Item No.:
32
|
|
Site:
Galley-Deck 9- Handwashing Sink near Biodigester
|
|
Violation:
An empty carton of milk and tea bags were in the paper towel waste bin for the handwashing station, which was not constructed for food waste. The paper towel bin was emptied.
|
|
Recommendation:
Ensure receptacles and containers for refuse and recyclables and for use with materials containing food residue are durable, nonabsorbent, easily cleanable, and leakproof. Ensure receptacles and containers for refuse and recyclables and for use with materials containing food residue are insect and rodent resistant and have tight-fitting lids.
|
|
|
Item No.:
33
|
|
Site:
Galley-Deck 9- Three-compartment Sink
|
|
Violation:
Condensate collected on the deckhead and dripped into the sanitizing compartment of the three-compartment sink. No dishes were in the three-compartment sink at the time of the inspection.
|
|
Recommendation:
Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
|
|
|
Item No.:
22
|
|
Site:
Galley-Deck 9- Three-compartment Sink
|
|
Violation:
Condensate from the deckhead dripped into the sanitizing compartment of the three-compartment sink. No dishes were in the three-compartment sink at the time of the inspection, and the sanitizing compartment water was changed.
|
|
Recommendation:
Ensure the wash, rinse, and sanitize solutions are kept clean.
|
|
|
Item No.:
37
|
|
Site:
Galley-Deck 9- Three-compartment Sink
|
|
Violation:
The ventilation above the sanitizing-compartment was not working. Condensate collected on the deckhead and dripped from the exhaust vent.
|
|
Recommendation:
Ensure ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensate from collecting on bulkheads and deckheads. Ensure ventilation hood systems and devices operate effectively to prevent grease and condensate from collecting on the bulkheads and deckheads and to remove contaminants generated by equipment located under them.
|
|
|
Item No.:
27
|
|
Site:
Food Service General-Technical Compartments between the Stacked Combination Ovens
|
|
Violation:
In the following locations, the technical compartments between the stacked combination ovens were soiled with more than one day's accumulation of dust, grease, or food debris. The compartments were cleaned immediately.
- Deck 9: Lido Center Galley
- Deck 3: Center Roast Station (the left and center combination ovens)
- Deck 0: Crew Galley
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
20
|
|
Site:
Galley-Deck 9- Sushi
|
|
Violation:
Slotted fasteners were in the food-splash zone of the sushi display case. The fasteners were replaced immediately.
|
|
Recommendation:
Ensure multiuse food-contact surfaces are: (1) Smooth; (2) Free of breaks, open seams greater than 0.8 mm (1/32 inch), cracks, chips, inclusions, pits, and similar imperfections; (3) Free of sharp internal angles, corners, and crevices; (4) Finished to have smooth welds and joints; (5) Accessible for cleaning and inspection by one of the following methods: without being disassembled, by disassembling without the use of tools, or by easy disassembling with the use of handheld tools commonly available to maintenance and cleaning personnel.
Use low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
|
|
|
Item No.:
17
|
|
Site:
Room Service-Deck 6- Time Control Plan
|
|
Violation:
The countertop and cold well were physically labeled as time control units but not listed on the time control plans posted in the area. Crew stated they do not use this galley for food service. The physical labels were removed from the countertop and cold well.
|
|
Recommendation:
Maintain a written time control plan that ensures compliance with these standards on the vessel and make it available for review during inspections. Ensure a time control plan is posted and available to all crew working at each outlet where time control is used. Ensure plan(s): (1) Include set-up and discard times for each outlet. Include all services and events where TCS/PHF is kept on time control. If used, ensure colored labels correspond to the discard times stated in the plan; (2) List all units (to include refrigeration and hot holding units, preparation counters, cabinets, compartments, and equipment) on time control. Cabinets and compartments on time control must be physically labeled; (3) Describe or show the flow of TCS/PHF from when last in temperature control to placement in time control and discard.
|
|
|
Item No.:
33
|
|
Site:
Room Service-Deck 6- Deck in front of Upright Refrigerators
|
|
Violation:
The deck tile grout was in disrepair, and water surfaced between five deck tiles when stepped on in front of the upright refrigerators. The area was cleaned and the deck repaired before the end of the inspection.
|
|
Recommendation:
Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary. Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
|
|
|
Item No.:
33
|
|
Site:
Food Service General-Deck Grout
|
|
Violation:
The deck grout was recessed in the areas listed below. Staff showed the inspector a plan addressing deck grout throughout the vessel.
- Deck 3 Main Galley: Buffet Pantry
- Deck 3 Main Galley: Pastry
- Deck 0 Crew Galley: In front of Walk-in Freezer
|
|
Recommendation:
Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
|
|
|
Item No.:
34
|
|
Site:
Galley-Deck 3- Hot Galley Service Line 1
|
|
Violation:
Water continuously dripped from a pipe located in the technical compartment. The leak was fixed immediately.
|
|
Recommendation:
Ensure the plumbing system in food areas is in good repair.
|
|
|
Item No.:
20
|
|
Site:
Galley-Deck 3- Pastry
|
|
Violation:
Slotted fasteners were in the food-splash zone on the arm of the counter-mounted mixer. The fasteners were replaced before the end of the inspection.
|
|
Recommendation:
Ensure multiuse food-contact surfaces are: (1) Smooth; (2) Free of breaks, open seams greater than 0.8 mm (1/32 inch), cracks, chips, inclusions, pits, and similar imperfections; (3) Free of sharp internal angles, corners, and crevices; (4) Finished to have smooth welds and joints; (5) Accessible for cleaning and inspection by one of the following methods: without being disassembled, by disassembling without the use of tools, or by easy disassembling with the use of handheld tools commonly available to maintenance and cleaning personnel.
Use low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
|
|
|
Item No.:
39
|
|
Site:
Preparation Room-Deck 0
|
|
Violation:
Three live phorid flies were around the door to the walk-in cooler, and one was near the biodigester.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in food areas.
|
|
|
Item No.:
40
|
|
Site:
Preparation Room-Deck 0
|
|
Violation:
Approximately 15 dead phorid flies were around the right front leg of the biodigester. The pest control manager said treatment had been applied that morning.
|
|
Recommendation:
Remove dead or trapped insects, rodents, and other pests from control devices and the vessel at a frequency that prevents their accumulation or decomposition or the attraction of other pests.
|
|
|
Item No.:
33
|
|
Site:
Buffet-Deck 0- Captain's Dining Room
|
|
Violation:
Carpet was installed under part of the buffet line, making the area difficult to clean.
|
|
Recommendation:
Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, bars, and food and equipment storage areas are constructed and maintained for easy cleaning. Do not use carpet in these areas.
|
|
|
Item No.:
11
|
|
Site:
Recreational Water Facilities-Deck 14 - Serenity Portside Whirlpool Shower
|
|
Violation:
A food employee continued to work after experiencing AGE symptoms. The food employee experienced onset of AGE symptoms on 13 August 2026 at 0825, worked until 0905, and reported to medical at 0910. The employee was retrained on AGE reporting requirements and a risk assessment was completed.
|
|
Recommendation:
When food employees are symptomatic and meet the case definition for AGE, ensure the following actions are taken: (1) Isolate in cabin or designated restricted area until symptom-free for a minimum of 48 hours; (2) Follow-up with and receive approval by designated medical personnel before returning crew to work; (3) Document date and time of last symptom and clearance to return to work; (4) Review [when possible] any reportable AGE cases among passengers or crew reported after the food employee's illness onset for epidemiologic link/connection.
Ensure the food employee's supervisor or person in charge conducts an assessment of food prepared or served by the food employee while symptomatic and take appropriate corrective actions. Document corrective actions taken as a result of the assessment.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Deck 14 - Serenity Portside Whirlpool Shower
|
|
Violation:
A shower did not activate when the button was pressed more than a dozen times. The activation started to work before the plumber arrived to fix the issue.
|
|
Recommendation:
Ensure showers provide potable water at a temperature not to exceed 43°C (110°F) during normal operations. Install showers within 10 meters (33 feet) of every entry point to each RWF. For beach entry RWFs, install a minimum of one showerhead per 10 meters (33 feet) of perimeter within 10 meters (33 feet) of the beach perimeter. Install a minimum of one shower at each water slide staircase entrance.
|
|