Skip directly to site content Skip directly to page options

Inspection Detail Report

  Advanced Search |  Ship Scored 100 |  Green Sheet  |  CDC Home |  VSP Home
 
Cruise Ship: Carnival Freedom Cruise Line: Carnival Cruise Lines, Inc. Inspection Date: 04/25/2009 Inspection Score: 100
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 33
Site: Other-Dinning Rooms
Violation: There were a few waiter stations with recessed grout at the coving and deck tile juncture.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 33
Site: Other-Dinning Rooms
Violation: There were a few waiter stations with open seams at the wait station side panel/carpet juncture. The open seams were soiled with food debris.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, are maintained in good repair.
Item No.: 33
Site: Galley-Walk-in Freezer (Room 38)
Violation: There were four holes in the back bulkhead panel.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 27
Site: Galley-Appetizer Preparation
Violation: The seams around the buffalo chopper data plate were soiled.
Recommendation: Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 33
Site: Galley-Center Galley
Violation: The deck below the port spice rack was soiled.
Recommendation: Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
Item No.: 33
Site: Buffet-Forward/Aft Beverage Stations
Violation: The floor of the technical spaces below the coffee machines had bubbled and peeled paint.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 33
Site: Buffet-Forward/Starboard Grill Pantry
Violation: There was heavy ice accumulation on the deck of walk-in freezer #53.
Recommendation: Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
Item No.: 25
Site: Buffet-Forward/Starboard Grill Pantry
Violation: There was a wiping cloth stored in an ashtray and placed inside the deckhead ventilation diffuser panel.
Recommendation: Ensure that wiping cloths that are in use for wiping food spills are used for no other purpose.
Item No.: 21
Site: Galley-Supper Club
Violation: There were two folding card tables which were rusting and had damaged edges. Per staff the tables were used in the dinning area to store soiled items.
Recommendation: Ensure that nonfood-contact surfaces of equipment and utensils are designed and constructed to be durable and to retain their characteristic qualities under normal use conditions. Ensure that nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning are constructed of a corrosion-resistant, nonabsorbent, and smooth material.
Item No.: 33
Site: Galley-Dishwash
Violation: There was an open void at the bottom of the fire doors. The void space was soiled with food matter and other debris.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 34
Site: Buffet-Beverage Station
Violation: The was a leak in one water line in the technical space below the juice machine.
Recommendation: Ensure that a plumbing system in a food area is maintained in good repair.
Item No.: 33
Site: Bar-Lobby Storage Room
Violation: Soft sealant was used as coving at the deck/baseboard juncture.
Recommendation: Ensure that bulkheads and deckheads have smooth, hard finishes, and light colored surfaces.
Item No.: 21
Site: Bar-Lobby Storage Room
Violation: The shelving unit had numerous small openings and other features, making it difficult to clean.
Recommendation: Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 10
Site: DO NOT USE (whirlpool/spa)-Deck 9 Mid-ship Starboard
Violation: The main drain was damaged. There was no water in the whirlpool.
Recommendation: Repair the main drain prior to opening the whirlpool.
Item No.: 10
Site: Recreational Water Facilities-Spa Pool
Violation: The pool section of this facility was deeper than one meter. There was no shepherd's hook or flotation device.
Recommendation: Provide a shepherd's hook and flotation device.
Item No.: 41
Site: Housekeeping-Lido Aft passenger Ladies Toilet Room
Violation: The tissue dispenser to exit the toilet room was mounted on the inner door. The inner door no self-closing and the dispenser was not visible or accessible. There was no means to exit the outer door without the use of bare hands.
Recommendation: Equip public toilet facilities so that persons exiting the toilet room are not required to handle the door with bare hands. This may be accomplished by methods such as locating paper towel dispensers at sinks and waste containers near the room door, installing mechanically operated doors, door removal, or other effective means.
Item No.: 08
Site: Potable Water-Crew Whirlpool Fill Line
Violation: The distance between the reduced pressure backflow prevention assembly and the drain funnel was less than two times the diameter of the vent.
Recommendation: Ensure that air gaps are at least twice the diameter of the delivery fixture opening and a minimum of 3 cm (1 inch).
Item No.: 09
Site: DO NOT USE (whirlpool/spa)-
Violation: The free bromine residual was less than 4.0 ppm for more than two hours at the mid-port whirlpool on December 29, 2008 and January 2 and 4, 2009. The free bromine residual was less than 4.0 ppm for more than two hours at the mid-starboard whirlpool on December 30, 2008 and at the aft-port whirlpool on January 9, 2009. There was no explanation on the charts.
Recommendation: Ensure that whirlpool spas are maintained at a free residual chlorine of >3.0 mg/L (ppm) and <10 mg/L (ppm), or a free residual bromine of >4.0 mg/L (ppm) and <10 mg/L (ppm).
Item No.: 08
Site: Potable Water-
Violation: The hose connections by the handwash stations in the garbage room and engine change room were not listed in the cross-connection control program. These connections were adequately protected.
Recommendation: Ensure that the cross-connection control program includes a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency.
*Inspections scores of 85 or lower are NOT satisfactory
Vessel Sanitation Program