, salt, spices, and sugar are identified with the common name of the food.
Item No.: 21
Site: Galley-Deck 10 Blue Iguana
Violation: The time control refrigerator unit did not fully close. No food was impacted.
Recommendation: Maintain nonfood-contact equipment in good repair and proper adjustment including: (1) Equipment must be maintained in a state of repair and condition that meets the materials, design, construction, and operation specifications of these standards; (2) Equipment components such as doors, seals, hinges, fasteners, and kick plates are kept intact and tight and adjusted in accordance with manufacturer's specifications.
Item No.: 21
Site: Food Service General-Silicone
Violation: The following areas had an accumulation of silicone buildup that was either peeling or in disrepair around equipment and nonfood-contact surfaces: -Deck 10 Breakfast Grill: The silicone around the two soup kettles was missing. Silicone was peeling from the entire deckhead paneling. -Deck 10 Omelettes: The silicone at the back bar counter ledge was hanging down and in disrepair. -Deck 10 Lido Center Galley Deep Fat Frying: A heavy amount of silicone buildup was around the piping and was detached which created a gap. Silicone was also missing from the parts of the bulkhead. -Deck 8 Main Galley: Silicone was missing around the back bulkhead by the soup kettles.
Recommendation: Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and are designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 26
Site: Pantry-Deck 10 Red Frog Pub
Violation: The ice machine's white deflector panel had pink and black debris on the food splash zone area.
Recommendation: Ensure food only contacts surfaces of cleaned and sanitized equipment and utensils. Ensure food-contact surfaces of equipment and utensils are clean to sight and touch.
Item No.: 27
Site: Galley-Deck 8 Center
Violation: All four bains-marie had an accumulation of yellow dust and other debris. Crew stated the bain maries had not been used since dinner the night before.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 27
Site: Galley-Deck 8 Center
Violation: A piece of soiled tape was covering a open seam along the hot grill.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 27
Site: Galley-Deck 10 Lido Center
Violation: The upright refrigerator's technical space was soiled with dust around the evaporator fan and the metal paneling. This was corrected before the end of inspection.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 27
Site: Galley-Deck 10 Guy's Burgers Joints
Violation: The undercounter refrigerator unit cooling coils were soiled with dust, sticky debris, and pieces of hair.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 27
Site: Galley-Deck 10 Seafood Shack
Violation: The undercounter refrigerator unit's cooling coils were soiled with dust, sticky debris and pieces of hair.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 33
Site: Galley-Deck 10 Guy's Burgers Joints
Violation: The deck grout was recessed around the undercounter refrigerators.
Recommendation: Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
Item No.: 33
Site: Galley-Deck 8 Center
Violation: The faucet was consistently leaking at the center soup kettle and pooled on the deck.
Recommendation: Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 34
Site: Galley-Deck 8 Center
Violation: The faucet was consistently leaking at the center soup kettle.
Recommendation: Ensure the plumbing system in food areas is in good repair.
Item No.: 39
Site: Food Service General-Pests
Violation: The following areas had flies and other insects: -Deck 10 Pizzeria Galley: One fly was in the area. -Deck 10 Tiffany Bar: Two flies were in the back bar area. -Deck 10 Dishwash Center Galley: One fly was near the soiled end of the flight-type dishwash machine. One six - legged insect was on the bulkhead. -Deck 10 Guys Burgers Show Galley: Two flies were near the back counter. -Deck 3 Officers Mess: One fly was near the condiment station.
Recommendation: Effectively control the presence of insects, rodents, and other pests to minimize their presence in food areas.
*Inspections scores of 85 or lower are NOT satisfactory
Vessel Sanitation Program